Delta AS16AM10N-A
Delta AS16AM10N-A 16-Channel Digital Input Module
Delta AS16AM10N-A is a 16-channel, 24 V DC digital input module for compatible Delta AS200 and Delta AS300 CPUs. Part of the AS digital modules range, it reads position sensors, limit switches and machine status contacts through a removable spring-clamp terminal block.
PNP/NPN sensors, S/S common and input filtering
Delta’s 2024 module manual specifies 24 V DC, 4.2 mA per input. The module supports sinking and sourcing wiring. Check the installation sheet to wire the S/S common for the sensor output and field supply. The 0–15 markings on the terminal block identify the physical channels.
The software filter can be set from 0 to 25 ms and defaults to 10 ms. If the PLC misses a short pulse, check the filter and CPU scan time. When calculating the power budget, account for the AS power supply and field supply in the panel.
Input addressing in ISPSoft
Configure the module in ISPSoft HWCONFIG in the same order as the AS expansion modules to the right of the CPU. Connect the PC using COMMGR and a suitable PLC programming cable. HWCONFIG assigns the addresses automatically. If the module starts at X1.0, its 16 inputs occupy X1.0–X1.15. Check the actual start address in the project and monitor the inputs online.
Related AS digital modules
The AS08AM10N-A provides 8 inputs, the AS32AM10N-A 32, and the AS64AM10N-A 64. These 32- and 64-input models use MIL connectors for field wiring.
For output applications, the AS16AN01T-A uses NPN outputs, the AS16AN01P-A uses PNP outputs, and the AS16AN01R-A uses relay outputs. The AS16AP11T-A combines 8 digital inputs and 8 NPN outputs in one module.
Editor’s Note
When buying used, confirm the AS16AM10N-A label and check that the spring-clamp terminal block is present. The -B suffix identifies the slimmer version.
If signals register on one terminal row only, check the terminal block seating and S/S wiring.
If a channel LED lights but the program misses the signal, monitor that channel’s X address in the PLC.
For intermittent signals, measure the sensor supply under load. Then review the filter setting.
After replacing the module, test all 16 inputs and match each field signal to its X address.