6ES5 458-7LA11
Siemens 6ES5 458-7LA11 – 16-Channel Reed Relay Output Module
Siemens 6ES5 458-7LA11 is a 16-channel Reed relay output module for measurement circuits in SIMATIC S5 systems. Part of the S5 digital output module range, each relay contact is individually galvanically isolated. The detailed system manual specifies 30 V DC maximum switching voltage and 0.5 A continuous current per contact.
A separate 10 W resistive switching limit applies, and inductive loads are not permitted. When selecting measurement-circuit channels, keep the digital and analog signal roles clear: the analog module reads the measurement, while the relay contact opens or closes the circuit.
Apply the 0.5 A and 10 W limits together
0.5 A is not an allowable switching current at every voltage. For a resistive DC load, use P = U × I to check power, voltage and current together. Review the load’s initial and steady operating conditions using the relevant circuit calculations and Ohm’s law.
The manufacturer specifies 60 Hz maximum switching frequency for resistive loads. There is no built-in short-circuit protection; provide appropriate current limiting and protection for the connected circuit.
Relay supply and system consumption
The relay auxiliary supply is 24 V DC, with a permitted range of 20–30 V DC. Consumption from the internal 5 V system rail is 50 mA maximum; external 24 V consumption is 240 mA typical. Check the two supplies separately when assessing the S5 power supply.
Trace the relay auxiliary supply separately from the measurement circuit switched by the contacts. A powered PLC alone does not establish that the relay auxiliary voltage is present and correct.
46-pin front connector and wiring
The module uses a 46-pin front connector. Catalog options include 6ES5 490-7LB21 for screw terminals, 6ES5 490-7LA11 for crimp termination with contacts, and 6ES5 490-7LA21 with contacts selected separately. Match the S5 cables and connectors to the existing installation.
Identify each contact pair and auxiliary supply terminal from the exact LA11 diagram. Check grounding and shielding against the measurement circuit’s reference arrangement. Include cable routing and connector contacts when investigating electromagnetic interference.
Channel testing and commissioning
Compare the output addresses in the PLC program with the field cable numbers. Verify each channel’s open and closed contact states under suitable test conditions. During troubleshooting, check the program command, auxiliary voltage and actual contact conduction together.
Test all 16 channels. In a low-level measurement circuit, a continuity tester’s beep is only a starting point. Check contact stability and its effect on the measurement as well.
LA11, LB11 and LC11 differences
458-7LA11 is the 0.5 A measurement-circuit version. The 458-7LB11 has eight relay outputs and the 458-7LC11 has sixteen, with different contact ratings, load conditions and isolation groups. Channel count or housing appearance alone does not establish interchangeability.
Editor’s note
Check the LA11 marking first. This card is intended to switch small loads in measurement circuits. Do not connect a contactor, valve or other coil directly just because the outputs are relays; the manufacturer does not permit inductive loads.
24 V × 0.5 A equals 12 W, exceeding the 10 W limit. Read the voltage and current ratings together before selecting a load. A short calculation is much easier than finding out later that a sound card has been overloaded.
If the program commands an output but the contact does not change, pause before condemning the card. Measure the 24 V auxiliary supply at the appropriate terminals first. Then trace the address and contact pair, keeping the measurement circuit separate from the relay supply.
A small contact problem can affect a measurement result. Inspect contact stability, connector tightness and the cable together. Also remember that the catalog’s 500 V AC figure is an insulation test voltage, not an operating rating.
When buying a used Siemens card, go beyond a successful test of one output. Record opening, closing and contact stability for all sixteen channels. If relays have been replaced, establish that the fitted parts are appropriate too.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · About Siemens S5 PLC
+ S5-115H system manual – English, our PDF archive. Printed page 17-33 / PDF page 465 gives the exact 458-7LA11 contact, supply and connection data.
+ Siemens S5 shared PDF archive and manuals
Related topics
+ 6ES5 458-7LB11 · 6ES5 458-7LC11: different relay-output versions; assess their load and wiring requirements individually.
+ 6ES5 490-7LB21 · 6ES5 490-7LA11 · 6ES5 490-7LA21: 46-pin front connection options.
Browse SIMATIC S5
+ S5 digital output modules · S5 cables and connectors · SIMATIC S5
+ Siemens S5 PLC · Siemens second-hand equipment
Siemens and external references
+ Siemens S5-115U Manual – English; EWA 4NEB 811 6130-02b. Printed page 15-41 / PDF page 569 identifies the exact LA11 code, 30 V DC, 0.5 A, 10 W and the prohibition on inductive loads.
+ Siemens ST 50, 1998 – English; printed page 3/38 / PDF page 124. Reed relay identification, short-circuit protection, LA/LB/LC comparison and front connector order codes; wiring diagrams are on page 3/40 / PDF page 126.