Humidity sensors

Selecting a sensor for reliable humidity measurements
Humidity sensors monitor water vapour in air and provide measurements such as relative humidity. This page covers sensors for air humidity; soil and material moisture require different measurement methods. Selection depends on the operating conditions and the purpose of humidity control, as well as the percentage shown on a display.
Measurement range, accuracy and response time
Measurement range describes the humidity limits over which a device operates. Its accuracy specification describes the expected measurement deviation under defined conditions. A 0–100% RH range does not establish identical accuracy across the entire range or at every temperature. Check typical and maximum error specifications, temperature limits and condensation conditions together.
When selecting a suitable system, focus on the part of the specification that covers your actual operating conditions.
Editor's note: Resolution and accuracy are different specifications. A display showing increments of 0.1% RH does not establish an accuracy of ±0.1% RH. Also, ±2% RH means two percentage points of relative humidity, rather than two percent of the displayed reading. The applicable specification conditions and measurement uncertainty require separate consideration.
Response time describes how quickly the sensor approaches a new value after humidity changes. Specifications such as t63 and t90 use different definitions. Filters, protective caps and low airflow can slow the response. When choosing measurement and control technology, consider more than the sampling rate: frequent data updates do not mean the sensing element responds equally quickly.
How temperature and condensation affect the reading
Relative humidity is temperature dependent. A probe warmer than the surrounding air can indicate a lower relative humidity than the air actually has. Suitable temperature measurement therefore matters alongside humidity measurement. Temperature compensation does not automatically correct poor positioning near sunlight, warm electronics or an enclosure heater.
Check suitability for condensing conditions separately. Measuring high humidity and maintaining reliable measurements when droplets form on the probe are different capabilities. Dust, oil mist, solvents and cleaning chemicals can affect the sensing element. Select appropriate filter and probe materials, and follow the manufacturer's permitted cleaning methods.
Match the output to the control system
A bare sensing element, an electronic module and an industrial humidity transmitter have different connection requirements. Depending on the model, outputs may include 0–10 V or 4–20 mA, Modbus RTU communication or a board-level digital interface. Verify the supply voltage, wiring and controller's analog input type together.
For example, a transmitter configured for 4–20 mA = 0–100% RH represents 50% RH at 12 mA. A different configured scale changes that interpretation. Check scaling in the PLC; for communicating devices, also verify addresses, data formats and units. Providing a humidity measurement does not mean the sensor can directly switch a fan or humidifier; a suitable control output is required.
Calibration, adjustment and long-term stability
Calibration compares the instrument with a suitable reference to determine measurement deviation and uncertainty. Adjustment changes its measurement behaviour to improve agreement with the reference. Treat these as separate operations. Select reference points relevant to the operating humidity range and allow the probe and reference to reach thermal equilibrium. The installation and maintenance plan should also track filter condition, contamination and long-term measurement drift. One calibration interval does not suit every sensor and application.
Evaluate the application and total cost
Greenhouses, storage rooms, ventilation ducts and drying processes have different probe requirements. In industrial applications, consider temperature, contamination, mounting and maintenance access together. Where stable control within a narrow band is required, select the sensor alongside the PID humidity control or on/off control strategy.
Price alone does not establish measurement quality. Compare quotations using equivalent accuracy conditions, output types, protective construction, calibration documentation and replaceable-probe options. A suitable sensor provides the required measurement performance, connects correctly to the system and can be maintained throughout its service life.
Related pages: Humidity control sensors, temperature controllers, humidity control questions.