6ES5 441-7LA12
Siemens 6ES5 441-7LA12 – 32-Channel Non-Isolated Digital Output Module, 24 V DC / 0.5 A
The 6ES5 441-7LA12 is a 32-channel, 24 V DC / 0.5 A transistor output module for S5-115U systems in the SIMATIC S5 family. Part of the S5 digital output range, it switches DC field loads under CPU control. It has no galvanic isolation (nonfloating). This distinguishes it from the isolated 451 range.
Nominal load voltage is 24 V DC, the permissible operating range is 20–30 V DC, and channel current is 5 mA–0.5 A. Check the power supply load calculation and rack compatibility together. The 0.5 A channel rating does not permit full loading at every ambient temperature.
Common reference and field wiring
The diagram shows four eight-channel supply sections. These are not galvanically isolated groups. For nonfloating modules, Siemens requires an external connection between the field M reference and internal M reference (PE). Check the wiring and grounding against the project and Siemens diagram; do not alter supply links without checking their function.
Load selection and electronic protection
The module has electronic short-circuit protection. When selecting an interface relay, check the coil's continuous current and inrush. Choose circuit fuses to suit the wiring and load. Connecting outputs in parallel to increase current is not permitted. Maximum lamp load is 5 W per channel.
Temperature-dependent load limits
Siemens specifies a load factor of 100% at 25 °C and 50% at 55 °C. The ST 50 footnote applies this to the sum of rated output currents supplied by one L+ connection. For an eight-channel section at 55 °C, the calculation is 8 × 0.5 A × 50% = 2 A. The four sections provide a combined 8 A while respecting each section's limit. A suitable overall current does not justify overloading one section.
Switching limits and off-state response
Maximum switching frequency is 100 Hz for resistive loads, 8 Hz for lamps and 0.5 Hz for inductive loads. Maximum off-state residual current is 1 mA. Check the off-state response of sensitive electronic loads and the operating frequency of coil loads.
46-pole front connector
This module uses a 46-pole front connector. Siemens lists the 490-7LB21 screw-terminal version and the 490-7LA11 46-pole crimp version supplied with 50 contacts. The 490-7LB11 is a 24-pole connector; belonging to the same 490 family does not make it suitable for this module. Specify the termination type and whether the connector is included when ordering.
Address checks and version comparisons
The 32 outputs occupy four output bytes. Verify the actual start address against the rack's addressing arrangement and match it to the PLC program. During testing, check the load response and any digital input feedback. During troubleshooting, examine the output command, relevant L+ supply and M reference together.
The 441-7LA11 and 441-7LA13 have different version codes; compare the complete labels and wiring before replacement. The 451-7LA12 and 451-7LA21 have isolated outputs. Matching 32-channel and 0.5 A ratings do not establish direct interchangeability. Disconnect system and load supplies before removal or installation.
Editor’s note
Start by checking the 441 designation carefully. The 451 range has a similar name but a different isolation arrangement. Keep clear photographs of the original label and front wiring to make spare selection easier.
If one eight-channel section does not work, check its L+ supply and M connection before writing off the card. A loose terminal in an older cabinet can make a healthy module look faulty.
Do not collect all the coils on one section simply because each channel is rated for 0.5 A. The permissible load drops as the cabinet warms up. At 55 °C, allow 2 A per eight-channel section and distribute the loads within that limit.
If a load needs more current, do not join two outputs together. Siemens does not permit parallel output operation on this card. Review the circuit and select a suitable interface for the load rather than straining the module.
Where practical, have all 32 channels checked with suitable loads. Inspect the 46-pole connector too, and correct loose, discoloured or damaged connections before installation. A ready-to-fit connection assembly is as useful as a healthy spare card.
OtomasyonAVM resources and PDFs
+ Siemens S5-115 PDF archive · S5 digital output modules · S5 racks
+ S5 cable types · PLC programming · PLC troubleshooting
Related topics
+ 441-7LA11 · 441-7LA13 · 451-7LA12 · 451-7LA21
+ 490-7LB21 screw-terminal front connector · 490-7LA11 crimp front connector
Browse SIMATIC S5
S5 digital output modules · S5 racks · Siemens S5 PLC · Used Siemens equipment
Siemens and external references
+ Siemens S5-115U Manual – English, 6ES5 998-0UF23: 441-7LA12 technical table and wiring diagram, printed p. 15-31 / PDF 559; nonfloating module connections, pp. 3-30 and 3-40 / PDF 94 and 104.
+ Siemens ST 50 / 1998 – English catalogue: exact-code specifications and L+ load-factor footnote, printed p. 3/36 / PDF 122; connector ordering table, p. 3/38 / PDF 124. Third-party archive copy of a Siemens publication.