6ES5 511-5AA12

6ES5 511-5AA12 – AS 511 PG Programming Interface Module

Siemens 6ES5 511-5AA12 is an AS 511 serial PG interface module connecting a programming device to the control system. Used for programmer connections in S5-130/S5-150 installations, this S5 interface communicates through a passive 20 mA current loop. It provides the programmer connection used when servicing Siemens S5 systems.

Siemens documentation specifies a 5 V supply, 1.6–2 A current consumption and a standard rate of 9600 baud. The PG 670 C manual gives a 0–50 °C temperature range for the 511-5AA11/12/13 group. The module handles serial communication between SIMATIC S5 and the programmer, a separate function from the PLC field inputs and outputs.

Supply and communication

5 V is the module supply; 20 mA describes the communication current loop. Keep these distinct from the cabinet’s 24 V field supply. When assessing S5 power supplies, check the actual rack’s 5 V rail and total current budget. Although the standard rate is 9600 baud, match communication settings to the PG software and system documentation.

A passive current loop requires the correct current source and connections at the other end. Select the PG cable and connectors by their pin assignments and follow the system diagram for grounding and shielding. When selecting an RS-232 or USB serial converter, check specifically for 20 mA current-loop support.

Programmer and cable selection

Siemens Catalog ST 53 lists the 6ES5 731 cable family for connecting a PG 670/PG 675 to PG-AS 511. For a PG 675 connection, select the complete cable order number, pinout and length together. Long-distance figures in the manual apply to the specified cable and arrangement, rather than to an arbitrary extension lead.

Check the intermediate adapter when using a PG 605U. The connection arrangement in Catalog ST 53 uses 984-1UA, order number 6ES5 984-1UA11. When selecting a 6ES5 605-0UA11 or 6ES5 605-0UA12 programmer, verify the adapter, cable and software together; matching connector shapes alone are insufficient.

Installation and connection checks

The arrangement described in the S5-150U manual specifies slot 69 or 79 for AS 511. Do not apply those slot numbers to other S5 racks without checking their documentation. Follow the layout for the actual central unit, and check that the correct front connector is fitted and locked.

If communication fails, start with the supply, cable continuity and active/passive current-loop pairing. Then check programming settings and suitable programming software. During troubleshooting, work through one change at a time so the cause remains identifiable.

Distinguishing other interfaces

511 uses serial communication; 6ES5 501-5AA11 is a parallel interface. Different order numbers such as 6ES5 500-7AA12 and 6ES5 511-5AA14 require checks against the actual PG and central-unit documentation before substitution. The final digits matter as well.

The 6ES5 512-5AA12 and 6ES5 512-5AA21 records provide further interface references. The similarity between 512 and 511 codes does not establish identical functions or hardware compatibility.

Editor’s note

With these older S5 systems, start with the label: the part required here is 6ES5 511-5AA12. “We have a 511 board” is only a starting point. Check the suffix, rack and programmer together so you do not end up chasing missing cables later.

Do not condemn the board as soon as communication fails. This is a passive 20 mA current loop; a healthy board still needs the correct cable and counterpart. Take a little time to check the connection before spending money on another part.

The supply measurement concerns the 5 V rail. Finding 24 V elsewhere in the cabinet does not establish that this board is correctly powered. Have a qualified person check against the diagram so a low or unstable supply is not mistaken for an interface fault.

When buying a used Siemens part, ask for label and connector photographs, plus the PG, cable and control system used for testing. Settle the adapter requirement early if a PG 605U is involved. Knowing the test conditions is more useful than a bare “it works.”

Once connected, resist the urge to write immediately. Where possible, back up the existing program and confirm that you are communicating with the intended system first. An older machine may have no other copy. Look after what is already working before making changes.

OtomasyonAVM resources and PDFs

+ S5 interface modules and PG connection components.

+ S5 programming cables and connectors.

+ S5 PDF archive: system and programming resources. Technical references for this model include the English PG 670 C and German S5-150U manuals; direct manufacturer links appear at the end of this page.

Related topics

+ PG 675 programmer · PG 605U: 605-0UA11.

+ 501-5AA11 parallel interface · 511-5AA14 interface record.

+ Step-by-step PLC communication troubleshooting.

Browse SIMATIC S5

S5 interfaces · S5 cables · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page

Siemens and external references

+ Siemens PU/PG 670 C Manual, 6ES5 998-0BK21, Release 3, English: PDF page 19, technical data for 511-5AA11/12/13.

+ Siemens S5-150U Handbuch, 6ES5 998-0AL11, Issue 11, German: section 2.6, printed page 20 / PDF page 33, AS 511 connection.