6ES5 947-3UA11

Siemens 6ES5 947-3UA11 – S5-155U CPU 947, memory and communication unit

Siemens 6ES5 947-3UA11 is a CPU 947 module for single-processor SIMATIC S5-155U systems. Within the Siemens S5 PLC family, it provides the memory and communication section of the 946/947 CPU assembly. Its integrated user RAM holds 64 Kwords; with 16-bit words, this equals 128 Kbytes.

Assess CPU 947 together with 6ES5 946-3UA11: the 946 provides instruction processing, while the 947 provides memory and the programmer connection. “Single processor” does not mean that the 947 board alone is a complete PLC. Check both parts of the existing S5 CPU assembly, their operating system and the rack arrangement.

Memory structure and expansion

Siemens' CPU 946/947 manual locates the user RAM on CPU 947 and describes parity monitoring. 64 Kwords and 64 Kbytes are different capacities. When selecting memory submodules, check word/byte units and the size of the installed program.

The family manual describes configurations reaching 448 Kwords / 896 Kbytes of user memory with the 355 memory expansion module and suitable submodules. This is not the board's integrated capacity. Verify the additional modules, RAM/EPROM arrangement and installed hardware version together.

STEP 5 and programmer connection

The 946/947 system executes STEP 5 programs. For PLC programming and servicing, CPU 947 has a 15-pin serial PG connection on its front panel; the family specification gives a transfer rate of 9600 bit/s. Use the correct S5 programming cable; do not assume a direct Ethernet or RS-232 connection.

The programmer connection and plant communication modules serve different purposes. Assess external device connections against the installed CP and interface modules. Having an internal communication unit does not mean CPU 947 includes every communication protocol.

Timers, counters and I/O arrangement

The family documentation specifies 256 timers and 256 software counters. These are not physical high-speed counter inputs. Digital inputs, digital outputs and analog modules use separate boards; field voltage, channel capacity and measurement range depend on the selected I/O module.

Supply and physical specifications

The CPU 946/947 family table lists a 5 V DC ±5% supply and approximately 2 A consumption for CPU 947. Power comes from the rack. When assessing the PLC power supply, include the accompanying CPU 946, memory expansion and other modules; 2 A is not the consumption of the complete CPU assembly.

The same table gives CPU 947 dimensions of 20.32 × 233.4 × 160 mm, an approximate weight of 500 g, IP00 protection and an operating range of 0–55 °C. Cabinet ventilation, rack connections and grounding should be included in maintenance checks.

3UA11 versus later versions

3UA11 is the single-processor version. The manual separately describes additional features, including multiprocessing, from 3UA21/22 onwards. Do not automatically assign 6ES5 946-3UA21 or 6ES5 947-3UA21 features to this board. Adding a 923C coordinator does not automatically convert an older 3UA11 assembly into a multiprocessor system.

6ES5 947-3UR11 is a different, R-coded version; UA and UR order numbers must not be treated as interchangeable. Select a spare using the complete label rather than “947” alone. The About Siemens S5 PLC section provides further system context.

Editor's note

Start by photographing the labels on both the 946 and 947. A board fitting into the rack does not establish compatibility; check the complete assembly before mixing revisions.

Because the 947 holds memory, replacing it requires more preparation than an ordinary I/O replacement. Save the working program, data blocks and any 355 memory configuration before considering an overall reset.

If the PG cannot connect, check the S5 cable, converter and programmer settings before condemning the board. A matching 15-pin connector does not make every serial cable suitable.

The INIT FAULT indicator can remain on during startup and should go out when initialization finishes. If it continues flashing, investigate startup conditions, memory and the CPU assembly as part of fault finding; the lamp alone does not identify the defective part.

Disconnect rack power before removing or inserting modules. Inspect rear connectors for bent pins, corrosion and contamination. During measurements, distinguish CPU 947's 5 V supply from the field modules' 24 V circuits.

When buying used Siemens equipment, request the complete 6ES5 947-3UA11 label and a test record from a suitable 946/947 assembly. Check PG communication, program transfer and memory retention after a power interruption before relying on photographs alone.

OtomasyonAVM resources

Browse the 6ES5 947-3UA11 model page, S5 CPU family, memory modules and used Siemens equipment. The manufacturer manual below covers 3UA11 and later versions together; read the version-specific sections separately.

Related topics and models

+ 6ES5 946-3UA11: the instruction-processing section of the same-generation 946/947 assembly.

+ 6ES5 946-3UA21: a later CPU 946 version.

+ 6ES5 947-3UA21: a later CPU 947 version; check compatibility separately.

+ 6ES5 947-3UR11: a different R-coded version; not an automatic direct substitute.

Other S5 equipment

Siemens S5 PLC · CPUs · Memory · Interfaces · Cables · Communication · Used Siemens equipment

Manufacturer document and external reference

+ Siemens S5-155U CPU 946/947 Manual – 6ES5 998-0UM22, Release 07, English: CPU 947 memory/communication functions and memory structure on PDF pages 127–133; specifications on 132–133; INIT FAULT on 142–143; 3UA11 and 3UA21/22 version distinctions on 313–315. The product-ordering summary also lists 6ES5 947-3UA11.