INVT Goodrive800 (GD800) is a modular AC motor drive family for rolling lines, paper machines, port cranes and other heavy-duty applications. It can be configured as a cabinet for a single motor or as a multi-drive system in which several motors share a common DC bus. The series documentation covers 380 V, 500 V and 660 V voltage classes. Current and overload duration depend on the full unit code and its duty cycle.
How do the common DC bus and braking work?
A rectifier feeds the DC bus from the mains. The inverter units draw power from the bus to control their motors independently. The INVT catalogue identifies the GD800-51 power module for common-bus configurations, the GD800-61 diode rectifier and the mains-side GD800-01 LCL filter for suitable four-quadrant configurations. Fibre-optic links connect control and power units in the modular system. The IGBT and PWM guides explain the power stage.
On a winding and unwinding line, for example, another motoring axis can use the regenerative energy from a decelerating axis. Depending on the cabinet design, an active front end can return surplus energy to the mains, or a suitable dynamic braking circuit can dissipate it through a braking resistor. Start by checking the cabinet's single-line diagram for the installed braking arrangement.
Motor control and INVT Studio
Start with what the load requires. A rolling mill can need steady torque at low speed, while speed and torque control can be assigned to different axes on a winding line. If the installation uses vector control, match the motor nameplate data to the parameter record. In a closed-loop system, also check the encoder type and PG feedback card. Consult the manual for the specific unit before running motor auto-tuning.
INVT lists GD800 rectifier and inverter units in its INVT Studio support information. Studio can read, back up and compare parameters. The installed control unit, port and firmware determine which of the manufacturer's listed connection options, serial Modbus or Ethernet UDP, applies to the cabinet.
Manuals and documents
Find this series under INVT Technical Documents › INVT VFD Documents. In the manufacturer's PDFs below, use the hardware manual for module and connection drawings and the installation and maintenance manual for cabinet layout and servicing. For units marked GD800 Pro, match the document to the full Pro-series model code.
Editor's Note
If the cabinet door says GD800, read the module labels too. When you're looking for a spare, separate photos of the rectifier, inverter and control board codes save time.
Before clearing the fault log, write down which axis tripped, its speed and where it was in the cycle. That gives you a better starting point when reading the drive fault codes.
If the alarm occurs during deceleration, look at the stop ramp alongside what the other axes were doing. If two axes on the same bus were braking together, check when the bus voltage rose.
Put the machine name, axis and firmware version in each parameter backup. If a factory reset is ever needed, you'll know which file to start from.
Account for the mains and auxiliary supplies in a common-bus cabinet. Before servicing, qualified personnel should verify isolation and residual voltage using the manufacturer's maintenance procedure.
Related topics
Drive and cabinet selection · Heavy-duty drives · VFD selection criteria · Rated power · Drive losses and heat
Control and protection · Frequency reference · Current limiting · Safe Torque Off (STO)
Other INVT families · GD350 / Goodrive350 · GD5000 / Goodrive5000 · IPE200
INVT brand home › INVT user manuals › INVT VFD drives
Manufacturer references
GD800 hardware manual (PDF, English) · GD800 installation and maintenance manual (PDF, English) · GD800 series catalogue (PDF, English) · Manufacturer's INVT Studio information