6ES5 415-7AA31

Siemens 6ES5 415-7AA31 — 8-Channel, 24–48 V AC / 2 A Digital Output Module

6ES5 415-7AA31 is an 8-channel, galvanically isolated static digital output module for the Siemens SIMATIC S5 S5-110A system. This model in the S5 digital output range has a nominal field voltage of 24–48 V AC, a permissible range of 20–65 V AC and a maximum output current of 2 A per channel.

The board switches suitable low-voltage AC control loads. It uses static outputs; do not treat it as a mechanical relay or 24 V DC output module. When selecting from S5-90/110 modules, verify the complete order code and the S5-110A construction of the existing SIMATIC S5 system.

AC loads and switching limits

Before connecting a contactor or valve coil, check its AC voltage, steady-state current and inrush current. If an interposing relay is used, its coil must also suit this AC output. Maximum switching frequencies are 20 Hz for resistive loads, 11 Hz for lamps and 2 Hz for inductive loads. The AC circuit is interrupted at current zero.

Temperature-dependent total load

Total load capability is 100% at 20 °C and 50% at 55 °C. For eight 2 A outputs, this corresponds to 16 A and 8 A total current at those respective temperatures. Apply the 2 A channel limit together with the module’s temperature-dependent total-load limit.

Short-circuit protection and fusing

The manual specifies an FF 6.3 A very fast fuse when short-circuit protection is required, giving Wickmann No. 19230 as an example. The fuse characteristic matters as much as its current rating. If a fuse opens, inspect the load and wiring; do not substitute a slow fuse for the specified FF characteristic.

Isolation and wiring arrangement

The operating instructions state that all eight outputs of the static modules are floating. When transferring terminal jumpers, check each channel’s field voltage and return path. Compare grounding and field cabling with the existing diagram; inspect old jumpers before connecting independent circuits together.

Maximum stated cable length is 400 m; assess voltage drop and line resistance separately. Internal current consumption from the 5 V supply is 16 mA, power loss is 16 W and approximate weight is 0.68 kg. Field-load power comes from a suitable AC source.

Off-state residual current

Maximum residual current at logic “0” is 5 mA AC. Consider this when interpreting voltage readings with low-consumption loads or high-impedance meters. An off output does not provide safe energy isolation; disconnect the supply before working on field wiring.

Addressing and field tests

Compare the eight channel addresses and terminal sequence with the PLC program. Select programming tools compatible with the S5-110A programmer and interface arrangement. Do not transfer addressing or wiring details from another S5 family without verification.

During troubleshooting, follow the relevant digital input condition, program command, AC load supply and return together. Check the S5 system operating state before testing the output with a suitable AC load. A channel indication or unloaded meter reading alone is insufficient.

Differences from related models

The 6ES5 415-7AB11 is a 115 V AC static output model; the 6ES5 415-7AB21 is rated 220 V AC. The 6ES5 410-7AA11 uses 24 V DC outputs, while the 6ES5 417-7AA21 has relay outputs. Their use around the same S5-110A system does not make their load voltages or switching characteristics identical.

Editor’s note

Start with the AC marking on the label. Do not connect a DC supply out of habit just because the rating includes “24 V”. Matching the coil voltage to the output type is one of the most useful checks before starting.

Photograph the upper and lower terminal rows before removing wires. In an older cabinet, the purpose of existing jumpers may not be obvious. Recording the independent output connections makes replacement easier to follow.

Eight outputs rated 2 A each do not allow the same full loading in a hot cabinet. At 55 °C, the total limit falls to 8 A. Include coils added later and summer cabinet temperatures in the assessment.

A voltage reading on an off output does not automatically condemn the board. This model permits up to 5 mA AC residual current. Interpret the measurement alongside load behaviour, and isolate the supply before touching the wiring.

When buying a used Siemens 415-7AA31, have all eight channels tested with suitable AC loads. A board powering up is only the beginning of the check. A little time spent on every channel now is easier than searching for a missing output after installation.

OtomasyonAVM resources and PDFs

S5 digital output modules · S5-90/110 modules · Siemens S5 PDF page. The technical source for this model is the Siemens S5-110A Operating Instructions, GWA 4NEB 807 0690-02. Page 1.13 covers specifications and the load curve; pp. 2.6–2.7 cover wiring principles. The source is in English.

Related topics

415-7AB11 · 415-7AB21 · 410-7AA11 · 417-7AA21 · What is a fuse?.

Navigation

S5 digital output modules · S5-90/110 modules · Siemens S5 PLC · Used Siemens.

Siemens and external references

Siemens S5-110A Operating Instructions — archived English manufacturer document; p. 1.13: 415-7AA31 column and total-load curve; pp. 2.6–2.7: connections.