Delta DVP10EC00R3
Delta DVP10EC00R3 Relay Output PLC
The Delta DVP10EC00R3 is a compact DVP-EC3 PLC CPU with 6 digital inputs and 4 relay outputs. It runs on 100–240 V AC. It suits small-machine automation tasks such as product counting, conveyor sequencing and valve control.
24 V DC inputs and high-speed counting
Inputs X0–X5 can read an inductive proximity sensor for metal parts, a photoelectric sensor for passing products, or a limit switch for end-of-travel feedback. Use Delta’s wiring diagram to match the S/S input common to the sensor’s PNP or NPN output. The instruction sheet rates the +24V/24G auxiliary supply at 200 mA.
Delta’s electrical input table lists 20 kHz for X0–X3 and 10 kHz for X4–X5. When using a high-speed counter, check the limit for the selected channel and counting mode. For an encoder, also check the encoder output type and input filter.
Four relay outputs and shared C0
Relay outputs Y0–Y3 share C0. Typical loads include an interposing relay, a contactor control circuit or a panel indicator. Delta’s instruction sheet lists 2 A per output and 5 A through C0 for resistive loads. Account for the total current when several loads are on together. The relay outputs have a maximum switching frequency of 1 Hz. For coil loads, select the fuse and coil suppression for the load circuit.
WPLSoft, ISPSoft and COM1
Use WPLSoft for PLC programming, program backup and live Ladder monitoring. Earlier EC3 units are listed at 4K steps. For V8.60 and later, Delta specifies the EC3-8K target in ISPSoft and a capacity of 7,920 steps. Set up the ISPSoft serial connection through COMMGR.
The PLC has one serial port, 8-pin Mini-DIN COM1 (RS-232). For a USB PC, use the UC-PRG020-12A programming cable. Install the driver and select the COM number assigned by Windows. A PC with a DB9 RS-232 port can use the UC-MS020-01A.
A compatible operator panel also uses COM1. Check its RS-232 driver, cable pinout and serial settings. Choose the panel supply to match its own power requirements. Route serial wiring away from motor and contactor cables to reduce electrical interference.
Editor’s Note
When buying used, check for the full DVP10EC00R3 code. Inspect C0 for discoloration and COM1 for bent pins or a loose socket.
If the original CPU still runs, back up its program and any retained values you need. Compare the CPU versions before transferring the project.
If all four loads stop together, check the C0 supply first. For a single faulty output, check the contact on the bench with a suitable low-voltage test load.
On a machine with an HMI, record the panel’s serial settings before connecting a PC to COM1. Change the connection while the machine is in its maintenance state.
Before reinstalling the PLC, check the L/N supply, S/S common and cabinet grounding against the wiring diagram.
Related models and topics
The DVP10EC00T3 has the same 6+4 I/O count with transistor outputs. The relay-output DVP14EC00R3 has 8 inputs and 6 outputs, and the DVP16EC00R3 has 8 inputs and 8 outputs. If the cabinet also needs built-in RS-485, see the DVP20EC00R3 with 12 inputs and 8 relay outputs.
What is a time relay? · RS-232, RS-422 and RS-485 compared · Delta DVP PLC series · Used Delta equipment
Internal references and PDF files
OtomasyonAVM Delta DVP PLC Files
External references
Delta DVP-EC3 installation and wiring sheet (PDF, EN/Chinese) · Delta DVP-PLC programming manual (PDF, EN) · Delta PLC/HMI cable selection guide (PDF, EN) · Delta DVP PLC and TP catalogue (PDF, EN)