Delta DVP64EH00R2
Delta DVP64EH00R2 · DVP-EH2 PLC with 32 Inputs and 32 Relay Outputs
The Delta DVP64EH00R2 is a PLC main unit in the second-generation DVP-EH2 family. It has a 100–240 V AC supply, 32 digital inputs rated for 24 V DC, 32 relay outputs and a 16k-step program capacity. It reads sensors, runs sequences and switches field loads on conveyors, packaging equipment and assembly machines.
Inputs, outputs and field wiring
Inputs X0–X37 and outputs Y0–Y37 use octal addressing. For example, X10 follows X7. When wiring an inductive sensor, photoelectric sensor or limit switch, check the S/S input common against the PNP or NPN signal circuit.
Delta’s 2014 instruction sheet rates the relay outputs at 2 A per point and 5 A per common for resistive loads. For inductive loads such as a contactor or valve coil, check the coil inrush current, transient suppression and the rating for that load type. Check output-group fusing and short-circuit protection against the panel schematic.
High-speed counting and related Delta models
The 2014 EH2 sheet specifies a 200 kHz input bandwidth for X0, X1, X4 and X5. When connecting an encoder, check its signal level and A/B phases, then confirm the counter address and frequency limit for the chosen mode. The R2 relay outputs are for on/off load control. For pulse commands to a servo drive or stepper motor drive, consult the pulse-output table for the specific CPU.
The DVP64EH00T2 has the same 32 inputs and 32 outputs with transistor switching. The DVP80EH00R2 provides 40 inputs and 40 relay outputs. The DVP64EH00R3 is the EH3 model with the same I/O count. When changing generations, compare the project target, instructions, retained data areas and installed modules.
Programming software and cable
Use WPLSoft or ISPSoft for PLC programming and ladder editing. Select DVP-EH2 as the project target. For ISPSoft, configure and start the serial channel in COMMGR, then select that channel in ISPSoft.
Connect the PC to COM1, the 8-pin mini-DIN RS-232 port. Delta’s DVPACAB230 cable is 3 m long and the DVPACAB215 is 1.5 m long. A PC without a serial port uses a suitable USB-to-RS-232 adapter and its driver. In the software, select the COM number assigned by Windows and match the machine’s existing serial settings.
The RS-485 interface on COM2 connects an HMI panel or other serial field devices. For Modbus RTU on an industrial communication link, match the station address, baud rate, parity and data format across devices.
Editor’s Note
Start by confirming 64EH00R2 on the nameplate. Photograph the supply terminals, relay commons and fitted cards before removing the CPU.
On a used unit, read the program through COM1 and test field communication through COM2 separately. Check the live inputs and switch the relays with a suitable test load.
If an output LED turns on and the load stays off, check the group common and field supply first. Pay particular attention to contacts that frequently switch contactors or valves.
If BAT.LOW is lit, back up the program and required retained data before a planned shutdown. Follow Delta’s instruction sheet for the hardware when servicing the battery.
If encoder counts jump when a motor starts, check the cable route, shield connection and panel grounding. Inspect the drive’s EMC filter connection if one is fitted.