6ES5 456-7LA11
6ES5 456-7LA11 – SIMATIC S5 16-Channel AC Digital Output Module
Siemens 6ES5 456-7LA11 provides 16 digital outputs rated at 115/230 V AC, 1 A per channel for S5-115U/H systems. Within the S5 digital output module range, it switches AC loads. In a Siemens S5 installation, its outputs have optocoupler isolation in four groups of four.
The permissible load-voltage range is 89–264 V AC at 47–63 Hz, with an operating output current of 40 mA–1 A per channel. For a SIMATIC S5 installation, check the group supplies and the pickup/dropout requirements of loads such as contactors together.
Load selection and OFF-state behaviour
The output stage uses triac semiconductor switching. Siemens specifies typical OFF-state leakage of 3/5 mA. With low-current SSR inputs or electronic loads, check the minimum load current and release requirements. A voltage reading without a load does not establish that the output is faulty.
Outputs cannot be connected in parallel. The maximum switching frequency is 10 Hz, and the specified lamp-load rating is 25/50 W. When changing from a relay-contact output, reassess the load type and wiring arrangement.
Group fuses and fault indicators
Each four-channel group has a 10 A FF fuse. When selecting a semiconductor protection fuse, retain the FF characteristic as well as the correct current rating. A 10 A group fuse does not increase the 1 A channel limit.
The red indicator for each group identifies a defective fuse. During fuse checks, examine the load cable and connected device as well. Find the cause before replacing the fuse, and check the other channels in the affected group.
Front connector and installation
The Siemens ST 50 table specifies a 24-pin front connector for this module. The screw-terminal option is 6ES5 490-7LB11. Match the cables and connectors and S5 subrack arrangement to the existing wiring diagram.
Consumption from the internal 5 V supply is 70 mA maximum, typical power loss is 16 W, and approximate weight is 1.1 kg. Maintain airflow in the control panel and preserve the grounding connections. Group isolation does not provide independent isolation between every channel within the same group.
Addressing and model comparison
Check that the 16 outputs in the PLC program correspond to the field connections. During troubleshooting, assess the program command, group supply, fuse and actual load switching separately. The 456-7LB11 is a different eight-output model, while the 458-7LC11 has relay outputs. A similar order number alone is insufficient for replacement.
Editor’s note
Start with a clear label on this S5 module: 456-7LA11, 16 outputs. The LB11 has a similar name, but needs a separate check. A photograph of the old module’s code and front connections can prevent a mistaken order.
If four outputs stop working together, do not condemn the whole module immediately. Check that group’s supply and FF fuse first. If the fuse blows again, find the load fault rather than fitting a larger fuse.
An OFF-state voltage reading can be misleading. This module has leakage current, so an unloaded measurement does not prove that an output is stuck ON. Check whether the load actually releases, alongside its operating current.
For a used Siemens spare, ask for more than a photograph of illuminated LEDs. Request a test of all sixteen channels with suitable AC loads, and ask which voltage was used for the test.
Take darkened terminals, loose connections or a cracked front connector seriously. Isolate power before replacing the module, record the wiring and check one group at a time. Check the load before connecting a healthy replacement to it.
OtomasyonAVM resources and PDFs
+ S5 digital output modules · 490-7LB11 front connector · S5 subracks.
Related topics
+ 456-7LB11 · 458-7LC11 · Semiconductor fast fuses.
+ Contactors · What is an SSR? · PLC troubleshooting.
Browse SIMATIC S5
S5 digital outputs · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand main page