6ES5 430-8MC11

Siemens 6ES5 430-8MC11 — 4-Channel, 115 V AC/DC Digital Input Module

6ES5 430-8MC11 is a 4-channel, 115 V AC/DC digital input module in the Siemens SIMATIC S5 family. This S5 digital input module provides optocoupler galvanic isolation, with all four inputs forming one isolation group. Siemens lists the exact model in its S5-90U, S5-95U, S5-100U, ET 100U and ET 200U manuals.

The module transfers appropriately rated relay contact and field status signals to the SIMATIC S5 controller. When selecting compact S5 modules, match the input voltage as well as the channel count. Direct connection of 24 V DC PNP/NPN sensors must not be assumed suitable.

Input voltage, thresholds and delay

The nominal input rating is 115 V AC/DC. The defined “0” range is 0–40 V and the “1” range is 85–135 V. The AC frequency range is 47–63 Hz. Signals between 40 V and 85 V must not be treated as a reliably defined logic state.

Input current at logic “1” is typically 14 mA at 115 V AC or 6 mA at 115 V DC. Inherent delay is typically 10 ms for 0→1 and 20 ms for 1→0. Allow for the CPU scan as well when considering short pulses during PLC programming.

Sensors, wiring and bus unit

Siemens specifies an unshielded cable length of up to 100 m. Appropriately rated two-wire BERO proximity switches may be connected, with an off-state residual current of no more than 5 mA. Check both the voltage rating and residual current of the sensor.

Follow the manufacturer’s L1/N connection diagram when arranging S5 wiring and grounding. Check the installed bus unit and terminal base too. Isolation in one group of four does not mean that each input is isolated from the other inputs.

Addressing and operating conditions

The front markings .0/.4, .1/.5, .2/.6 and .3/.7 indicate alternative bit positions; the module has four physical inputs. Confirm the actual input address against the CPU and station layout, then monitor it with suitable programming software. In ET 200U DP Siemens configuration, the identifier is 4DI or 008 with a 1-byte address scope. These identifiers are not fixed CPU input addresses.

Typical consumption from the internal +9 V system supply is 16 mA; this is not an external field supply rating. Typical power loss is 2.8 W and weight is approximately 210 g. The S5-100U manual specifies ambient temperatures of 0–60 °C for horizontal installation and 0–40 °C for vertical installation.

Differences between nearby order codes

6ES5 430-8MB11 is rated 4 × 24–60 V DC; 6ES5 430-8MD11, 4 × 230 V AC; 6ES5 431-8MC11, 8 × 115 V AC; and 6ES5 431-8MA11, 8 × 24 V DC. A similar housing does not establish interchangeability.

Editor’s Note

Take a moment to read the label before working on an older S5 installation. Make sure it says 430-8MC11 and 115 V; similar housings can easily lead to a mistaken selection.

If an input stops responding, check the field signal, common connections and program address in that order. This simple PLC troubleshooting routine often saves an unnecessary module replacement.

If a two-wire sensor leaves an LED on or flickering, check its off-state leakage current. A voltage reading alone does not establish correct operation; compare the sensor specification with the 5 mA residual-current limit.

When buying a used Siemens module, inspect the label, terminals, latch and base contacts. On a suitable test setup, monitor all four channels individually; one working LED tells only part of the story.

Photograph the wiring and record the addresses before removing anything. When updating a Siemens S5 system, keep input wiring and output modules clearly identified. A few careful notes make the next maintenance job much easier.

OtomasyonAVM resources and PDFs

OtomasyonAVM Siemens S5 PDF page · S5 digital input modules · Siemens S5 main page. For this module, consult S5-100U, printed p. 14-20, or S5-90U/S5-95U, printed p. 15-17. Manufacturer references are provided below.

Related topics

430-8MB11 · 430-8MD11 · 431-8MC11 · 431-8MA11 · PLC troubleshooting.

Navigation

S5 digital inputs · S5 90/110 modules · Siemens S5 · Used Siemens.

Siemens and external references

Siemens S5-100U system manual — printed p. 14-20: exact 430-8MC11 specifications and wiring diagram.

Siemens S5-90U/S5-95U system manual — printed p. 15-17.

Siemens ET 100U manual — printed p. 2-18.

Siemens ET 200U manual — printed p. 8-20; table 4-1 for DP Siemens configuration.