Siemens 6ES5 955-3NA11 SIMATIC S5-135U Power Supply
The Siemens 6ES5 955-3NA11 is a PS 955 rack power supply for the S5-135U central controller (ZG 135U) in the SIMATIC S5 family. It takes a 24 V DC input and supplies the CPU and backplane modules from a 5 V DC / 10 A main rail. The front socket marked Test 5 V is for checking rail voltage. The one marked 3 V = 10 A provides a voltage indication of main output current.
If several modules in an S5 central rack go dark together, start with the power supply. In a rack fitted with a CPU 921, CPU 922 or CPU 928, check the 24 V input and the 5 V rail under load before swapping the CPU. The 10 A rating applies to the 5 V main output.
Rack compatibility and replacement parts
Siemens’s later system manual pairs the 6ES5 135-3UA41 central controller with the 6ES5 955-3NA12. The Niemur service list identifies the 3NA12 as the successor to the 3NA11. When assessing a 3NA12 for an existing installation, match the full rack number, hardware revision, rear power and signal connectors, and alarm wiring.
Within the same family, the 6ES5 955-3NC13 is an 18 A unit and the 6ES5 955-3NF11 is a 40 A unit. Both have 24 V DC inputs. Siemens documents the 6ES5 135-3UA11 central controller with the AC-input 6ES5 955-3LC14. Match the rack label, input type and main output rating when choosing a supply.
If the fault is confined to one of the expansion units, check that rack’s local supply and the S5 interface module connection separately. The 6ES5 183-3UA22 expansion rack, for example, has a different power supply assignment from the 10 A central rack.
Front panel connections and fault signals
L+ and M are the 24 V input connections, and PE is protective earth. EN/UH is used for the enable circuit and Monitor Output for the alarm relay. The 3NA11 has no external 24 V load-voltage monitoring input. When tracing the S5 cables and connectors, use the cabinet drawings to distinguish sensor power for the digital inputs from field power for the digital outputs.
When Fan Fault lights, check the fans and air path. Siemens’s S5-135U manual identifies the F–R jumper as the setting that controls power supply shutdown after a fan fault. Read the LED, relay contact and 5 V rail status together.
Batt. Low indicates a problem with the memory backup battery. Siemens documents that on 3NA11 hardware revision 9 and later, closing RR–LL allows a battery fault to operate the signaling relay as well. Check the installed S5 memory card type and program backup before isolating power.
Editor’s note
Ask for one clear photo showing both the 3NA11 order number and the E revision. The hardware revision matters when the cabinet alarm relies on battery fault reporting.
If the unit will not start, check 24 V at its own L+ and M terminals. Then trace the EN circuit using the cabinet drawings. Do both checks before replacing the CPU.
Photograph EN/UH and Monitor Output wiring before removal. Once the power is isolated, document the rear connectors and original jumper positions.
On a fan alarm, check the filter and air path as well as fan rotation. Verify the alarm and shutdown response against the cabinet’s existing fan monitoring setup.
When buying a used power supply, ask for a loaded 5 V reading in a compatible S5-135U rack, along with fan and relay test results. Ask separately whether the battery was tested.
OtomasyonAVM resources and PDFs
+ SIMATIC S5 power supplies · Siemens S5 PLC overview
+ OtomasyonAVM shared SIMATIC S5 PDF archive
Related topics
+ 6ES5 955-3NA12 power supply · 10 A class with a 24 V DC input.
+ 6ES5 955-3NC13 power supply · 18 A class with a 24 V DC input.
+ 6ES5 135-3UA41 central controller · S5-135U rack and power supply configuration.
To offer a 3NA11 for sale, email the nameplate photo, quantity and test status to otomasyonavm@gmail.com.
Navigation
+ S5 power supplies · S5 racks · SIMATIC S5 · Used Siemens equipment
External references
+ Siemens SIMATIC S5-135U/155U System Manual (English PDF) · §4.4, 3NA12 and 6ES5 135-3UA41 configuration.
+ Siemens S5-135U CPU 921/922 manual (English PDF) · §4.3, Table 5, 3NA11 hardware revision and battery alarm jumper.
+ Siemens S5-135U wiring manual (Russian PDF) · External load-voltage monitoring and the 3NA11 exception.
+ 6ES5 955-3NA11 E:09 front panel and nameplate photos · Input and main output markings.
+ Niemur SIMATIC S5 service parts list (PDF) · 3NA12 successor listing, p. 38.