6ES5 477-8EC11
Siemens 6ES5 477-8EC11 – SIMATIC S5 Ex Analog Output Module, 2 × 4–20 mA
The Siemens 6ES5 477-8EC11 is a two-channel 4–20 mA Ex analog output module. Siemens lists it in the SIMATIC S5 analog I/O range for S5-95U and S5-100U controllers and for ET 100U and ET 200U distributed I/O stations. Its original marking is [EEx ib] IIC, with PTB certificate number Ex-91.C.2109.
The module converts the CPU’s digital command into an analog current signal and powers a suitable actuator through the current output. For example, it can send a position command to a process valve positioner. Siemens specifies installing the module outside the hazardous area. A suitable field actuator connects to the intrinsically safe circuit on the hazardous-area side.
Ex bus unit, partition and power supply
The 477-8EC11 fits the 6ES5 700-8EA11 Ex bus unit. The rear marking is D and the bus unit keying is 14. Siemens specifies the 6ES5 497-8EA11 partition to separate the Ex module group from standard modules. Check the full order number on the fitted base. The 700-8MA11, for example, belongs to the standard bus unit range.
The module draws 350 mA from the backplane bus. Check both the station’s total module current and its available address space. If the current budget is insufficient, Siemens lists the PS 935 auxiliary power supply for compatible systems. The S5-100U CPU 100 cannot operate with the PS 935.
STEP 5 scaling and diagnostic addresses
On the Siemens nominal scale, 0 units = 4 mA, 512 units = 12 mA and 1,024 units = 20 mA. In the STEP 5 program, format the output word using the bit layout in Table 11.10 of the manual. A command of 0 units corresponds to 4 mA.
The module uses 4 output bytes for the two channel commands and 4 input bytes for diagnostic readback. On an ET 200U, the two address areas can start at different addresses. Record both separately when checking the I/O assignment.
Red fault LED and related modules
An open circuit in the actuator loop lights the red fault LED and sets bit 0 in the low byte of that channel’s diagnostic input word. During fault diagnosis, interpret the channel bits using Table 11.12. Siemens specifies reading them as digital signals. FB 250 is unsuitable for this diagnostic readback.
The 467-8EE11 is an Ex analog input module that reads 4–20 mA field signals. The 470-8MC12 is a standard two-channel 4–20 mA analog output. When selecting a spare, compare the Ex marking, bus unit code and diagnostic addresses as well as the signal range.
Editor’s note
Record the module and base labels together. The photograph should show the 477-8EC11 order number, the Ex marking and the 700-8EA11 base code.
Write down the addresses for both channels. Match each output command and its diagnostic readback to the corresponding channel in the PLC project.
Check the complete circuit. Review the Ex documentation for the module and field device alongside the cable and the approved plant circuit drawing.
Read the channel diagnostics when the red LED lights. Confirm that the open-circuit bit points to the same loop as the actuator that stopped responding.
Bench-test both outputs. With a suitable test setup, record how each channel responds to the 4, 12 and 20 mA commands.
OtomasyonAVM resources and PDFs
OtomasyonAVM S5 PDF archive · Siemens S5 PLC guide · S5 Ex analog input and related hardware
Related topics
437-8EA12 Ex NAMUR input · 457-8EA12 Ex digital output · 700-8EA11 Ex bus unit
Site navigation
Siemens SIMATIC S5 › S5 CPUs and modules › S5 analog modules
External references
Siemens S5-100U Ex I/O manual – 477-8EC11, Section 11.8.2 (PDF)
Siemens ET 200U manual – 477-8EC11 address identifier and I/O allocation (PDF)
PTB Mitteilungen – original Ex-91.C.2109 certificate listing (PDF, German)