6ES5 500-7AA11

Siemens 6ES5 500-7AA11 — S5-110A / S5-010W Programmer Interface

Siemens 6ES5 500-7AA11 is a 500 programmer interface module for connecting an S5-110A to a PG 630, PG 631 or PG 670 programmer. This PG interface in the Siemens SIMATIC S5 family uses parallel TTL data transfer and a 50-way programmer connection.

The exact 6ES5 500-7AA11 part number also appears in Siemens’ S5-010W spare-parts list for online operation. This S5 auxiliary module establishes the test connection between the CPU and programmer. Match the controller system, PG model and connecting cable together.

Online testing from programmer memory

Siemens’ S5-110A manual describes online testing, correction and commissioning of a program held in the programmer’s RAM. During programming, signal states and the result of logic operation, RLO, can be observed. This allows the PLC program to be examined together with the field inputs and outputs.

Check separately that the program running from the PG agrees with the program in the EPROM. Record the S5 memory submodule label and orientation before removal. A successful online test with the 900-series CPU does not by itself establish that the permanent memory contains the current program.

75 mm rail mounting and CPU memory connection

In the S5-110A arrangement, the interface mounts beside the CPU on a 75 mm sectional rail and has no contact with the backplane bus. It connects through the CPU’s memory-submodule receptacle. When inspecting its position in the S5 rack, check mechanical seating and the CPU-side connection together.

Select the PG connecting cable for the 734 cable family and the installed connector arrangement. Siemens’ ordering list identifies 6ES5 734-0BD20 as the interface-to-programmer cable. A USB-to-RS232 converter alone does not provide compatibility with this parallel TTL connection.

Mint and PE arrangement for the 7AA11

Figure 31 in the S5-110A manual identifies the exact 500-7AA11 with 930-7AA11 and 930-7AA21 power supplies. Connections between Mint, the interface PE terminal and rack earth matter in this arrangement. Check grounding against that drawing rather than applying a generic wiring assumption.

Route the programmer cable separately from external module connection cables. Electrical interference can resemble an interface fault. Observe Siemens’ connection conditions for Mint, and check the existing wiring and equipment power state before connecting or disconnecting the assembly.

Dimensions, weight and power dissipation

Siemens’ S5-010W documentation gives the 500 interface dimensions as 40 × 166 × 150 mm, approximate weight as 0.4 kg and power dissipation as 2 W. Its spare-parts list confirms 6ES5 500-7AA11. Power dissipation should not be treated as a direct current-consumption or external supply-terminal specification.

500-7AA12 and other PG interfaces

6ES5 500-7AA12 is another revision in the 500 interface family. Siemens shows the revisions in separate drawings for their power-supply and interference-suppression arrangements. 6ES5 501-5AA11 and 6ES5 511-5AA12 are different PG interface part numbers; the description “S5 programming interface” alone is insufficient for selecting a replacement.

Addressing, diagnostics and used-unit checks

The 500 interface is not assigned channels or a starting I/O address like a normal input/output module. During fault-finding, test the CPU, PG and cable together. Distinguish other Siemens S5 service equipment, such as the 330 test module, by function; different test devices are not the same connecting component.

For a used unit, inspect the complete identification label, 50-way connection, CPU-side cable, mechanical retainers and PE connection. Then perform an actual online test with a suitable programmer and CPU. A clean enclosure or a connector that fits does not establish reliable data transfer.

Editor’s note

Start with the 7AA11 label and the complete connection assembly. A housing without the CPU-side connector or PG cable may still require additional parts before it can be used on site.

Before working at the CPU memory receptacle, preserve the EPROM identification, orientation and program record. Avoid turning a cable or interface problem into a damaged CPU socket by forcing old connectors.

For intermittent communication, compare the Mint–PE arrangement and cable routing with Figure 31 before condemning the board. A connection that fails when contactors operate also warrants an interference investigation.

Treat this as a 50-way parallel programmer connection. Verify the correct cable rather than trying serial PG cables or converters because the connectors look familiar.

Distinguish the program tested in PG memory from the program in permanent memory. After online testing, check operation from the machine’s own memory as well. Preserve the backup before making program changes.

OtomasyonAVM resources and PDFs

See S5 interface modules, S5 cable types and About Siemens S5 PLC for related information. General documents are collected in the shared Siemens S5 PDF archive. The S5-110A connection instructions and S5-010W document containing the exact 7AA11 part number are linked below.

Related topics

+ 6ES5 500-7AA12 — another 500 PG interface revision.

+ 6ES5 501-5AA11 — PG interface for other S5 systems.

+ 6ES5 511-5AA12 — 511 PG interface.

+ 6ES5 330-7AB11 — S5-110A test module.

Browse SIMATIC S5

S5 interface modules · S5 auxiliary and expansion modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

Siemens S5-110A — Operating Instructions, GWA 4NEB 807 0690-02 — English. Section 1.3.9: parallel PG interface, printed p. 1.9 / PDF p. 13. Section 2.5, Figure 31: exact 500-7AA11 connection arrangement, printed p. 2.8 / PDF p. 27.

Siemens S5-010W — Betriebsanleitung, GWA 4NEB 807 1021-01a — German. PG application: PDF p. 4; dimensions, weight and power dissipation: PDF p. 11; exact 6ES5 500-7AA11 ordering entry: PDF p. 26.