Siemens 6ES5 441-4UA14 — 32-Channel 24 V DC / 0.5 A Digital Output Module

6ES5 441-4UA14 is a 32-channel, non-isolated, 24 V DC digital output module for Siemens SIMATIC S5 systems. Rated current is 0.5 A per channel, the load supply range is 20–30 V DC, and specified switching current is 5 mA–0.5 A. Its electronic digital outputs switch DC field loads.

This compact module is documented in the S5-135U/155U system manual. Check the installed SIMATIC S5 arrangement, suitable rack and cooling conditions. 441-4UA14 has no galvanic isolation; this distinguishes it from the isolated 451-4UA14, despite matching channel count and current ratings.

Combined load and cooling conditions

The combined current of each eight-output group must not exceed 4 A. The CSA certificate published by Siemens specifies 16 A total at 55 °C with a fan, 8 A at 55 °C without a fan, and 16 A at 35 °C without a fan. The system manual’s 100%/50% load factors support this distinction. Do not use the 32 × 0.5 A calculation independently of cooling conditions.

When selecting relays, contactors and interposing relay coils, assess channel current, pickup behaviour and simultaneous loads together. Maximum switching frequency is 100 Hz for resistive loads; for inductive loads it is 2 Hz at 0.3 A or 0.5 Hz at 0.5 A. Maximum off-state leakage is 0.5 mA, and the lamp-load limit is 0.22 A / 5 W.

Supply, common reference and enable input

Check the field load supply and S5 system power supply separately. The F+ enable input operates relative to the common 0 V reference. The manual’s wiring diagram requires the power supply’s L− terminal to be connected to the reference potential (PE); assess the installation against that diagram.

The enable input is rated at 24 V DC, with a logic-1 range of 13–33 V and rated input current of 5 mA. The enable input is active with jumper X20 inserted; this is the factory setting. In expansion units, also inspect the interface connection and controller fault state alongside the load feeds.

Front connector and fuses

Within the 42-pole connector family, 497-4UA12 is a 20 mm wide crimp connector and 497-4UB12 is a 40 mm wide screw-terminal connector. The manual lists the single-width crimp option for fan-cooled arrangements. When selecting S5 cables and connections, check connector width, module spacing and cooling conditions together.

The 4UA14 version has one 7 A fast fuse per eight outputs. The wiring diagram identifies F+: 1, 1L+: 3, 2L+: 24 and H+: 22. Do not transfer the isolated 451 module’s wiring arrangement directly to this card.

LED indication and H+ signaling

Green LEDs indicate channel status; red LEDs indicate a short circuit within an eight-output group. H+ is the common short-circuit signaling output, rated at 10 mA maximum; it requires a supply at 1L+. Comparing the PLC program command with the output channel measured under load helps fault diagnosis. Establish safe machine conditions before testing.

Comparing versions and related modules

Evaluate 441-4UA11, 441-4UA12 and 441-4UA13 using their complete suffixes. The manual specifies 6.3 A slow-blow fuses for 4UA13 and 7 A fast fuses for 4UA14. Matching 32-channel and 0.5 A ratings do not establish identical hardware details.

441-7LA13 and 441-8MA11 provide comparisons with different S5 module families. The shared 441 designation does not establish direct mechanical compatibility or identical wiring.

Editor’s note

Start by making the 441 versus 451 distinction clear. Both may have 32 outputs, but 441-4UA14 is non-isolated. Keep that difference in view when choosing a spare.

Before adding up “half an amp on every output,” check the fan and cabinet temperature. At 55 °C without a fan, the total limit is 8 A. Think about how the module will operate all day, as well as during the first test.

If a fuse opens, inspect the cables and coils in that eight-channel group first. This version specifies a 7 A fast fuse; do not transfer the 4UA13’s 6.3 A slow-blow rating to it.

If the program commands an output but the load stays off, give the card a fair check. Inspect 1L+/2L+, F+ enable, the common 0 V reference and X20 setting together. A missing connection can make a healthy card look faulty.

For a used card, LEDs alone are not enough; test all 32 channels individually with suitable loads. Photograph the label, address setting and front wiring before removal. Good records are useful at the next maintenance visit.

OtomasyonAVM resources and PDF files

+ S5 PDF files and user manuals · About Siemens S5 PLCs. The main reference is the S5-135U/155U System Manual, Section 8.4.9, printed pages 8-48–8-49 / PDF pages 362–363. The document is in English.

Related topics

+ 441-4UA13 · 451-4UA14 isolated output · 497-4UA12 crimp connector · 497-4UB12 screw-terminal connector · PLC fault diagnosis.

Browse SIMATIC S5

+ S5 digital output modules · S5 racks · S5 interface modules · Siemens S5 PLC · Siemens second-hand equipment.

Siemens and external references

+ Siemens S5-135U/155U System Manual, C79000-G8576-C199-07 — Section 8.4.9, 8-48–8-49 / PDF 362–363: 441-4UA14 specifications, non-isolated design and wiring. Connector table: 8-21 / PDF 335. English.

+ CSA Certificate 1232105 in the Siemens archive, September 11, 2001 — 441-4UA14 entry: 32 outputs, 24 V DC / 0.5 A and total-load ratings according to temperature and ventilation. English.