Device standards

Device standards

Matching the right standard to the equipment's role

A standard number on industrial equipment is useful, but its value depends on knowing which product, which hazards and which operating conditions it covers. IEC standards address electrical and electronic equipment, while ISO standards cover many fields, including machinery and robot safety. The contactor, PLC, drive and power supply in one automation panel may fall under different product standards.

A practical starting point is to identify the equipment's function, operating environment and intended market first. Then check the applicable part, edition, amendments and scope of the supporting documents. A statement such as “IEC compliant” alone does not identify the tests performed or establish that the complete system has been assessed.

Common rules and product parts for switchgear

The IEC 60947 series concerns low-voltage switchgear and controlgear. IEC 60947-1 provides common rules when referenced by the relevant product standard; the circuits within its scope generally do not exceed 1,000 V AC or 1,500 V DC. Specific parts must also be considered, such as IEC 60947-2 for circuit-breakers and IEC 60947-4-1 for electromechanical contactors and motor starters.

For a motor contactor, checking rated current alone is insufficient. Utilization category, operating voltage, switching duty and protective-device coordination need to be considered together. Selecting a suitable component also does not, by itself, establish that the completed panel or machine meets every applicable requirement.

PLC programming and hardware safety have different scopes

IEC 61131-3 defines the syntax and semantics of programming languages for programmable controllers. Its 2025 edition includes Structured Text (ST), Ladder Diagram (LD) and Function Block Diagram (FBD). Sequential Function Chart (SFC) is defined for structuring the internal organization of programs and function blocks.

Support for programming in accordance with this standard does not automatically establish the PLC's electrical safety or validate a safety function implemented in an application. Programming-language conformity, hardware assessment and application validation are separate matters. For control equipment, relevant particular safety requirements, such as IEC 61010-2-201 used with IEC 61010-1, also need to be considered according to the product's scope.

Safety of measurement and control equipment

The IEC 61010 series addresses safety for electrical test and measurement equipment, industrial process-control equipment and laboratory equipment. The EN 61010 guide provides a useful introduction to its European adoption. The general and particular parts that apply depend on what the equipment actually does.

For a multimeter, measurement category, voltage rating, input protection and suitable probes must be considered together. For a process controller, the supply, insulation, terminals and specified environmental conditions are key considerations. Two instruments with the same supply voltage cannot automatically be assumed suitable for the same measurement location.

Drive safety, EMC and stopping functions

The IEC 61800 series covers adjustable-speed electrical power drive systems. IEC 61800-5-1 addresses electrical, thermal and other safety hazards; IEC 61800-3 addresses electromagnetic compatibility; and IEC 61800-5-2 addresses functional safety of safety-related drive systems. Meeting one part does not automatically establish conformity with the others.

Linear or S-curve acceleration, ramp stopping, coasting and DC injection braking are operating features specific to the product. Their adjustment ranges come from the drive manual and should not be presented as universal standardized values. An ordinary stop command cannot substitute for a separately designed and validated safety function.

Functional safety and the complete robot cell

IEC 61508 provides a basic framework for electrical, electronic and programmable electronic systems that perform safety functions. An assessment involving SIL considers the function's requirements and how the system achieves them. The ISO 13849 approach is also relevant to machinery control systems, depending on the application. Using a component with safety capabilities does not validate the complete function from the sensor to the final control element.

For industrial robotics, ISO 10218-1:2025 focuses on the robot itself, while ISO 10218-2:2025 focuses on industrial robot applications and robot cells. Even where the robot arm is suitable, the gripper, workpiece, surrounding machinery, safeguards and maintenance access need to be assessed together. Component conformity and the safety of the completed application involve different levels of assessment.

Legacy references and conformity markings

IEC 60950-1 is a legacy safety standard for information technology equipment. IEC 62368-1 has replaced it for relevant audio/video and information and communication technology products, but does not automatically apply to every industrial device. Check product scope, the edition accepted in the destination country and any applicable transition arrangements.

UL 508 should likewise not be presented as the single current standard for all industrial control products. Depending on the product category, transitions include UL 60947, UL 61010-2-201 and UL 61800-5-1. UL 508A concerns industrial control panels; component documentation and panel assessment therefore need to be reviewed separately.

CE marking is not a standard number. It is linked to the manufacturer's declaration of conformity with applicable EU product requirements; the required assessment route depends on the legislation covering the product. When reviewing EN standards, also check the relevant adoption, amendments and, where applicable, harmonized-standard status.

Editor's note: “Designed to a standard”, “test report available”, “third-party certified” and “CE marked” do not provide the same evidence. Compare the model identification, standard part, edition, assessment scope and conditions of use in the documents. A certificate for another model, or a report covering unrelated tests, does not establish conformity of the equipment you selected.

What to check when selecting and specifying equipment

Start with the exact model and its intended function, then match the manufacturer's declaration, any certificate and relevant test reports to that model. Check ratings, temperature inside the panel, altitude, pollution degree, mounting orientation and protective requirements against the manual. Documented limitations are part of the product-selection process.

Enclosure protection against dust and water ingress can be addressed through IEC 60529 and IP ratings, while classification of transport, storage and operating environments can be addressed through IEC 60721. An IP rating alone does not describe all temperature, condensation, chemical exposure or vibration conditions. The final choice needs to consider product standards, installation conditions and system requirements together.

Related topics and product groups

For documentation and market distinctions, see UL standards, cUL marking, CSA standards, the National Electrical Code and the Canadian Electrical Code. The industrial standards section provides a broader starting point.

Depending on the application, review the documentation separately for contactors, PLCs and accessories, variable-speed drives, power supplies and control instruments.