6ES5 482-3BA11
Siemens 6ES5 482-3BA11 — 16 Inputs / 16 Outputs, 24 V DC, 0.5 A
Siemens 6ES5 482-3BA11 is a compact version K combination module with 16 digital inputs and 16 digital outputs for Siemens SIMATIC S5 systems. Its digital I/O operates at 24 V DC, with outputs rated at 0.5 A per channel. The module is non-isolated. Siemens manual C233-3 places this compact module family within the S5-130K, S5-130W and S5-150K system range.
The module reads pushbuttons, limit switches and suitable inductive sensors, while its outputs can operate appropriately rated interface relays and contactor coils. Check coil voltage, pickup current and inductive switching requirements; a 24 V marking alone does not establish suitability.
24 V inputs: thresholds and response
The specified logic 0 range is −33 to +4.5 V, and the logic 1 range is +13 to +33 V. These are recognition limits; the nominal operating signal is 24 V DC. When choosing between PNP and NPN sensors, check whether the sensor produces the required positive voltage levels and how its reference is connected.
The 16 inputs have a typical current of 8.5 mA, a typical delay of 3 ms and a specified maximum input frequency of 100 Hz. This does not make the module a high-speed encoder counter. Siemens ST 53 references the 6ES5 420-3BA11 class for individual input characteristics; compare both delay and isolation when considering other S5 digital input modules.
Output current, supply and group protection
The permitted output load is 5 mA to 0.5 A per channel, with an external supply range of 20 to 30 V DC. Size the 24 V DC power supply for the connected loads as well as the module itself. For this S5 digital output design, the specified ON-state voltage is at least Up − 2.5 V; the OFF-state voltage is no more than 3 V.
The outputs are short-circuit protected. The manual specifies one T4 A time-delay fuse for each of two output groups and a maximum combined switching current of 4 A per group. Observe both channel and group limits. Short-circuit protection does not replace load-current checks or correctly rated fuses.
Maximum switching rates are 100 Hz for resistive loads, 2 Hz for nominal inductive loads and 11 Hz for lamps, with a maximum lamp load of 5 W. ST 53 refers to the 6ES5 445-3AA11 class for individual output characteristics. The 100 Hz rating should therefore not be applied to every load type.
Non-isolated design and installation
A defining feature of this SIMATIC S5 module is its lack of galvanic isolation. Assess the field supply reference, potential differences within the cabinet and the existing machine wiring together. Wiring assumptions taken from an isolated module should not be carried over to this model.
Approximate dimensions are 19.5 × 244 × 202 mm, weight is 0.3 kg and operating temperature is 0 to +55 °C. Check the S5 rack and front connector and cable arrangement before replacement. Isolate power before removal and record connector orientation, contact condition and the original addressing components.
STEP 5 addressing and related part numbers
The 16 inputs and 16 outputs represent two bytes in each direction. Addresses used in the PLC program must match the module coding plug and the existing system configuration. German STEP 5 notation uses E for inputs and A for outputs. Check the installed Siemens S5 system against its project and hardware records rather than inferring the address solely from the slot number.
6ES5 430-3BA11 is an input module, while 6ES5 451-3AA11 is an output module; their isolation arrangements differ from this combination module. 6ES5 482-4UA11 and 6ES5 482-7LA11 are also separate part numbers. A shared 482 series designation does not establish interchangeability. Verify construction, system support, addressing and wiring separately.
Editor’s note
Start with a clear photograph of the original complete part number and addressing plug. The 482 designation alone is insufficient: the 3BA11 suffix and version K construction are essential when selecting a spare.
If an input LED stays off, check the signal against the module’s own reference before condemning the board. A sensor may have 24 V available while a broken return prevents the correct level from reaching the input.
When several outputs in one group fail together, inspect that group’s supply and T4 A fuse first. Find a shorted coil or damaged cable before fitting another fuse, so the replacement module does not face the same fault.
Do not accept an unloaded voltage reading as a complete output test. Use a suitable test load with known current and observe switching under load. If the voltage collapses when a coil pulls in, check the supply, connector and output stage separately.
For a used module, test all 16 inputs and all 16 outputs, then repeat after warm-up. During PLC fault-finding, compare the addressed bit, channel LED and actual load response. One working channel does not prove that the whole module is serviceable.
OtomasyonAVM resources and PDFs
See About Siemens S5 PLC for system background and S5 digital input/output modules for the module group. General manuals are collected in the shared Siemens S5 PDF archive. The German Siemens document below provides the exact-model technical reference.
Related topics
+ 6ES5 420-3BA11 — comparison of input characteristics.
+ 6ES5 445-3AA11 — comparison of output characteristics.
+ 6ES5 482-4UA11 · 6ES5 482-7LA11 — other 482 variants; interchangeability requires a separate check.
Browse SIMATIC S5
S5 digital input/output modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
Siemens C79000-B8500-C233-3 — German compact digital I/O operating instructions, printed p. 21 / online compilation p. 163; exact 6ES5 482-3BA11 technical page. Manufacturer document reproduced by ManualsLib.
Siemens ST 53, 1985 — German S5-130/S5-150 catalogue; printed pp. 8/11–8/12, PDF pp. 97–98. 482-3 input/output characteristics and comparison tables. Manufacturer catalogue hosted by ADEGIS.