6ES7 134-4LB02-0AB0
6ES7 134-4LB02-0AB0 – Siemens ET 200S 2AI U High Feature
Series: Siemens SIMATIC DP / ET 200S
Category: Two-channel analog voltage input module
Description and system role
6ES7 134-4LB02-0AB0 is a 2AI U High Feature analog input module for ET 200S stations. It reads two separate voltage signals and transfers their values to the PLC program. Applications include monitoring pressure, level and similar transmitters with voltage outputs. For the fundamentals, see what is an analog signal?
When selecting a spare, check the full order number, transmitter output range, terminal base, project settings and required update time together. Save the existing channel and filter settings before replacement so the new module can be commissioned under the same conditions.
Voltage ranges and resolution
Resolution is 15 bits plus sign in the ±10 V and ±5 V ranges and 15 bits in the 1–5 V range. Input resistance is at least 800 kΩ in all three ranges. See the analog voltage explanation for more on this signal type.
For transmitters with a 0–10 V output, consider the ±10 V channel setting together with PLC scaling; the parameter list does not include a separate 0–10 V option. Also check the transmitter's physical measurement span. The distinction between 0–10 V and 4–20 mA signals is a basic part of selecting the correct input module.
Connections and terminal base
Channel 0 uses terminal 1: M0+ and terminal 2: M0−; channel 1 uses terminal 5: M1+ and terminal 6: M1−. Connect the transmitter's signal output to the corresponding positive and negative measurement terminals. The module does not supply power to the transmitters; field-device power must be arranged separately.
The screw-terminal TM-E15S24-01 and spring-terminal TM-E15C24-01 are among the compatible bases listed in the manual. Check the installed base's full order number and terminal layout. Assess analog cable shielding and grounding against the installation's wiring conditions.
Supply and isolation
The electronic module receives 24 V DC from the ET 200S power module. Maximum L+ current consumption is 55 mA, and module width is 15 mm. Include the other station modules and external transmitter supplies in the power-supply calculation.
The input channels are not galvanically isolated from each other. They are isolated from the backplane bus and L+ supply. For signals coming from different panels, check the measurement reference and the potential difference between grounding points.
Cycle time and filtering
Module cycle time is 0.5 ms with interference suppression disabled. With suppression enabled, it is 21 ms at 50 Hz or 18 ms at 60 Hz. The smoothing setting also affects how quickly changes in the signal are followed. Include the PLC cycle and communication time when assessing the application's overall response.
Diagnostics and troubleshooting
The red SF LED indicates a group fault. Diagnostics cover conditions such as parameter errors, underflow/overflow and wire breaks. Wire-break diagnostics are available only in the 1–5 V range. Deactivate unused channels in the project parameters.
If a reading is incorrect, first compare the transmitter output, channel range and PLC scaling. Then inspect the terminal connections, transmitter supply and shielding. Assess the SF indication together with the detailed diagnostic record in the PLC.
Comparison with the current-input model
6ES7 134-4MB02-0AB0 is the High Feature current-input model for two-wire and four-wire transmitters. Select 4LB02 for voltage measurement and 4MB02 for current measurement. Similar appearance and the same channel count do not establish replacement compatibility; check the transmitter output, wiring and hardware configuration together.
Editor's Note
For a used voltage-input module, ask for measurement results from both channels. A test in the ±10 V range should include negative, zero and positive voltage points. A record that identifies the range, filter setting and terminal base makes it easier to compare the part's measured performance with your application.
PDFs and operating manuals
Visit the Siemens ET 200 PDFs and user manuals section. The main document for this model is the 2AI U HF manual, 04/2007, A5E01076007-01. Use the exact order number in the document when checking terminal assignments, filter conditions and diagnostic settings.