Delta DVP20EC00R3

Delta DVP20EC00R3 · DVP-EC3 PLC with 12 Inputs and 8 Relay Outputs

The Delta DVP20EC00R3 is a block-type PLC main unit in the DVP-EC3 family. It runs on 100–240 V AC. Its 20 I/O points comprise 12 digital inputs rated for 24 V DC and 8 relay outputs. It reads sensors, runs sequences and switches field loads on small conveyors, packaging machines and assembly stations.

Inputs, relay outputs and terminal layout

The digital inputs are addressed X0–X7 and X10–X13. In octal addressing, X10 follows X7. When connecting an inductive sensor, photoelectric sensor or limit switch, check the PNP or NPN signal type and S/S input common against the panel schematic.

C0 is the common for Y0–Y3, and C1 is the common for Y4–Y7. Delta’s relay output table specifies 2 A per point and 5 A per common for resistive loads. For a contactor or valve coil, check the coil inrush current, transient suppression and short-circuit protection for the load.

High-speed counting and related Delta models

The model listing specifies two high-speed counter points at up to 10 kHz. When connecting an encoder, check its signal level, input assignment and frequency limit for the selected counting mode. The DVP20EC00R3’s mechanical relay outputs are for on/off control. For high-speed pulse output, check the DVP20EC00T3 transistor outputs against the drive’s input circuit.

The DVP16EC00R3 provides 8 inputs and 8 relay outputs. The DVP24EC00R3 provides 12 inputs and 12 relay outputs. When selecting a spare CPU, compare the sensor count, output groups and serial connections with the machine schematic.

Programming software, memory and connection cable

Use WPLSoft for PLC programming and ladder editing. The older model listing specifies 4K program steps. Delta’s updated manual includes this model in the 8K range for V8.60 or later. Select EC3-8K in ISPSoft for those versions and configure the serial channel in COMMGR.

The PC connects to COM1, the 8-pin mini-DIN RS-232 port. For a USB-equipped computer, use the UC-PRG020-12A cable. Install its driver and select the COM number assigned by Windows. A PC with a physical RS-232 port can use the UC-MS020-01A cable.

The RS-485 interface on COM2 handles industrial communication with an HMI panel and other field devices. On a Modbus RTU link, match the station address, baud rate, parity and data format.

Editor’s Note

On a used unit, check for 20EC00R3 on the nameplate. Photograph the old terminals, especially C0 and C1, before disconnecting them.

On the bench, read the program through COM1 and record the firmware version shown by the software. Use that record to select the 4K or 8K project target.

If an output LED turns on and the load stays off, check the common and field supply first. Verify the contact with a suitable test load isolated from machine motion.

Before fitting a spare CPU, save the program, required retained data and COM2 settings. Check the panel schematic to identify which circuit the emergency stop disconnects.

If inputs fluctuate or serial communication drops when a contactor operates, inspect cable routing and panel grounding. Check the drive’s EMC filter connection if fitted.