Delta DVP24XP11T

Delta DVP24XP11T – 16-input, 8-transistor-output ES/EX expansion module

Delta DVP24XP11T is a mixed I/O expansion module for the original DVP-ES/EX family, providing 16 digital 24 VDC inputs and eight NPN open-collector transistor outputs. Its 24 points are the combined input and output count. The connected PLC CPU executes the control program and uses the module to extend field I/O.

Typical duties include additional sensor signals, DC coils and indicator lamps in conveyor, packaging and auxiliary-machine automation. Inputs can monitor an inductive sensor, photoelectric sensor, pushbutton or limit switch. Check NPN switching, load voltage and coil current when selecting output loads.

Model identification and compatibility

In the ordering code, X identifies expansion, P mixed inputs/outputs, 11 the DC-powered H-type construction, and T transistor outputs. DVP24XP11T belongs to the ES/EX expansion module family; use documentation for the actual DVP-ES or DVP-EX host. When moving to ES2/EX2 or another CPU, confirm the exact host code and expansion interface instead of relying on the DVP name alone.

DVP24XP11R has the same 16-input/eight-output count with relay outputs. DVP24XP00T is the AC-powered version, with a different power arrangement. Verify every supply and field terminal before replacing one version with another.

Power supply and digital inputs

The nominal supply is 24 VDC. Size the power supply for the module, sensors and output loads. Distinguish the 24VDC/0V power input from the +24V/24G/S/S sensor-circuit markings. Do not parallel the positive outputs of separate supplies without checking the manufacturer's circuit.

The local inputs are marked X0–X7 and X10–X17. The ES/EX digital expansion sheet specifies 24 VDC, approximately 5 mA, ON above 16.5 VDC, OFF below 8 VDC, and approximately 20 ms response time. These are expansion-sheet values, rather than the CPU's high-speed input specifications. Measure the actual voltage between the input and its appropriate common.

For an NPN sensor, connect S/S to +24 V; for a PNP sensor, connect S/S to 0 V. Connect the sensor signal to its X channel. Check NPN/PNP polarity together with the sensor label and common wiring. Verify that the input LED and corresponding CPU X bit follow the same signal.

NPN outputs and C0–C7 terminals

The local outputs are Y0–Y7. The terminal drawing shows C0–Y0, C1–Y1, C2–Y2, C3–Y3, C4–Y4, C5–Y5, C6–Y6 and C7–Y7 pairs. Connecting C0 alone must not be treated as completing every output common connection. Wire each C terminal according to the model diagram. Separate terminal pairs do not, by themselves, guarantee galvanic isolation between channels.

A typical NPN circuit is +V → DC load → Yn, with the corresponding Cn connected to the load supply's 0 V. The transistor sinks current when enabled. Before driving a relay or contactor coil, compare its DC voltage, continuous current and inrush current with the output rating; use an appropriate interface driver where necessary.

The 2008 ES/EX digital expansion sheet specifies transistor loads up to 30 VDC, with maximum channel current of 0.3 A at 40°C, 0.2 A at 45°C, 0.15 A at 50°C and 0.1 A at 55°C. A common-terminal rating does not override the temperature-dependent channel limit. Eight 0.1 A loads at 55°C total 0.8 A; size the supply and wiring accordingly.

The same expansion sheet lists approximately 15 µs turn-on and 25 µs turn-off. These figures do not establish that the CPU's high-speed pulse functions operate through the expansion outputs. Select appropriate hardware for high-speed encoder counting or servo pulse control.

Use a suitable flyback diode or the coil manufacturer's recommended suppression circuit with DC coils. Provide appropriate circuit fuse protection and do not assume the outputs withstand a load short circuit or reverse connection. Do not connect an AC load directly to a transistor output.

I/O addressing and example arrangements

Inputs use CPU X addresses and outputs use Y addresses. Numbering is octal: X7 is followed by X10. The local X0/Y0 label on the expansion module need not match its starting address in the CPU program.

Example: using the ES/EX sheet's addressing rules, when this module is the first digital expansion of a 14ES or 32ES CPU, its inputs occupy X20–X37 and its outputs Y20–Y27. A 60ES CPU uses different starting points: the same first module occupies X50–X67 and Y30–Y37. Confirm the actual CPU and preceding modules before using these addresses.

Ordinary digital I/O is handled in the CPU's ladder program. No analog scaling or analog-style CR register readout is needed for normal digital operation. Confirm both the correct X/Y addresses and a safe machine state during testing.

Programming software and cables

No separate user program is downloaded to this module. The original ES/EX documentation identifies WPLSoft as the standard programming tool. PLC programming and online monitoring take place through the host CPU. If using ISPSoft, verify that the selected version supports the exact CPU and configure communication through COMMGR. Back up the existing project before changing engineering software.

CPU programming cable: the ES/EX manual lists DVPACAB2A30, 3 m. The 2019 cable guide lists UC-MS020-01A, 2 m and UC-MS030-01A, 3 m for CPU COM1. The connection uses an 8-pin mini-DIN PLC connector and a DB9 RS-232 PC interface. A USB-only computer needs a suitable USB-to-RS-232 adapter and its driver.

The ES/EX CPU diagram also lists UC-PRG020-12A, a 2 m USB programming cable, requiring its compatible USB driver and correct COM selection. These are CPU connections; DVP24XP11T has no independent programming port. The CPU's RS-485 communication connection and the module expansion interface perform different jobs.

CPU-to-module expansion cable: original ES/EX documents identify DVPACAB403, 30 cm as an I/O expansion cable. It is different from the computer programming cable. Isolate power before connecting it, then inspect the correct expansion connector, cable orientation, pins and retaining parts.

Installation and field checks

The expansion sheet lists the DVP24XP11R/T enclosure at approximately 155 mm wide × 100 mm high × 82 mm deep. Use 35 mm DIN rail or the specified screw mounting. Maintain ventilation clearance, separate signal and power cables and provide suitable grounding. Leave terminals marked unused unconnected.

Editor's Note

Read the complete label: 24XP11T. A relay-output or AC-powered unit can have the same 16-input/eight-output count. Compare the power terminals and output technology against the original unit before replacement.

If several inputs fail together, check S/S and the sensor supply first. Trigger each sensor separately and watch both the local LED and its CPU bit. One common-wire fault can look like several failed inputs.

Pay particular attention to C0–C7. If one output works and the next does not, measure its C terminal and load return before replacing the transistor. The individual terminal connections are easy to overlook.

Use a small, known DC test load. For a resistor load, calculate I=V/R and P=V²/R and provide adequate resistor power margin. An unloaded voltage measurement alone does not establish that an output is healthy under load.

When a damaged channel is found, inspect the coil, cable and suppression device too. Back up the CPU program, photograph the module order and establish a safe test arrangement. Remove temporary forces afterward and test every input and each output with its intended load.

Related modules and topics

DVP24XP11R: 16 inputs/eight relay outputs. DVP32XP11T: 16 inputs/16 transistor outputs. DVP16XM11N: 16 digital inputs only. DVP24XN11T: 24 transistor outputs only. These are functional comparisons; confirm power, commons and addressing before treating another model as a replacement.

PDF files and manuals

Follow our Delta DVP PLC PDF files page for documents. The ES/EX general instruction sheet hosted on our site – English, 2006 also lists DVP24XP11T. Read it together with the dedicated ES/EX digital expansion sheet for detailed terminal and load information.

Navigation: DVP24XP11T main page · ES/EX modules · DVP PLC series · Delta PLC models · Used Delta products · DVP PDF files

External references

Delta ES/EX DIDO digital expansion sheet – 8 July 2008, English/Chinese · Delta legacy ES/EX technical manual – model list and wiring, English · Delta PLC/HMI Cable Selection Guide – 2019, English