6ES5 922-3UA11
Siemens 6ES5 922-3UA11 – CPU 922 R Processor for S5-135U/155U
Siemens 6ES5 922-3UA11 is the CPU 922, also known as the R processor, for S5-135U and S5-155U in the SIMATIC S5 family. Designed for arithmetic and closed-loop control involving word processing, this S5 CPU also processes binary signals. It contains 22 KB of internal DB RAM and uses a separate RAM or EPROM submodule of up to 64 KB for program and data blocks.
The programming language is STEP 5, supporting cyclic, time-controlled and hardware-interrupt processing. Record the software used, block versions and current data-block settings when reviewing an installed application. The processor number alone does not describe every feature of the machine’s application.
DB RAM and plug-in program memory
The 22 KB DB RAM is separate from the plug-in program memory. The memory submodule can be a 376 EPROM or 377 RAM unit. Siemens states that DB/DX blocks are loaded into internal DB RAM when the RAM submodule is full or an EPROM is inserted. Check whether memory is included, its capacity and the machine associated with its contents.
PG interface and connection
The CPU has a 15-pin PG connection with a serial transmission rate of 9600 bit/s. It uses a 20 mA TTY current loop. Select a suitable S5 programming cable and interface adapter. When planning an industrial communications connection, check connector type, electrical interface and protocol separately.
Single and multiprocessor operation
CPU 922 supports single-processor operation or systems with up to four CPUs. In a multiprocessor installation, check the applicable system scope, CPU count and address allocation of the installed COR 923A or COR 923C coordinator. Record the other system modules as well; one CPU stopping can affect other processors according to the coordination arrangement.
Power supply, installation and dimensions
The supply is 5 V DC ±5%, with 2.2 A typical consumption on that rail. Do not treat this as a maximum-current rating. Include all modules in the S5 power supply calculation. Dimensions are 20.32 × 233.4 × 160 mm, occupying one CPU slot. Check the rack arrangement and grounding against the installed chassis. Remove and insert the CPU with power switched off.
Timers, counters and fault indicators
The CPU provides 128 timers and 128 counters. Its front panel includes RUN/STOP and QVZ, ADF, ZYK and BASP indicators. During PLC debugging, record whether STOP is continuously lit, flashing slowly or flashing rapidly. Assess these indications together with PG diagnostics during Siemens S5 maintenance.
Comparison with CPU 928 and 928B
6ES5 928-3UA12 and 6ES5 928-3UB12 are separate processor models. Do not assign their memory capacities, operating behaviour or interface hardware automatically to CPU 922. Compare the application’s functions, memory submodule and installed coordination arrangement before replacement.
Communications hardware and project backup
List the station’s S5 communications modules and connections separately from the CPU. A working PG connection alone does not validate every communications application. Keep the program, current data blocks, memory details and communications settings together in the backup record.
Editor’s Note
When buying a used Siemens CPU 922, obtain a clear view of 922-3UA11 and its revision label. Establish whether the memory receptacle is empty and identify any fitted submodule before ordering. Prepare accordingly if program memory is excluded.
Do not interpret 22 KB as the total program capacity. Internal DB RAM and the RAM/EPROM submodule have different roles. Back up current data-block values as well as program blocks from the working machine.
If PG access fails, check the cable, TTY adapter and connection settings before declaring the CPU faulty. Sharing a connector shape does not make every cable suitable for this processor.
In a multiprocessor rack, assess the remaining CPUs when replacing one board. Record coordinator settings, CPU order and I/O ownership. Investigate the cause of BASP rather than bypassing output protection.
Do not use overall reset as the first diagnostic test; it can erase RAM program and data. Record RUN status, PG access, memory reading and application operation separately. Identify the rack and memory submodule used for testing.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 CPU models · S5 memory modules · Shared SIMATIC S5 PDF archive – S5-115 PDF files
Related topics
+ 6ES5 923-3UA11 COR 923A · 6ES5 923-3UC11 COR 923C · 6ES5 928-3UA12 · 6ES5 928-3UB12
Browse SIMATIC S5
+ Siemens SIMATIC S5 · S5 CPU models · S5 memory modules · S5 racks and chassis · Used Siemens equipment
Siemens and external references
+ Siemens S5-135U CPU 921/CPU 922 Manual – 6ES5 998-0UL22, Release 01 (English). Product summary: R processor role, 22 KB DB RAM, maximum 64 KB memory submodule and programming scope. R processor section: memory and PG connection.
+ Siemens S5-135U/155U System Manual – C79000-G8576-C199-07 (English). Section 5.7, printed pages 5-71…5-79: CPU 922 hardware, memory, indicators and specifications. Chapter 6: coordinators.
+ Siemens 6ES5922-3UA11 data sheet – 14 February 2020 (English). Exact order number and CPU 922 system identity; externally archived copy of the Siemens document.