6ES5 460-7LA11

Siemens 6ES5 460-7LA11 – 8-Channel Isolated Analog Input Module

The 6ES5 460-7LA11 is an eight-channel analog input module in the SIMATIC S5 family, documented by its complete order number in the S5-115H manual. It handles voltage, current and Pt100 measurements. This S5 analog module uses two 498 range cards, each setting the range for four channels.

With suitable range cards, it can acquire current outputs from pressure transmitters, voltage signals or temperature measurements. Identify the analog signal type by checking both the fitted range card and the operating-mode settings.

Measuring range cards

The 6ES5 498-1AA11 supports ±50 mV, ±500 mV or Pt100; the 498-1AA21 provides ±1 V; the 498-1AA31 provides ±10 V; and the 498-1AA61 provides ±5 V nominal ranges. Set the module's rear switches for the selected range as well.

The 498-1AA41 is for ±20 mA, the 498-1AA51 for two-wire 4–20 mA transmitters, and the 498-1AA71 for four-wire 4–20 mA transmitters. Each card covers four inputs, so consider the whole channel group.

Front connector and external supply

The 46-pole front connector uses pin 1 for L+ and pin 47 for L−. The external supply is 24 V DC, with a permissible range of 20–30 V DC. Follow the pin numbers when checking existing S5 cables and connectors.

Measuring pairs are CH0: 3/5, CH1: 7/9, CH2: 15/17, CH3: 19/21, CH4: 27/29, CH5: 31/33, CH6: 39/41 and CH7: 43/45. The first pin in each pair is M+ and the second is M−. Pins 11/35 are S+/S− for the Pt100 current circuit; pins 23/25 are KOMP+/KOMP− for compensation.

Pt100 connection and isolation

Pt100 measurements use a four-wire connection and a 2.5 mA constant-current circuit. Pt100 and thermocouple wiring differs; check the sensor type, compensation and operating mode together.

Galvanic isolation does not apply in Pt100 operation. Using a 498-1AA51 also removes the galvanic separation between the analog inputs and L+. Assess isolation from the complete configuration, including the range cards.

Conversion time and reading values

Integration time is 20 ms at 50 Hz or 16.6 ms at 60 Hz. The specifications for this exact order number give an eight-input scan time of 0.48 seconds at 50 Hz. Integration time and the refresh time of the complete module are different quantities.

Depending on the selected mode, data uses 12 bits plus sign or 13-bit two's complement. CPU access can use FB250, FB252 as appropriate to the S5-115H application, or L PW. Check addressing, representation and status bits together in the PLC program.

For 4–20 mA, the manual's measurement units are 512 at 4 mA and 2560 at 20 mA. The raw word includes left-justified measurement data and status bits; these units are not the numeric value of the directly read word.

Fault behaviour specific to the 7LA11 revision

On the 7LA11, overflow at one measuring point sets OV on all channels. During PLC troubleshooting, avoid concluding that every transmitter has failed. On the 460-7LA12, overflow leaves the other channels' OV bits unaffected. Use the relevant revision information when assessing a 460-7LA13 as well.

Wire-break monitoring requires a suitable 498-1AA11 card and mode selection. On the 7LA11, selecting “No wirebreak signal” suppresses evaluation of the fault bit but does not switch off the test current. Current range cards do not support the same hardware wire-break detection.

The 465-7LA11 has a different input and isolation arrangement. Check more than the similarity of order numbers when choosing a spare. Our Siemens S5 PLC overview provides background on the system structure.

Editor’s note

Check the two measuring range cards as carefully as the main module. A correct main module can still arrive with cards unsuitable for your signals. A photograph of the original assembly makes comparison much easier.

Before removal, take clear photographs of the rear switches and front wiring. It may all seem easy to remember at the bench, but those pictures are welcome companions when you return to the cabinet.

If every channel reports a problem, take a moment before replacing transmitters. Keep the 7LA11's shared overflow behaviour in mind and check the measuring points one at a time.

For an incorrect Pt100 reading, work through the sensor, measuring leads and constant-current circuit first. Finding one poor connection is more useful than replacing a sound module.

When buying a used spare, request low, middle and high-point test results in the range you intend to use. Test every channel where possible; powering up alone does not demonstrate measurement accuracy.

OtomasyonAVM resources and PDFs

+ S5 analog modules and About Siemens S5 PLC: related modules and system information.

+ Siemens S5 PDF archive: system manuals and related documents.

+ S5-115H System Manual – English; 460-7LA11 wiring and specifications. Chapter 7; exact-order-number pin and specification tables on 17-37–17-38.

Related topics

+ 460-7LA12 · 460-7LA13 · 465-7LA11: revision and input configuration comparisons.

+ 498-1AA11 · 498-1AA41 · 498-1AA51 · 498-1AA71: measuring range card selection.

Browse SIMATIC S5

S5 analog modules · SIMATIC S5 CPUs · Siemens S5 PLC · Used Siemens equipment

Siemens and external references

+ Siemens S5-115H Manual – English, EWA 4NEB 811 6111-02b; 7-17–7-27 and 17-37–17-38.

+ Siemens S5-115U Manual – English; comparison with later 460-7LA12/13 revisions.

+ Siemens S5-115F Manual, Volume 1 – English; Chapter 6 analog wiring and range cards.

+ Siemens ST 50 Catalog – English, third-party archive copy; 498 range cards.