GD200 / Goodrive200
INVT GD200 / Goodrive200 Variable Frequency Drive
The INVT Goodrive200 (GD200) is a general-purpose variable frequency drive for induction motors. On fans, centrifugal pumps and conveyors, size the drive for motor current and the way the load operates. If you have an older GD200, read the complete nameplate first. The voltage suffix and G/P ratings show what the unit is rated to drive.
G/P ratings and control mode
The GD200-037G/045P-4, for example, belongs to the three-phase 380–440 V class. The manual lists 37 kW / 75 A output for constant-torque G duty and 45 kW / 92 A for variable-torque P duty. When selecting a drive, consider rated power alongside motor current and the load’s torque characteristics. A suitable centrifugal pump is an example of a P-duty load.
P00.00 selects the control mode. One GD200 manual edition lists V/f control. Another lists SVPWM alongside sensorless vector control (SVC). Match the drive’s menu to the manual for the unit you have. For P02.01–P02.05, record the motor’s nameplate power, rated frequency, speed, voltage and current. If motor auto-tuning is needed, check the test conditions in the manual.
Run command, speed reference and software
P00.01 selects the run command source from the keypad, terminals or communications. P00.06 selects the channel A frequency reference. For cabinet controls, see the notes on three-wire control and sink/source wiring. Depending on the application, the speed reference can also come from preset speeds or a PID loop tracking a process value such as pressure.
INVT lists the GD200 for serial connection with INVT Studio, which reads and backs up parameters and monitors operating values. The P14 group contains settings for Modbus RTU over RS-485. Check the address, baud rate and data format against chapter 10 of the manual. See INVT VFD Software for version information.
Fault history and braking
P07.27–P07.32 hold recent fault types. When recording a fault code, note whether it occurred during acceleration, at steady speed or while stopping. OC1 is overcurrent during acceleration. OV2 is overvoltage during deceleration. For OC1, review the load and acceleration ramp. For OV2, review the deceleration time and the DC bus record. Regenerative energy from the load can raise bus voltage. Use the full model’s hardware table when assessing dynamic braking and braking resistor options.
Editor’s Note
If the old drive still powers up, record its nameplate, terminals and parameters before removal. Tracing the machine’s run command later can take longer than changing the drive.
The bigger kW figure on a dual-rated nameplate is easy to spot. For a conveyor that starts loaded, compare the G-duty current with the motor nameplate.
If the keypad shows RUN and the shaft stays still, look at the requested frequency first. The terminals may be sending a run command while the drive waits for a speed reference from elsewhere.
Before changing the current limit on a motor that struggles at startup, check the entered motor data and the mechanical load.
For an OV2 trip on stopping, write down the recorded bus voltage and the load at the time. A machine that stops smoothly when empty can return more energy in the same time when loaded.
PDF manuals and related INVT ranges
Start with INVT VFD Documents in the OtomasyonAVM archive. In the Goodrive200 manual, chapter 6 covers parameters, chapter 8 covers fault tracking and chapter 10 covers communications. If the nameplate carries the A suffix, use the GD200A manual. GD200-01 is a separate range intended for solar pumping.
INVT brand home › INVT user manuals › INVT VFD drives
External references
INVT Goodrive200 manual, V/f edition (English PDF) · INVT Goodrive200 manual, SVC/SVPWM edition (English PDF) · INVT Studio manufacturer download list