Delta AS08AM10N-A
Delta AS08AM10N-A 8-point digital input module
The Delta AS08AM10N-A provides eight 24 V DC inputs in the Delta AS digital module range. It reads inductive sensors, photoelectric sensors, limit switches and pushbuttons for the PLC program. Field wires connect to a removable spring-clamp terminal block.
S/S wiring and input ratings
Nominal input current is 4.2 mA per channel. Across X and S/S, Delta specifies ON above 15 V DC and OFF below 5 V DC. For standard three-wire sensors, connect S/S to 0 V for PNP or to +24 V for NPN. Select one polarity for sensors sharing the same S/S group. Check NPN and PNP wiring and the 24 V DC supply against the panel diagram.
Input filter and PLC addresses
The software filter is adjustable from 0 to 25 ms. Delta specifies a 10 ms default. A longer filter helps suppress contact bounce. For short pulses, check the filter setting and CPU scan time together.
Fit the module to a compatible AS expansion bus. Select the exact model in ISPSoft HWCONFIG for the AS200 or AS300 project. Connect to the CPU through COMMGR. Match terminal channels 0–7 to the X addresses assigned in the hardware project.
Editor’s Note
Check the AS08AM10N-A nameplate and the condition of the removable terminal block.
Isolate power and verify the sensor’s PNP or NPN type and the S/S connection.
Start by testing one channel with a known-good sensor.
Compare the channel LED with the X bit monitored in the PLC.
For intermittent missed pulses, check the filter and scan time.
Related topics
For higher input counts, the AS16AM10N-A, AS32AM10N-A and AS64AM10N-A provide 16, 32 and 64 inputs respectively. Output options include the AS08AN01T-A for NPN, AS08AN01P-A for PNP and AS08AN01R-A for relay outputs.
AS Series Operation Manual (EN, 2018 archive edition) · Delta PLC accessory PDFs
Delta AS PLC series · Delta PLC models
External references · AS08AM10N-A installation and wiring sheet (2024, includes EN and TR) · Delta AS Module Manual, section 2.4.1 (EN)