6ES5 315-8MA11
Siemens 6ES5 315-8MA11 — IM 315 Two-Tier I/O Expansion Interface
6ES5 315-8MA11 is the IM 315 interface set for connecting one additional I/O tier in Siemens SIMATIC S5 systems. The set consists of two modules permanently interconnected by a 0.5 m cable, providing a two-tier arrangement. This model in the S5 interface module range is used with S5-100U, ET 100U and ET 200U. In ET 200 applications, it links two local I/O tiers of the same station.
Siemens specifies a maximum current of 2.5 A supplied to the expansion tier and typical interface consumption of 1 mA from +9 V. These are different ratings: 1 mA describes the interface’s own consumption, while 2.5 A is the upper limit for the supply passed to the expansion side. Actual available current depends on the host supply and the combined module consumption.
Choosing the tier arrangement
IM 315 allows suitable systems in the S5-90/110 module group to place I/O on a second rail. Siemens ST 50 lists two-tier use with S5-90U, S5-95U and S5-100U. It is not for S5-95F. For three or four tiers, assess the IM 316 — 6ES5 316-8MA12. For suitable applications requiring increased EMC protection, including S5-95F, assess the IM 316F — 6ES5 316-8FA12.
The IM 315’s 0.5 m cable is permanently attached to the set. The separate 712-series cables used with IM 316 are not an extension option for this set. When selecting S5 cables and connectors, match the interface type and the system to which the cable belongs.
Bus units, connection direction and mounting
The local bus connection at the end of each tier connects to the corresponding IM 315 half. Follow the IN/OUT markings and the manual’s connection arrangement. With a 6ES5 700-8MA11 screw-terminal bus unit or 6ES5 700-8MA22 crimp-terminal bus unit, inspect the final bus unit’s ribbon cable, connector seating and rail latch.
Plan the tier positions so the fixed cable remains free of tension and sharp bends. Siemens permits a maximum potential difference of ±1 V between IM 315 and the CPU’s central grounding point. Where separate rails or cabinet sections are used, check grounding and equipotential bonding.
9 V bus supply and field loads
Add the 9 V bus consumption of connected boards such as the 431-8MA11 digital input, 464-8MC11 analog input and 451-8MA11 digital output. Calculate field current for valves, relays and contactors separately. The IM 315’s 2.5 A limit is not a total field-output load rating.
If the installation uses a suitable supplementary supply such as the PS 935 — 6ES5 935-8ME11, follow the system manual for wiring and current calculations. IM 315 carries the existing bus connection to the second tier; it does not create additional supply capacity. If an entire tier stops working, check supply and connection continuity first.
Addressing and checks after expansion
Check the addresses of boards moved to the second tier against the host system’s addressing rules. The I/O addresses in the PLC program, physical module order and any hardware definitions in the configuration software must agree. A neat physical installation does not establish correct addressing.
During troubleshooting, assess the first and second tiers separately. On Siemens S5 systems, check the CPU-side bus supply and connection chain. On ET 200 stations, include the station head and local I/O arrangement. If all second-tier boards disappear together, inspect their shared interface connection and supply before replacing individual boards.
Editor’s note
When buying IM 315, first establish that both halves and the permanently attached cable are included. A photograph may show only one half. Seeing the complete set before ordering is easier than searching for the missing part later.
Photograph the connection direction and the ribbon cable to the final bus unit before removal. Switch off the supply and handle the connectors without force. On equipment of this age, preserving a healthy socket is part of a successful repair.
If the second tier disappears suddenly, do not assume every board has failed. Check the shared connection, 9 V supply and total bus consumption first. One loose plug can make a complete row of healthy boards appear unavailable.
If the 0.5 m cable will not reach comfortably, measure the rail arrangement again instead of pulling it into place. The connectors must remain free of mechanical strain. A greater distance or more tiers calls for the appropriate interface arrangement.
For a set from the used Siemens equipment range, inspect the cable sheath, cable entries, ribbon connections and rail latches. Where possible, request a test with several I/O boards on the second tier. Seeing an input change and an output respond there tells you more than confirmation that the set was fitted.
OtomasyonAVM resources and PDFs
+ S5 interface modules · S5 cables and connectors · Siemens ET 200 range.
+ OtomasyonAVM shared S5 PDF archive · Siemens ET 200 manuals. Consult S5-100U System Manual §14.5 and ET 200U Manual §§8.5 and 3.1 for the exact-code specification, two-tier installation and bus connection.
Related topics
+ IM 316 8MA12 · IM 316F 8FA12 · 700-8MA11 bus unit · 700-8MA22 bus unit · PS 935 bus supply.
Browse SIMATIC S5
+ S5 interface modules · S5-90/110 modules · SIMATIC S5 · Siemens ET 200 · Siemens second-hand equipment.