6ES5 760-0AB11
Siemens 6ES5 760-0AB11 — IM 312 / IM 301-3 Terminating Connector
The Siemens 6ES5 760-0AB11 is a 50-pin passive terminating connector for the appropriate IM 312 and IM 301-3 interface connections in SIMATIC S5 systems. Within an expansion arrangement using S5 interface modules, it is specified particularly for the last IM 312-3 and an unused centralized connection on the IM 301-3.
The manufacturer’s drawing for this exact order number shows a 180 Ω resistor between pins 5 and 12 and a jumper between pins 6 and 22. The connector provides the specified electrical termination at the relevant interface connection.
Where is it fitted?
The S5-135U/155U manual requires this terminator on the last IM 312-3 in a centralized expansion chain. The 6ES5 312-3AB11 and 6ES5 312-3AB31 are examples listed for that arrangement. Assess the expansion chain together with the 6ES5 300-3AB11 IM 300-3 at the other end.
On the 6ES5 301-3AB13 IM 301-3, the 760-0AB11 is specified for an unused centralized connection. Different ports on the same module may require different terminators, so establish the port’s function as well as the module type.
Differences from 760-0AA11 and 760-1AA11
The 6ES5 760-0AA11 is specified for the IM 301-3’s unused distributed connection and is also used in the corresponding termination arrangement at the 6ES5 310-3AB11 IM 310. Similar housings do not establish identical internal connections between the 0AA11 and 0AB11.
For a distributed arrangement using the 6ES5 304-3UB11 IM 304 and 6ES5 314-3UA11 IM 314, the last IM 314 uses the 6ES5 760-1AA11. Select 0AB11, 0AA11 or 1AA11 according to the actual connection point.
Cabling and expansion layout
When reviewing the SIMATIC S5 expansion layout, distinguish centralized connections from distributed connections. Check the S5 cables and connectors, interface models and final connection point together.
The 721 family used for distributed connections includes cables such as the 6ES5 721-0BB00, 6ES5 721-0BC00 and 6ES5 721-0BF00. Select the cable code and length for the interface arrangement. Their presence does not mean that every unused socket takes the same terminating connector.
Resistance checks and fault finding
With the connector disconnected from the system, follow the manufacturer’s pin numbering to check approximately 180 Ω between pins 5 and 12 and continuity between pins 6 and 22. Complete these checks by inspecting the contacts and confirming the correct port. Use the connector markings and drawing rather than guessing pin numbers from the viewing direction.
During PLC debugging for loss of access to an expansion unit, include the connector code, port and end-of-chain position in the checks. For noise immunity and grounding, inspect the cable shield, housing contact and loose connections as well. A communication problem alone does not establish that this connector is faulty.
Editor’s note
Give the suffix a proper look, even on a small part. A 0AB11 and a 0AA11 can look much alike on the bench. Establish the label and the exact socket before changing anything; a wrong connector can lead you into unnecessary work on a serviceable system.
Disconnect the plug before taking resistance measurements. We are checking a resistor between 5 and 12 and a jumper between 6 and 22. Do not expect a continuity beep between every pair: a resistor path and a direct jumper give different readings.
If another expansion rack has been added, check whether the terminator was left in its old position. A change to the end of the chain calls for another termination check. That small detail may save an unnecessary module replacement.
On a used connector, inspect bent pins, loose contacts, housing cracks and securing hardware. The resistance can measure correctly while a poor mechanical fit still causes intermittent contact.
Keep the wider installation in view. Assess the S5 system layout, connecting cable and interface modules together. A photograph of the previous arrangement and a note identifying the first inaccessible rack can be more useful than a long sequence of trial replacements.
OtomasyonAVM resources and PDFs
+ Browse S5 interface modules, S5 cables and connectors and About Siemens S5 PLCs to review the related components together.
+ OtomasyonAVM S5 PDF archive: system manuals and connection documents.
+ OtomasyonAVM S5-115H manual — English, AS 301 / AS 310 connection: printed page 3-28, PDF page 78, Figure 3-26. This section shows the 0AB11 and 0AA11 at different connection points.
Related topics
+ 6ES5 760-0AA11 — terminator for a different port · 6ES5 760-1AA11 — IM 314 line terminator.
+ 6ES5 312-3AB11 IM 312-3 · 6ES5 312-3AB31 IM 312-3 · 6ES5 301-3AB13 IM 301-3.
Browse SIMATIC S5
+ S5 interface modules · S5 cables and connectors · SIMATIC S5 systems.
+ Siemens S5 main page · Used Siemens automation equipment.
Siemens and external references
+ Siemens S5-135U/155U System Manual — C79000-G8576-C199-07, English: printed pages 2-4, 2-7 and 7-23; last IM 312-3, IM 301-3 port selection and pin assignments in Figure 7-16.
+ Siemens S5-115H Manual — EWA 4NEB 811 6111-02b, English: AS 301 / AS 310 connection arrangement in Figure 3-26.
+ Siemens ST 50, 1998 catalog — archived English copy: ordering tables for IM 300/312, IM 301/310, 760 terminators and 721 connecting cables.