6ES5 102-8MA01
Siemens SIMATIC S5 6ES5 102-8MA01 CPU 102
The Siemens 6ES5 102-8MA01 is the CPU 102 central processing unit for the S5-100U in the SIMATIC S5 family. It takes 24 V DC and provides an internal 9 V DC supply for the I/O modules. The early specifications that list the 8MA01 give an internal RAM capacity of 1,024 statements and support for EPROM or EEPROM memory submodules.
The CPU runs the STEP 5 program and reads and writes machine signals through the I/O modules. Check the full part number when comparing a spare with the CPU 100, CPU 103 or later CPU 102 8MA02. Siemens’ later 2,048-statement RAM table applies to the 8MA02.
24 V input and 9 V I/O supply
The early 8MA01 specifications give an input range of 18–34 V DC. The 24 V feed connects to L+ and M. If the cabinet uses a PS 930, a PS 931 or another 24 V power supply, use the cabinet drawings to trace the CPU feed and field load circuits separately. Verify the grounding connection against the installation diagram.
Mounting rail and I/O row
The CPU clips onto the S5-100U DIN rail. The 6ES5 710-8MA31 is one rail used in this system. Before removal, record the order of the modules and the bus units to the right of the CPU, such as the 700-8MA11 screw-terminal unit or 700-8MA21 crimp-terminal unit.
Hardware revisions and slot assignments
For the 6ES5 482-8MA13 24 V DC module with 16 inputs and 16 outputs, Siemens specifies revision 5 or later of the CPU 102 8MA01 and slots 0–7. Check the address tables for other cards, including the 420-8MA11 input module and 451-8MA11 output module. Siemens excludes slot 7 when using a CP 521 SI communications processor with this CPU.
STEP 5 program, memory and PG connection
Keep a copy of the running STEP 5 project and record the part number of the fitted S5 memory submodule. Choose an S5 programming cable that matches your PG setup. Before replacing the CPU, record the current program, battery status and RUN/STOP indications on the S5 installation.
Editor’s note
Ask for a label photo that shows both 102-8MA01 and the hardware revision. If the rack uses the 16-input/16-output module, put the revision requirement on the order.
Back up the STEP 5 project before removal. Photograph the fitted EPROM or EEPROM label and record the battery indication.
If the CPU does not power up, have qualified maintenance staff measure L+ to M at the CPU input. Record the reading and inspect the terminals between the supply and the CPU.
If an I/O card is missing from the process image, check the bus connection, slot number and CPU revision together. If a CP 521 SI is fitted, check slot 7 specifically.
When buying used, ask for a PG connection and RUN test. To sell a unit, email a label photo, quantity, known condition and asking price to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 memory submodules
+ SIMATIC S5 manuals and PDF archive
Related topics
+ 6ES5 930-8MD11 PS 930 power supply
Browse SIMATIC S5
+ Used Siemens automation equipment
External references
+ Early S5-100U manual · 6ES5 102-8MA01 specifications, pp. 6-10 and 6-11 (RU)
+ Siemens S5-100U system manual · revision requirement §6.4.2 and 8MA02 specifications p. 14-8 (EN)
+ Siemens CP 521 SI manual · slot restrictions, Table 3-1 (EN)