6ES5 482-4UA20
6ES5 482-4UA20 – SIMATIC S5 24 V DC Combined Digital I/O Module
Siemens 6ES5 482-4UA20 is a compact U-design digital I/O module for S5-135U/155U systems, supporting 16 inputs plus 16 outputs or 24 inputs plus 8 outputs. Inputs are rated 24 V DC; outputs are rated 24 V DC / 0.5 A. Within the S5 digital input/output module range, this Siemens S5 unit has 32 jointly isolated channels; the individual channels are not isolated from one another.
It combines machine sensor signals with valve, indicator and interposing relay commands on one module. When connecting an inductive sensor or photoelectric sensor, check signal polarity, the reference connection and the program's use of dual-purpose channels as well as the supply voltage.
Input specifications and channel allocation
Channels 0.0–0.7 are outputs, 2.0–3.7 are inputs, and 1.0–1.7 can individually serve as inputs or outputs. Eight selectable channels therefore supplement the sixteen fixed inputs and eight fixed outputs. For the 4UA20 digital inputs, logic 0 is specified as −33 to 7 V, logic 1 as 13 to 33 V, typical input current as 7 mA and typical delay as 0.3 ms. Review PNP/NPN signal differences before assuming that a sensor can connect directly.
Output loading and protection
The transistor digital outputs have a 0.5 A per-channel limit and a 4 A total limit per eight outputs. Assess loading together with cabinet temperature and ventilation. When selecting an interposing relay or contactor coil, include pickup current and inductive suppression in the assessment. A red short-circuit indicator monitors each eight-output section; these sections are not separate galvanic isolation groups.
Supply, front connector and enable
The front connection diagram identifies L+ at pin 3, L− at pins 21 and 42, F+ at pin 1 and F− at pin 2. Check the 24 V DC supply, grounding and field wiring together. With X20 fitted, the enable input is active. Verify F+/F− against the module diagram before treating an enable-related acknowledgment timeout as a failed module.
Addressing and the dual-purpose byte
The module's address switch sets its start address independently of the rack slot. Select a multiple of four from 0 to 252 for the four-byte block. For example, 80 = 64 + 16 gives output byte 80, selectable I/O byte 81 and input bytes 82 and 83. In the PLC program, keep the corresponding output bits at 0 wherever selectable channels are used as inputs. Apply this example only after checking the machine's existing address allocation.
Differences from the 4UA11 and other 482 modules
The 482-4UA20 has no IP 257 connection interface. This is a key distinction when comparing it with the 482-4UA11. The 482-8MA13 has a different mechanical and electrical design. For replacement, match the complete order number, front connection, addressing and installed system rather than relying on the shared 482 designation.
Editor's Note
Before buying a used module, ask for a clear photo of both the label and address switch. Losing the original setting in a SIMATIC S5 cabinet can turn a straightforward spare-module job into a long fault search.
If the outputs will not operate, start with load power, connector seating and the enable circuit. These three checks can save hours of PLC troubleshooting before you condemn the board.
Pay particular attention to the eight selectable channels: writing an output to a channel wired as an input can conflict with its sensor. Sensors on these channels and 1L+ must use the same supply; do not test this arrangement with separate sources.
On the bench, read each input individually and check every output with a suitable test load. A relay should release cleanly as well as pick up; a lit status LED alone does not prove that the output stage works.
When planning spares, match the full order number before the Siemens brand name. Keep a record of the S5 system configuration alongside the machine's program backup. Both will make the next replacement much easier.
OtomasyonAVM resources and PDF files
+ 6ES5 482-4UA20 model page · Used S5 digital input/output models.
+ Siemens S5 PDF archive. In the S5-135U/155U system manual, printed pages 8-12–8-13 cover operating principles, while 8-69–8-71 contain the 4UA11/4UA20 comparison and connection diagram.
Related topics and options to compare
+ 6ES5 482-4UA11: a related model requiring particular attention to the IP 257 interface.
+ 6ES5 420-4UA14: a separate digital input module; using it instead of combined I/O requires a hardware and program review.
+ 6ES5 451-4UA14: a separate digital output module, requiring system redesign rather than direct 482 substitution.
+ Derell B Series PLC: an option to assess for a complete machine control upgrade; it is not a spare module that fits the existing S5 rack.
Navigation
Siemens · Siemens S5 · Digital inputs · Digital outputs · Combined I/O · Racks · PDF files
External references
+ Siemens S5–S7-1500 migration guide: 482-4UA20 hardware description.