Delta DVP16SP11R

Delta DVP16SP11R – 8-Input / 8-Relay Output Slim PLC Module

Delta DVP16SP11R adds 8 digital inputs and 8 mechanical relay outputs to the right expansion bus of a compatible Delta DVP-S Slim PLC. For Slim CPUs such as DVP-SS2, DVP-SA2, DVP-SX2 and DVP-SV2, confirm the exact model, expansion limits and power budget. The CPU bus supplies 24 V DC to the module electronics. Sensor and load circuits are powered according to the panel design.

Inputs, relay outputs and mounting

Inputs X0–X7 accept 24 V DC at about 5 mA per point, with a 4.7 kΩ input impedance. Delta’s 2026 manual gives an ON threshold above 16.5 V, an OFF threshold below 8 V and a response of approximately 10 ms. All eight inputs share S/S. For a PNP sensor, connect S/S to 0 V. For an NPN sensor, connect S/S to +24 V.

All Y0–Y7 relay outputs share one common, C0. For resistive loads, the 2026 module manual’s wiring section specifies 1.5 A per output and 5 A total at C0, with a load range of 10–240 V AC or 5–30 V DC. The same manual’s product summary and some earlier Delta tables show 250 V AC. This page uses the 240 V AC upper limit from the model-specific wiring section. Relay response is about 10 ms and switching frequency is at most 1 Hz.

The body measures 25.2 × 90 × 60 mm and fits a 35 mm DIN rail. It has removable terminals, I/O indicators and a low-voltage indicator. When choosing a panel power supply for the 24 V field circuits, calculate the total sensor and control load currents separately.

Programming, cable and X/Y addresses

PLC programming takes place in the host using WPLSoft or ISPSoft, depending on CPU support. For the SS2, SA2, SX2 and SV2 models in Delta’s cable guide, use UC-PRG020-12A from PC USB to CPU COM1 RS-232. A PC with a serial port can use UC-MS020-01A. SX2 models with Mini USB can use UC-PRG015-01A. Select the programming cable for the port on the CPU.

The ladder program uses standard X/Y bits. X0–X7 and Y0–Y7 on the module identify local terminal positions. In the Slim arrangement starting at X20/Y20, this module occupies X20–X27 / Y20–Y27 when installed first. DVP X/Y addresses are octal. Verify the project addresses if the CPU or module order changes.

Two field wiring examples

Detecting parts and position on a conveyor. An inductive sensor for metal parts, a photoelectric sensor for boxes and a limit switch for the end position can use the same input group if they match its S/S wiring. Check each sensor’s PNP/NPN type, then verify its NO or NC behavior. Monitor the PLC inputs to confirm the expected changes before enabling movement.

Contactor and indicator control. One output can drive a suitable interposing relay or contactor coil while another drives an indicator lamp on the same supply group. Feed back contactor status to an X input using an auxiliary contact. Use one load supply for the C0 group. Select a suitable fuse and coil suppression. A flyback diode on a DC coil or a suitable RC suppressor or varistor on an AC coil helps reduce electromagnetic interference. Design panel grounding and the emergency stop circuit separately.

Related modules

DVP08SP11R provides 4 inputs and 4 relay outputs. DVP08SN11R provides 8 relay outputs. DVP16SP11T has 8 inputs and 8 NPN transistor outputs, while DVP16SP11TS has 8 inputs and 8 PNP transistor outputs. Compare the terminal layout and load type. For a new control panel, also see Derell PLCs and smart relays.

Editor’s Note

On a used unit, look for the 11R suffix and inspect C0 and the right expansion connector.

If the input LEDs remain off, use a multimeter to verify S/S polarity and the sensor output.

If the Y LED lights but the load remains off, check the C0 supply and the individual relay contact separately.

Eight loads at 0.7 A each total 5.6 A. This exceeds the 5 A limit at C0.

Test each relay contact with a suitable low-voltage load. Investigate sticking or intermittent switching under load before installing the unit.

Route analog, communication and RS-485 wiring away from power wiring. Clear any test output forces before handover.

PDF documents and series links

See our Delta DVP PLC files page for installation, input polarity and common terminal diagrams. The 2026 Module Manual covers DVP16SP11R wiring in section 7.4.14, printed page 7-18, PDF page 142.

DVP16SP11R · DVP Slim digital modules · DVP expansion modules · DVP PLC series · Used Delta PLCs · Delta Automation

External references

Delta DVP Series Module Manual, 2026 · Delta DVP-Slim Instruction Sheet · Delta PLC/HMI Cable Selection Guide