6ES5 460-7LA13
Siemens 6ES5 460-7LA13 — 8-Channel Voltage, Current and Pt100 Analog Input Module
The Siemens 6ES5 460-7LA13 is an eight-channel analog input module for the S5-115U/H/F family. Within the S5 analog module range, it supports voltage, current and Pt100 measurement using plug-in 498 measuring range cards in two groups of four channels. In an S5-115U installation, both range cards must match the required signals as well as the main module.
The module transfers field analog inputs to the PLC. A sensor’s voltage or current signal and a Pt100 resistance require different wiring and settings. A key addition in the 7LA13 is the −100 to +100 °C Pt100 climatic measurement option, with approximately 1/40 °C resolution.
Selecting the measuring range cards
The 6ES5 498-1AA11 through-connection card supports ±50 mV, ±500 mV and Pt100. With the main module set to 500 mV/V/mA, the 498-1AA21 provides ±1 V, the 498-1AA61 ±5 V, the 498-1AA31 ±10 V and the 498-1AA41 ±20 mA.
For 4–20 mA, the 498-1AA51 two-wire transducer card and 498-1AA71 four-wire transducer card use different connections. With the 1AA51 fitted, the analog inputs are no longer galvanically isolated from L+. Check the range card, main module setting and transmitter supply arrangement together.
Standard and climatic Pt100 measurement
For Pt100 measurement, Siemens specifies a standard option of −200 to +850 °C and a climatic option of −100 to +100 °C. Climatic mode assigns all eight inputs to that mode and requires 498-1AA11 cards only. Convert resistance to temperature using the Pt100 characteristic. Approximately 0.025 °C resolution does not mean 0.025 °C measurement accuracy.
Siemens states that the 460-7LA12 sensor wiring, range cards and front connector assignments are retained. However, use the 7LA13-specific Pt100 and 50 mV switch settings. In climatic mode, unused inputs are wired in parallel with connected inputs as shown in Figure 10-11; do not automatically apply the standard-mode jumper arrangement.
Supply, front connector and isolation
The external supply is 24 V DC, with a permitted range of 20–30 V DC. On the 46-pin front connector, supply terminals are 1 L+ / 47 L−; channel 0 uses 3 M+ / 5 M−, and channel 1 uses 7 M+ / 9 M−. When checking S5 cables and connectors, also identify the Pt100 current-circuit terminals 11 S+ / 35 S− on the wiring diagram.
The specification qualifies galvanic isolation with “not for Pt100”; the isolation arrangement must be assessed for the selected measurement circuit. Maximum shielded cable length is generally 200 m, reduced to 50 m for the ±50 mV range.
Scan time, data format and diagnostics
At 50 Hz, integration time is 20 ms and single-channel encoding at the nominal value takes up to 60 ms. The specified eight-input cycle is 0.48 seconds. In the PLC program, cyclic/selective acquisition, signed data format and measurement scaling must match the hardware settings.
In climatic mode, a break in the shared IC+/IC− excitation circuit can produce the negative end value and OV overflow status for all inputs. A sensor or measuring-lead break also requires assessment of the affected channel’s F fault status. During PLC troubleshooting, inspect the status bits alongside the displayed temperature.
Differences from other S5 analog modules
The 465-7LA13 has 16 voltage/current inputs or eight Pt100 inputs and is non-isolated. The 463-4UA12 is a different four-input module. The 466-3LA11 provides 16 single-ended or eight differential inputs with a shorter encoding time. Compare the wiring and program before treating any of these as a replacement.
Editor’s note
Do not stop at the main label when checking this module. The codes on the two small 498 cards matter just as much. When buying a used analog module, ask for close-up photographs of both cards so a missing or incorrect range card is clear from the start.
If four channels read incorrectly together, start with that group’s range card and switch settings. A ±5 V circuit and a ±10 V circuit may look similar, but their program scaling differs. Prove one group first, then move to the other. It makes the fault easier to follow.
If every Pt100 reading suddenly drops to the lower limit, check the shared excitation loop and series sensor connections before assuming eight failed channels. One open connection can make the fault look much larger than it really is.
The fine climatic-range resolution is useful, but keep the sensor, cable joints and test instrument in the picture. Check several points against a known reference. You want to establish that the reading is correct, as well as that it changes.
Photograph the range cards, rear switches and front connector before removal, and back up the program where possible. After fitting the replacement, check both channel groups and the wire-break response in order. A few minutes spent recording the setup now will make the next service visit easier.
OtomasyonAVM resources and PDFs
+ About Siemens S5 PLCs and S5 analog modules — our system overview and measurement module pages.
+ Siemens S5 PDF files — our archive of S5 system manuals.
+ S5-115H system manual, English — redundant system architecture and 460/465 family wiring. For 7LA13-specific climatic mode and switch settings, use the S5-115U manual below.
Related topics
+ 6ES5 460-7LA12 — earlier version; check the Pt100 and switch-setting differences.
+ 498-1AA11, 498-1AA31 and 498-1AA51 — through-connection, ±10 V and two-wire 4–20 mA range cards.
Browse SIMATIC S5
+ S5 analog modules · S5 CPU and system group · SIMATIC S5 · Siemens second-hand equipment
Siemens and external references
+ Siemens S5-115U Manual, English — §10.3, 10-16–10-18: exact 7LA13, climatic mode and wiring
+ Same manual — Table 10-1, 10-14: 498 range cards and connection conditions
+ Same manual — 15-46/15-47: 7LA13 front connector and specifications
+ Same manual — Table 10.24, 10-46: climatic-range raw data and fault bits