6ES5 436-4UA11
6ES5 436-4UA11 – SIMATIC S5 16-Channel 115–240 V AC Digital Input Module
Siemens 6ES5 436-4UA11 is a 16-channel, 115–240 V AC digital input module in the U-series I/O range for S5-135U, S5-150U and S5-155U systems. Within the S5 digital input module range, it provides two galvanically isolated groups of eight inputs. It transfers 47–63 Hz AC field signals to the Siemens S5 controller.
Typical applications include reading switch positions, contactor auxiliary contacts and compatible sensors in AC control circuits. Contact status is detected through the voltage applied to the input. A 24 V DC sensor output does not directly match this module’s AC input level.
Input voltage and sensor selection
The manufacturer specifies 0–60 V AC for logic 0 and 90–264 V AC for logic 1. Do not treat the intermediate 60–90 V region as a defined logic state. The DC-input 430-4UA11 and lower-voltage AC 435-4UA12 belong to different signal classes.
Typical input current is 15 mA at 115 V AC and 25 mA at 240 V AC; typical input resistance is 10 kΩ. The manual also covers two-wire BERO proximity switches. When selecting an inductive sensor, check operating voltage, OFF-state leakage current and the input’s detection requirements together.
Isolation groups and common connections
The first eight inputs belong to one group and the remaining eight to the other; the channels are not individually isolated. The 436-4UB12, with eight individually isolated inputs, has a different arrangement. Preserve the group commons and grounding scheme shown in the installation drawings rather than joining common terminals arbitrarily.
Input delay and pulse detection
The maximum input frequency as a pulse train is 20 Hz. Rising-edge delay is typically 5 ms, with a 2–15 ms range; falling-edge delay is typically 20 ms, with a 10–25 ms range. CPU scan time adds to the module’s response when evaluating short pulses, so review the reading sequence in the PLC program.
Addressing and channel indicators
The sixteen inputs occupy two input bytes. With a starting byte N, the channel arrangement is I N.0–I N.7 followed by I (N+1).0–I (N+1).7. The actual starting address depends on the address switch and system configuration. Record the existing setting before replacing a SIMATIC S5 module. Comparing the green channel LEDs with the program’s input bits helps separate field-signal faults from addressing problems during troubleshooting.
Front connector and enable connection
Field wiring connects through the S5 front connector. The manufacturer shows the F+/F– enable connection as a jumper in the front connector. Do not apply AC field voltage to these terminals. Match the subrack, connector, common connections and cable markings to the existing installation.
In the shared drawing for the 436-4UA12, the X20 enable-mode setting applies only to 4UA12. Do not transfer that adjustment to 4UA11. Compare the complete order code, hardware revision and front wiring before selecting a replacement.
Simultaneous inputs and panel installation
The manufacturer permits 100% simultaneous inputs with fan cooling. Without a fan, the stated conditions are 75% at 240 V AC, or 100% at 35 °C or at 115 V AC. Assess ventilation and the number of continuously active inputs in the control panel. Dimensions are 40 × 255 × 195 mm, with an approximate weight of 0.55 kg.
The digital section draws typically 100 mA from the 5 V system bus. This is separate from the AC field-input voltage. Trace the system power supply and AC field circuit separately. Select field-circuit fuses and protection according to the cable and circuit design.
Editor’s note
Start by reading the complete label on this S5 module: 436-4UA11. A familiar appearance does not establish the input voltage. Find out what signal the field circuit actually supplies before connecting anything.
If eight inputs disappear together, check the group common, field supply and connector contacts first. One shared wiring fault can look like eight failed channels. Work through those common points before condemning the module.
If an LED stays on while a sensor is OFF, examine both two-wire sensor leakage and the AC voltage remaining at the input. An unloaded voltage reading alone is not enough to decide which component is faulty.
When short pulses are missed, remember the 20 Hz limit and input delays before changing the program. Expecting high-speed counter performance can lead to replacing a healthy module without solving the application problem.
For a used Siemens module, ask whether both groups and all 16 channels were checked on a suitable AC test setup. Examine the connector for heat damage, loose contacts and moisture. Photograph the address setting before removal and isolate power before touching the wiring. Understand the existing arrangement first, then work through it one step at a time.
OtomasyonAVM resources and PDFs
+ S5 digital input modules · S5 cables and connectors · S5 subracks.
+ Siemens S5 shared PDF archive. The exact 4UA11 specifications and wiring appear in the English U Periphery manual below, section 5.7, printed pages 46–47 / PDF pages 249–250.
Related topics
+ 436-4UA12 · 436-4UB12 · 435-4UA12 · 430-4UA11.
+ PLC troubleshooting · Inductive sensors · Grounding information.