Delta DVP32XP11R
Delta DVP32XP11R — 16-Input, 16-Relay-Output Expansion Unit
Delta DVP32XP11R is a mixed expansion unit for DVP-ES and DVP-EX PLC systems, providing 16 digital inputs and 16 relay outputs. Its total capacity is 32 I/O points. It uses a 24 V DC supply and requires a host CPU to execute the PLC program. The final R identifies relay outputs.
Power supply and model identification
This 11-series model is DC powered. Connect its supply to the marked 24VDC and 0V terminals using the equipment label and wiring diagram. Check DC supply polarity. The AC-powered DVP32XP00R uses a different power connection. Include the unit and connected field equipment when sizing the power source.
16 digital inputs and NPN/PNP wiring
The inputs accept 24 V DC sink/source signals. The instruction sheet specifies 5 mA input current, an ON level above 16.5 V, an OFF level below 8 V and approximately 20 ms response time. Photocoupler isolation and channel LEDs are provided. Read pushbuttons, limit switches, relay contacts and compatible sensors through these inputs.
Select the S/S common connection for the NPN/PNP sensor type. For an NPN open-collector sensor, connect S/S to +24 V; for a PNP sensor, connect it to 0 V. Connect the sensor output to the assigned X terminal. Check both the output type and common wiring when replacing an inductive sensor or photoelectric sensor.
These standard inputs should not be treated as high-speed counter inputs for fast encoder pulses. Short pulses may be missed because of input response or CPU scanning. Use documented high-speed CPU inputs or a dedicated module for fast counting.
16 relay outputs and common groups
The 16 outputs are relay contacts. Field loads need their own supply; an output terminal does not generate 24 V. The instruction sheet specifies 2 A per output and 5 A total per common group, with switching-voltage limits of 250 V AC / 30 V DC. Load type and contact life must also be considered.
Local output groups: C0 → Y0–Y3; C1 → Y4–Y7; C2 → Y10–Y13; C3 → Y14–Y17. Four outputs each carrying 2 A would total 8 A and exceed the 5 A common-group limit. These local terminal labels are distinct from the actual starting Y address in the CPU project.
Relay response is approximately 10 ms, with a specified switching frequency of up to 1 Hz; CPU scanning also affects actual operation. These outputs are unsuitable for servo pulse trains or fast PWM. Provide suitable suppression for inductive loads and appropriate fusing. Use correctly rated intermediate switching equipment for larger loads.
Host compatibility and X/Y addressing
DVP32XP11R belongs to the ES/EX-generation digital I/O expansion group. Verify the exact host CPU, expansion connector, module order and total system I/O capacity. Do not apply a newer ES2/E2 module’s ordering code or wiring diagram directly to this legacy 11R model.
X and Y addresses use octal numbering: X7 is followed by X10, and Y7 by Y10. For example, as the first digital expansion after an ES CPU with 16 inputs and 16 outputs, this unit normally occupies X20–X37 and Y20–Y37. Confirm the actual allocation against the CPU rules and preceding modules.
Programming software and connection cable
DVP32XP11R receives no separate program. Its I/O is used in the host CPU’s PLC programming project. WPLSoft is a primary option for ES/EX systems. When using ISPSoft, confirm support for the exact CPU and software version. Use the assigned X/Y addresses in the ladder program; analog-module CR configuration does not apply to this standard digital unit.
For a host CPU with an 8-pin mini-DIN RS-232 port, use a suitable UC-PRG020-12A USB programming cable. Alternatively, UC-MS020-01A connects to a PC RS-232 port or an appropriate USB-to-RS-232 converter. Configure the driver, COM port and COMMGR connection where required. The computer cable connects to the CPU; the expansion connection joins the CPU and unit.
The unit is not a standalone RS-485 or Modbus RTU station. Communication and remote monitoring operate through the host CPU. Distinguish the computer programming cable from the expansion connection.
Panel installation and field checks
Approximate dimensions are 155 × 100 × 82 mm (width × height × depth), with a specified operating temperature of 0…55°C. Provide adequate enclosure ventilation. Complete grounding and separate sensor wiring from relay-switched power circuits to reduce electromagnetic interference.
Editor’s Note
Start with the 32XP11R label and the DC supply terminals. Do not transfer mains wiring from a similar-looking 32XP00R. Check the R/T distinction too: relay and transistor output circuits need different load wiring.
For second-hand equipment, inspect the expansion cable, connector, terminals and rail clip. A power LED alone is insufficient evidence of condition. Darkened common terminals or loose connections may only reveal their faults under load.
Test all 16 inputs separately, matching each LED to the expected CPU X address. If several inputs fail together, check S/S and the sensor supply return first. Disconnect power before removing or installing expansion connections.
Test all 16 relay outputs individually with an appropriate fused load. A clicking relay or illuminated Y LED does not prove contact integrity. Check contact voltage drop under load to identify resistive or welded contacts.
If four outputs fail together, inspect that group’s C common, supply and total current. A replacement relay must match more than coil voltage: contact arrangement, ratings, dimensions and isolation clearances also matter. Retest every channel after repair.
Review the machine’s emergency stop and safety relay arrangement. A welded contact can keep a load energised even when the program switches Y off. Safe removal of hazardous energy requires a suitable safety design beyond this standard output unit.
PDF documentation
Use our Delta DVP PLC files page for documentation. The 2013 ES/EX DIDO sheet covers I/O characteristics; Appendix 11.3 of the 2012 programming manual shows the exact model’s terminal layout. The cable guide illustrates the ES/EX host CPU’s computer connection. Compare the document edition with the actual terminal markings.
Related models and navigation
DVP32XP11T has the same point count with transistor outputs; DVP32XP00R provides 16 inputs/16 relay outputs with AC power. DVP24XP11R provides 16 inputs/8 relay outputs, while DVP16XN11R provides 16 relay outputs only. Select by the documented supply, output and terminal differences.
Delta main page | Delta PLC | DVP PLC series | ES/EX expansion modules | DVP32XP11R | DVP PDF files
External manufacturer documents
Delta ES/EX DIDO — 15 August 2013 manufacturer sheet, distributor archive | DVP-PLC Programming Manual — 2012, Revision V, English | Delta PLC/HMI Cable Selection Guide — 2019, English