6ES5 470-8MA11

6ES5 470-8MA11 Siemens SIMATIC S5 470 Analog Output Module, 2 × ±10 V

The Siemens 6ES5 470-8MA11 is a SIMATIC S5 analog output module for S5-100U and ET 100U systems. Its two galvanically isolated ±10 V outputs convert PLC command words to bipolar voltage signals. The rated full scale is ±1024 units, and the field supply is 24 V DC. Siemens also lists this exact order number in its ET 200U configuration tables.

The module can send a signed reference to a drive or position controller with a ±10 V input. Check the receiver parameters to see how it interprets a negative reference. The 6ES5 470-8MA12 has the same voltage range and a different order suffix. In Siemens’ ET 200U tables, the module delay is 0.1 ms for 8MA11 and 0.15 ms for 8MA12.

Which slot does the module use, and how is it addressed?

On S5-100U installations with a CPU 100, CPU 102 or CPU 103, check the analog slot address. The local analog address space covers slots 0–7, with eight bytes reserved per slot. In slot 0, for example, channel 0 uses bytes 64–65 and channel 1 uses bytes 66–67.

Check the IM 318-CC arrangement on ET 100U and the station interface and DP mode on ET 200U. Check whether the interface label reads IM 318-B 8MB11, IM 318-B 8MB12 or IM 318-B 8MB13. On ET 200U, the module occupies four output bytes. The address ID is 2AQ or 021 for DP Siemens and 2AQ or 097 for DP Standard.

The module fits an S5-100U-style bus unit. The 700-8MA11 screw-terminal unit and the 700-8MA22 crimp-terminal unit are two bus unit versions. When servicing the S5 90/110 module family, match the terminal type and mechanical keying to the installed unit.

How do you wire the 24 V supply and analog outputs?

Connect the 24 V DC field supply to terminals 1 (L+) and 2 (M). The output voltage appears between QV and the corresponding MANA. The receiving device must have an input resistance above 3.3 kΩ.

+ Channel 0 · 3 S+, 4 QV, 5 S−, 6 MANA.

+ Channel 1 · 7 S+, 8 QV, 9 S−, 10 MANA.

For four-wire operation, run the S+ and S− sense leads directly to the QV and MANA sides of the load. This compensates for a voltage drop of up to 3 V per lead. Two-wire operation is suitable when lead resistance is negligible compared with load resistance. At the module, jumper S+ to QV and S− to MANA. Leave unused outputs open.

What voltage does each STEP 5 command produce?

Each channel uses a left-justified, 16-bit two’s-complement output word. At rated scale, −1024 = −10 V, 0 = 0 V and +1024 = +10 V. With the bottom four bits set to zero, −10 V, −5 V, 0 V, +5 V and +10 V correspond to C000H, E000H, 0000H, 2000H and 4000H, respectively.

When monitoring the output word over a PG connection, check the channel address and scaling in the program. If a separate 464-8MC11 analog input module reads the voltage feedback, monitor the feedback value and the written output command separately.

Which signal does each 470 suffix identify?

The 470-8MD11 has two 1–5 V voltage outputs. The 470-8MB11 has two ±20 mA outputs, and the 470-8MC11 has two 4–20 mA outputs. Match the receiving device’s input type and signed voltage range when selecting a spare.

Editor’s note

Read the nameplate. Verify the 8MA11 suffix on the module. If you are considering the same-range 8MA12 as a spare, check its suitability for the station separately.

Record the slot. Before removing the module, record the slot number, the channel addresses in use and, for remote I/O, the DP configuration.

Photograph the jumpers. For two-wire wiring, mark the S+ and S− jumpers for each channel. Record where the signal cable shield is terminated.

Check the common supply first. If both channels are unresponsive, measure 24 V DC across terminals 1 and 2, then check that the CPU is writing to the corresponding output words.

Compare the module and load terminals. When commissioning conditions allow, apply a known reference and measure at QV–MANA and at the receiver input. If the readings differ, trace the terminals and sense leads.

OtomasyonAVM resources and PDFs

About Siemens SIMATIC S5 PLCs · S5 analog modules · S5 station interfaces