Delta DVP08SN11R

Delta DVP08SN11R – 8-Relay Output Slim PLC Module

Delta DVP08SN11R adds eight relay outputs to the right expansion bus of a compatible DVP-S Slim PLC. The module has 0 inputs and 8 outputs. For host CPUs such as DVP-SS2, DVP-SA2, DVP-SX2 and DVP-SV2, confirm the exact CPU, right-side expansion support and power budget. The CPU bus supplies 24 V DC to the module electronics. The field supply provides the voltage switched by the relay contacts.

Y0–Y7 outputs and C0 common

Eight normally open relay contacts share one C0 common. The resistive load rating is 1.5 A per output and 5 A total at C0. Delta’s model-specific wiring diagram specifies 10–240 V AC or 5–30 V DC. The product summary shows 250 V AC. This page uses the 240 V AC limit given in the wiring section. Use a single load supply for the C0 group.

Relay response is approximately 10 ms and switching frequency is at most 1 Hz. For resistive loads with frequent switching, consider a suitable solid-state relay based on the duty cycle. The module measures 25.2 × 90 × 60 mm and mounts on a 35 mm DIN rail. When choosing a panel power supply for 24 V DC loads, add the currents of loads that can operate together.

Programming, cable and output addresses

PLC programming takes place in the host using WPLSoft or ISPSoft, depending on CPU support. For the SS2, SA2, SX2 and SV2 CPUs listed in Delta’s cable guide, use UC-PRG020-12A from PC USB to CPU COM1 RS-232, or UC-MS020-01A with a serial port. SX2 CPUs with Mini USB can use UC-PRG015-01A. Select the programming cable for the CPU port.

The ladder program controls the eight outputs as Y bits. Y0–Y7 on the body mark local terminals. In a Slim layout that starts at Y20, this module occupies Y20–Y27 as the first output expansion. DVP I/O addresses are octal and can change with preceding modules. During service, check program addresses, industrial communication addresses and field wiring labels separately.

Two field applications

Contactor control and feedback. Connect the start and stop buttons to the CPU or an input module. A Y output can drive a suitable contactor coil or interposing relay within its load rating. Read contactor position on a separate X input using an auxiliary contact. Identify NO and NC contacts in the drawing. An indicator lamp can show a mismatch between command and feedback. Use the machine’s safety circuit for the emergency stop function.

Several loads on one C0 group. The sum of simultaneous load currents must stay within 5 A even if every contact is within its own limit. For example, six resistive loads at 0.9 A total 5.4 A. For coils, also check pickup current and contact life. Select a suitable load fuse. Suppress switching transients using a suitable flyback diode on a DC coil or the manufacturer’s recommended RC suppressor or varistor on an AC coil. Route load wiring away from signal wiring to reduce electromagnetic interference. Follow the panel electrical design for grounding.

Related Delta modules

DVP06SN11R has six relay outputs. DVP08SN11T has eight NPN transistor outputs and DVP08SN11TS has eight PNP transistor outputs. If the application also needs inputs, DVP16SP11R provides eight inputs and eight relay outputs. Check terminal drawings and load limits for each model. For a new panel, also see Derell PLCs and smart relays.

Editor’s Note

On a used module, check the SN11R label, C0 terminal and right expansion connector.

If a Y LED turns on but the load stays off, confirm that the field supply reaches C0.

With the field load and supply disconnected, check the relay contact with a multimeter. Then test each output using a suitable low-voltage load.

When testing a contactor coil, account for pickup current and suppression as well as holding current.

If a load stays on after the output switches off, check for a welded contact or another feed in the field circuit.

Verify Y addresses after replacing a module. Clear any test output forces before handover.

PDF documents and series links

See our Delta DVP PLC files page for terminal and load wiring. The 2026 module manual shows DVP08SN11R wiring in section 7.4.6, printed page 7-11, PDF page 135.

DVP08SN11R · DVP Slim digital modules · DVP expansion modules · DVP PLC series · Used Delta PLCs · Delta Automation

External references

Delta DVP Series Module Manual, 2026 · Delta DVP-Slim Instruction Sheet · Delta PLC/HMI Cable Selection Guide