Delta DVP60EC00R3 PLC | 36 Inputs, 24 Relay Outputs
The Delta DVP60EC00R3 is a 60-point PLC CPU in the DVP-EC3 series. It uses a 100–240 V AC supply and offers 36 digital inputs at 24 V DC and 24 relay outputs. In filling, assembly and conveyor systems, it can read inductive sensors and photoelectric sensors and sequence valves, interposing relays and contactors.
Input addresses and relay commons
The onboard PLC inputs and outputs use octal addresses. Inputs run from X0–X43 and outputs from Y0–Y27. Wire the S/S common for the PNP or NPN sensors in use, following Delta’s sink/source diagram. The 60-point model has removable terminal blocks and relay outputs grouped under C0–C5.
For resistive loads, Delta rates the relay contacts at 2 A per output and 5 A per common. The maximum relay switching frequency is 1 Hz. For inductive loads such as coils, check the load rating, suppression device and fuse separately. The CPU has 60 fixed digital I/O points. For analog signals or additional local I/O, choose a family that supports the required modules.
Delta’s input table lists 20 kHz for X0 and X1. If you use an incremental encoder, check the separate limit for the selected counting mode. The R3’s Y terminals use relays for load switching. For high-speed pulse output, check the transistor model’s supported channel, hardware version and drive input together.
WPLSoft, ISPSoft and program capacity
Use WPLSoft to read the existing Ladder program from the PLC to the PC and save a backup. Delta’s programming manual lists 4K (3,792 steps) for earlier EC units and 8K (7,920 steps) for EC3-8K units at V8.60 or later. When programming, check the full part number and firmware. For units at V8.60 or later, select EC3-8K in ISPSoft and set up serial communication in COMMGR.
Programming cables and serial communications
Use COM1 RS-232 for the PC connection. Delta’s cable guide lists the UC-PRG020-12A for USB-equipped PCs and the UC-MS030-01A for PCs with a serial port. For USB access, install the driver and select the COM port assigned by Windows. See Delta PLC cables for other options.
COM2 RS-485 supports industrial communications. For Modbus RTU, match the station address, baud rate, parity and stop bits at both ends. Before replacing the CPU, record the serial settings and the addresses of connected devices.
Related Delta models
DVP60EC00T3 has the same I/O count and transistor outputs. DVP48EC00R3 provides 28 inputs and 20 relay outputs, while DVP40EC00R3 provides 24 inputs and 16 relay outputs. DVP60ES200R is an ES2 unit with 36 inputs and 24 relay outputs. When moving to ES2, compare terminal layouts, program instructions and communications settings.
Editor’s Note
When buying used, ask for clear photos of the side label and removable terminal blocks.
Back up the program and required data first. If you are buying a spare CPU, compare the firmware versions of both units.
If several outputs in a group go down together, check the common supply and terminal contact before testing individual relays.
When a Y indicator lights, check that the relay contact switches a suitable test load. Disable machine motion for the test.
If communications drop when a variable-frequency drive starts, check the serial cable route, sources of electromagnetic interference and cabinet grounding.
Related topics and PDF files
Delta DVP PLC files · Delta DVP-EC3 series · Delta PLC cables
External references
Delta EC3 instruction sheet (EN PDF) · Delta DVP-PLC programming manual, EC3-8K (EN PDF) · Delta PLC/HMI Cable Selection Guide, section 1.3 (EN PDF) · Delta DVP catalogue, EC3 model table (EN PDF)