6ES5 374-1FH21

Siemens 6ES5 374-1FH21 SIMATIC S5 Short-Type 256 KB Flash EPROM Memory Card

The Siemens 6ES5 374-1FH21 is a short-format SIMATIC S5 memory card with 256 KB of Flash EPROM organized in 16-bit words. It retains its contents without power and uses 5 V for reading and 12 V for programming. Siemens lists this order number as the 256 KB card for the IM 308-C 6ES5 308-3UC11 PROFIBUS-DP master interface used in S5-115U/H, S5-135U and S5-155U/H systems.

In an IM 308-C, the card stores the network configuration generated in COM PROFIBUS. The project defines PROFIBUS-DP station addresses, the bus rate and the distributed I/O mapping. When replacing an ET 200U station with an IM 318-B, for example, match its station address and I/O layout to the configuration on the card.

Which slot takes this card?

In this application the card fits the memory slot on the front of the IM 308-C. On an S5-115U, S5-135U or S5-135U/155U central rack, check the order number and hardware release of the interface module that holds the card. For a CPU slot, consult the CPU’s own compatibility table. The S5-115U CPU 945 manual, for example, lists 374-1FH11 and 374-1KH21 as its 256 KB options.

How do the 1FH21 and 1KH21 differ?

The 374-1FH21 requires a programmer that supports 12 V writes. Its Siemens-designated successor, the short-format 256 KB 374-1KH21, reads and writes at 5 V. The Siemens ET 200 manual lists the 1KH21 for the 308-3UC11 at release 2 or later. Siemens’ 5 V transition notice specifies release 3 or later for IM 308-C applications that read and write the card. The IM 308-C 6ES5 308-3UC21 data sheet specifies 5 V cards for in-module programming and lists the 1KH21 as a separate order item.

The 374-2FH21 also holds 256 KB, in the long format. The 374-2KH21 is the long-format 5 V option. Other short cards include the 128 KB 374-1KG11 and the 512 KB 374-1FJ21. Use the full order number to distinguish the format, capacity and programming voltage.

How do you write the COM PROFIBUS project to the card?

For offline export, use a PG memory card interface or an external programming unit that supports the 12 V card. Siemens lists the 6ES5 985-2MC11 adapter for PGs equipped with an E(E)PROM slot. In COM PROFIBUS, select File → Export → Memory Card to write the relevant master system to the card. Archive the STEP 5 PLC application program and the COM PROFIBUS network project as separate files.

What should you check when replacing the card?

Siemens specifies setting the IM 308-C selector to ST or OFF, switching off power to the module and then changing the card. After restarting the SIMATIC S5 system, verify the master configuration and check the status of the DP stations.

When IF is on and RN and OF are off, the Siemens diagnostic table lists a missing or incorrect card, a missing valid master project and an IM 308-C fault as possible causes. Check the card and project first. If the bus fault persists, use the PROFIBUS troubleshooting guide to check station addresses, DP connectors and termination. Record module and bus symptoms separately during PLC troubleshooting.

Editor’s note

Read both labels. Photograph the 374-1FH21 suffix on the card and the 3UC11 or 3UC21 number on the IM 308-C.

Keep two backups. Retain the original card and save the station address and I/O mapping lists with the COM PROFIBUS project.

Verify write support. A programmer may be able to read the card. Check that it also supports 12 V writes before preparing a spare.

Check the master selected for export. If the project contains several masters, export the network configuration for the module being replaced.

Load the spare before testing. Write the working configuration to a blank spare card first. On startup, check IF and OF, then confirm that the DP stations come online.

OtomasyonAVM resources and PDFs

+ Siemens IM 308-C 6ES5 308-3UC11 module page

+ SIMATIC S5 memory cards and memory modules

+ SIMATIC S5-135U central rack and documentation page

+ OtomasyonAVM SIMATIC S5-115 PDF archive

+ ET 200 distributed I/O manual archive

Related topics

+ 6ES5 374-1KH21 short-type 256 KB 5 V Flash EPROM

+ 6ES5 374-1FJ21 short-type 512 KB Flash EPROM

+ 6ES5 374-2FH21 long-type 256 KB Flash EPROM

+ 6ES5 308-3UC21 IM 308-C interface module

If you have a 6ES5 374-1FH21 to sell, send the label photo, quantity and test status to otomasyonavm@gmail.com.

Browse the S5 range

SIMATIC S5 memory cards · Siemens SIMATIC S5

Siemens and external references

+ Siemens ET 200 Distributed I/O System manual, IM 308-C and memory card ordering table (G-1)

+ Siemens COM PROFIBUS offline memory card export (§8.5.3)

+ Siemens 4202137 notice on the transition to 5 V Flash memory cards (German)

+ Siemens 6ES5 308-3UC21 data sheet

+ Siemens SIMATIC S5-115U CPU 945 manual, memory card table (p. 2-6)

+ Siemens ST 50 catalog, IM 308-C and 256 KB card (p. 3/91)

+ ADEGIS 6ES5 374-1FH21 short-format 16-bit product record