6ES5 752-0AA52

Siemens 6ES5 752-0AA52 – CPU928B PG Interface Submodule

The 6ES5 752-0AA52 is identified as a PG interface submodule for the CPU928B in the SIMATIC S5 family. It belongs to the S5 interface module group and is intended for the PG connection between the CPU and a programming device. Check the complete 0AA52 order number together with the CPU revision when selecting a spare.

The CPU928B's standard PG interface is SI1. With a suitable PG submodule, the second serial interface SI2 can also provide PG functionality. This arrangement supports an additional connection for PLC programming, online monitoring and troubleshooting.

Matching the CPU and revision

The 928-3UB11, 928-3UB12 and 928-3UB21 are different CPU928B versions. Record the complete CPU order number and hardware revision, rather than relying on the name “928”.

The ordering table in the later S5-135U/155U System Manual lists the 6ES5 752-0AA53 as the PG submodule. This does not establish unconditional interchangeability between 0AA52 and 0AA53. Assess any substitution against the actual CPU and submodule revisions.

PG connection and cable checks

For S5 programming connections, match both the CPU and programmer ends of the cable. When considering 734-family cables such as the 734-2BD20 and 734-2BF00, check the full cable code, selected port and device-side connection.

A matching connector shape does not establish electrical compatibility. For example, the 752-0AA42 RS422-A/485 submodule and a PG submodule serve different connection functions. Do not substitute a PG cable for a serial data cable.

Differences from other 752 submodules

The 752-0AA22 V.24, 752-0AA12 TTY and 752-0AA62 SINEC L1 are intended for different serial communication functions. Match the PG function, electrical interface and communication method together; membership of the 752 family alone is insufficient.

Assess 0LA-coded submodules such as the 752-0LA52, 752-0LA12 and 752-0LA62 as separate products. Similar appearance does not establish their suitability as replacements for the 0AA52.

Installation and communication diagnosis

The Siemens installation sequence requires switching off the PLC supply, removing the CPU and securing the submodule in its CPU receptacle. Check the connections and fastening points during reassembly. Our Siemens S5 PLC overview explains the general system structure.

If a connection through SI2 cannot be established, check the fitted submodule's function, CPU interface selection and existing DX2 communication parameters. The CPU928B communication manual lists an incorrect submodule or unsuitable parameter assignment among possible causes.

The CPU928B supports parallel use of two PG interfaces, subject to restrictions on certain test and monitoring functions. Access denied on the second PG may be caused by a function running on the other interface. Record the active PG function as part of the diagnosis.

Editor’s note

Write down the CPU's complete code alongside the submodule code before looking for a spare. “It fits a 928” is too little information. Suffixes and revisions matter in these older systems.

Before deciding that the small module has failed, confirm that the cable and programmer work, then check which port you are using. A known working starting point makes the fault much easier to narrow down.

Photograph the submodule, its connections and any jumpers before removal. Similar parts can become difficult to distinguish at the bench; keep a clear record of the original arrangement.

If two devices are online, find out what is running at the other end. Access refused because of an active test or monitoring function should not be mistaken for a hardware failure.

For a used spare, ask for a connection and data-reading trial with your CPU and programmer arrangement where practical. Keep the original module labelled until the checks are complete.

OtomasyonAVM resources and PDFs

+ S5 interface modules and S5 cables and connectors: related submodules and connection parts.

+ About Siemens S5 PLC and PLC troubleshooting: system and maintenance information.

+ Siemens S5 PDF archive: related system manuals. The documents below explain CPU928B PG functionality and interface architecture; the later System Manual lists 0AA53 in its PG submodule ordering table.

Related topics

+ 752-0AA53 · 752-0AA22 · 752-0AA12 · 752-0AA62: PG and other serial interface functions.

+ CPU928B 3UB11 · CPU928B 3UB12 · CPU928B 3UB21: identifying the CPU revision.

Browse SIMATIC S5

S5 interface modules · S5 cables and connectors · SIMATIC S5 CPUs · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens S5-135U/155U System Manual – English, C79000-G8576-C199-07; Section 5.11, interface submodules.

+ Siemens CPU928B Programming Guide – English, 6ES5 998-2PR21; Chapter 11, PG interfaces and parallel operation.

+ Siemens CPU928B/CPU948 Communication – English, C79000-B8576-C277-01; SI2 selection, installation and diagnosis.