What Is a Type T Thermocouple?
A Type T thermocouple is a standardized thermocouple made from a copper positive thermoelement and a copper-nickel negative thermoelement. It is particularly well known for low-temperature measurement and is widely associated with refrigeration, laboratory work, environmental testing and cryogenic applications.
In simple terms: a Type T thermocouple converts a temperature difference into a very small thermoelectric voltage. A PLC, transmitter or temperature controller measures that voltage and uses the Type T reference characteristic to calculate temperature.
Type T is often described simply as a “low-temperature thermocouple,” but that description is incomplete. One of its important characteristics is the well-defined thermoelectric behaviour of its high-purity copper positive leg, particularly through much of the low- and moderate-temperature region.
What materials are used in a Type T thermocouple?
The nominal Type T thermoelement pair is:
Positive (+) thermoelement: Copper
Negative (-) thermoelement: Copper-Nickel alloy
The negative conductor is often described in technical literature as constantan. However, the word constantan does not identify one universal and exact alloy composition. Historically, it has been used for a family of copper-nickel alloys with different detailed compositions and thermoelectric properties.
For that reason, a copper-nickel conductor used in Type T should not automatically be assumed to be interchangeable with the negative conductor used in every other thermocouple type simply because both are called “constantan.”
What is the Type T thermocouple reference range?
The NIST ITS-90 reference function for Type T covers approximately -270 °C to +400 °C.
An important distinction must be made here:
The reference-function range is not the guaranteed operating range of every physical Type T sensor.
The actual usable temperature range of a probe can also depend on thermoelement diameter, insulation, cable construction, sheath material, process atmosphere, sealing and mechanical design.
The same distinction applies to other thermocouple families and is discussed further in IEC 60584-1 Thermocouple EMF Reference Functions and Tolerances.
Why is Type T important for low-temperature measurement?
Type T has a long history in low-temperature thermometry. Its standardized reference characteristic extends deep into the cryogenic region, making it useful where ordinary industrial temperature measurements move well below 0 °C.
Applications can include refrigeration research, ultra-low-temperature test equipment, environmental chambers and specialized laboratory measurements.
At very low temperatures, however, a good reference table alone does not guarantee a good measurement. The performance of the complete system becomes increasingly dependent on:
thermoelement purity
wire homogeneity
individual calibration
thermal connections
reference-junction measurement
low-level voltage measurement performance
Why does material purity matter below about -200 °C?
NIST thermocouple research shows that the copper positive thermoelement used for Type T can exhibit very uniform thermoelectric behaviour above roughly -200 °C when suitable high-purity copper is used.
At lower temperatures, extremely small concentrations of impurities in the copper can have a more noticeable influence on its thermoelectric properties.
This means that the statement “Type T is standardized to -270 °C, so any copper wire can be used at -270 °C” is incorrect.
For serious cryogenic measurement, thermoelement quality, homogeneity and calibration become particularly important.
How does a Type T thermocouple work?
Like other thermocouples, Type T operates through the Seebeck effect.
When copper and the appropriate copper-nickel alloy form a thermoelectric circuit and are exposed to a temperature distribution, a small electromotive force is generated.
The signal is measured in millivolts and is not perfectly linear with temperature. A Type T measuring instrument must therefore use the correct standardized temperature–EMF relationship rather than one fixed millivolts-per-degree conversion factor.
How is Type T EMF converted into temperature?
The forward thermocouple relationship can be written conceptually as:
E = f(t90)
where E is thermocouple EMF and t90 is temperature on the ITS-90 scale.
A PLC or digital temperature instrument normally performs the inverse operation:
t90 = g(E)
The relationship between reference tables, polynomial functions and ITS-90 is explained in Thermocouple Reference Tables, Polynomials and ITS-90.
How much signal does a Type T thermocouple produce?
Thermocouple sensitivity changes with temperature, so Type T does not have one constant µV/°C value over its complete range.
Around ordinary room-temperature conditions, Type T sensitivity is approximately 40 µV/°C in magnitude.
This is useful for understanding the signal level but should not be used as a universal linear conversion factor. Accurate temperature conversion should use the appropriate reference function.
Where are Type T thermocouples used?
With a suitable probe construction, Type T thermocouples can be used in applications such as:
Refrigeration and freezer systems
Low-temperature laboratory experiments
Cryogenic research
Cold-chain and food applications
Environmental and climate test chambers
Low- and moderate-temperature process measurement
Gas and liquid temperature measurement
The chemical environment, process pressure and physical construction of the sensor must still be evaluated separately.
Is Type T suitable for wet environments?
Type T is used in many low- and moderate-temperature applications, including installations where moisture may be present, but water resistance is a property of the complete sensor construction, not of the Type T designation itself.
Cable insulation, probe sheath, seals, terminal heads and process fittings determine whether a particular sensor can tolerate moisture or immersion.
A bare or poorly sealed Type T sensor should therefore not be assumed to be waterproof simply because the thermoelements are copper based.
Is Type T suitable for high temperatures?
Type T is primarily associated with low- and moderate-temperature measurement. Its standardized reference function extends to approximately 400 °C.
At higher temperatures, oxidation and material limitations of the copper thermoelement become increasingly important. Depending on the process, Type K, Type N or noble-metal thermocouples may be more appropriate.
Changing thermocouple type should still be based on more than maximum temperature. Process atmosphere, required tolerance, service life and receiving instrument compatibility must also be considered.
Type T versus Type K
Type K thermocouples use nickel-based thermoelements and are widely used over much higher industrial temperature ranges.
Type T uses copper and copper-nickel and is particularly important at lower temperatures.
Their temperature–EMF curves are completely different. Replacing a physical Type K sensor with Type T therefore also requires changing the PLC, transmitter or temperature controller configuration to Type T.
Type T versus Type J
Type J uses iron against a copper-nickel alloy, while Type T uses copper against copper-nickel.
Although the negative conductors of Type J and Type T may both be described casually as “constantan,” they should not automatically be treated as interchangeable thermoelements.
NIST specifically notes that the copper-nickel alloy used as the Type T negative thermoelement and the copper-nickel alloy used for Type J are not generally interchangeable even though both may be referred to by the same traditional name.
Type T versus Pt100
A Type T thermocouple and a Pt100 use fundamentally different measuring principles.
Type T generates a thermoelectric EMF, while a Pt100 measures temperature through the change in electrical resistance of a platinum sensing element.
For low- and moderate-temperature measurement, the best choice depends on required accuracy, stability, response time, cable distance, mechanical construction and instrument compatibility.
See Thermocouple vs Pt100 for a broader comparison.
Does Type T require cold-junction compensation?
Yes. Type T is a differential thermoelectric measurement system just like other standardized thermocouples.
Its standard reference functions assume a reference junction at 0 °C. Since the terminals of a real PLC or controller are normally not at 0 °C, the instrument must apply cold-junction compensation (CJC).
The fact that the Type T positive leg is copper does not remove the requirement for CJC.
If one leg is copper, can ordinary copper cable be used?
Not for both conductors. This is an important Type T wiring issue.
The positive thermoelement is copper, but the negative thermoelement is a specific copper-nickel alloy. The complete circuit must preserve the correct Type T thermoelectric relationship.
Under appropriate conditions, a copper connection on the positive side may not introduce an additional thermoelectric junction because the materials are equivalent. That does not mean that an entire Type T circuit can be extended using ordinary two-core copper cable.
The negative leg would no longer maintain the required Type T thermoelectric behaviour.
Why is the correct Type T extension cable important?
The wiring between the sensor and the measuring instrument must preserve the appropriate thermoelectric relationship.
Requirements for thermocouple extension and compensating cables are addressed in IEC 60584-3 Thermocouple Extension and Compensating Cables.
Changing a Type T circuit to ordinary copper conductors at a remote uncontrolled junction can create measurement error, particularly when the transition points are at different temperatures.
What is the polarity of a Type T thermocouple?
For Type T:
Copper is the positive (+) thermoelement.
Copper-nickel is the negative (-) thermoelement.
Care should be taken when identifying polarity by insulation colour. IEC, ANSI and other thermocouple wiring standards use different colour conventions.
Use conductor colour only when the applicable wiring standard is known. There is no safe worldwide rule that one insulation colour always means Type T positive or negative.
Can Type T be grounded, ungrounded or exposed?
Yes. The letter T identifies the thermoelement pair, not the mechanical junction construction.
A Type T sensor can be manufactured with a:
Grounded junction
Ungrounded junction
Exposed junction
The differences in response time, electrical isolation and process protection are explained in Grounded, Ungrounded and Exposed-Junction Thermocouples.
Can a Type T thermocouple be connected directly to a PLC?
Yes, provided the PLC thermocouple module supports Type T.
The PLC thermocouple input must be configured for Type T. The module measures the low-level EMF, applies CJC and converts the compensated signal using the Type T reference characteristic.
An ordinary 0–10 V analog input is not a direct replacement for a thermocouple input. Type T produces a much smaller signal and requires low-level measurement, cold-junction compensation and nonlinear conversion.
Can Type T be converted to 4–20 mA?
Yes. For long signal distances or systems using standard analog inputs, Type T can be connected to a temperature transmitter or sensor converter.
The transmitter measures the Type T EMF, applies cold-junction compensation and linearization, and converts the temperature into a standard signal such as 4–20 mA.
The PLC can then process a standard analog value rather than the raw thermocouple signal.
Advantages of Type T thermocouples
In suitable applications, Type T offers several useful characteristics:
Reference data extending to very low temperatures
Well-characterized behaviour in low- and moderate-temperature measurement
Highly uniform copper positive thermoelements when appropriate material is used
Availability in small, fast-response probe constructions
Useful options for refrigeration, laboratory and cryogenic measurement
Limitations of Type T thermocouples
Type T is not the correct sensor for every temperature measurement:
Its upper temperature region is limited compared with Type K, Type N and noble-metal thermocouples.
Thermoelement purity becomes increasingly important at extreme cryogenic temperatures.
Cold-junction compensation is required.
Incorrect extension wiring can create thermoelectric error.
Its millivolt-level signal can be affected by electrical interference.
Actual process resistance depends on probe, sheath and insulation construction.
What should be specified when selecting a Type T thermocouple?
“Type T” alone is not a complete sensor specification. At minimum, consider:
Normal operating temperature
Minimum temperature
Maximum process temperature
Gas, liquid or surface measurement
Probe diameter and insertion length
Sheath material
Grounded or ungrounded junction
Cable insulation and length
Type T support in the PLC or controller
Required tolerance and calibration level
For cryogenic or precision laboratory work, individual calibration and the total measurement uncertainty may be more important than a generic thermocouple tolerance specification.
What does Type T thermocouple tolerance mean?
A real Type T thermocouple can differ slightly from the ideal standardized reference function. The permitted difference is defined by the applicable thermocouple tolerance.
Tolerance depends on the temperature region and standard being used. It is therefore incorrect to take one old catalogue value such as “±1 °C” or “±0.75%” and apply it universally across the entire Type T reference range.
IEC-based thermocouple tolerances and reference characteristics are discussed under Thermocouple Standards.
Is calibration the same as the Type T reference table?
No.
The reference table describes the standardized ideal temperature–EMF relationship for Type T.
Calibration determines how one individual physical thermocouple differs from that ideal relationship at specified temperatures.
This distinction becomes particularly important at very low temperatures or wherever a small measurement uncertainty is required.
Conclusion
Type T is a copper / copper-nickel thermocouple with an important role in low-temperature and cryogenic measurement.
Its ITS-90 reference function covers approximately -270 °C to +400 °C, but this mathematical range should not be confused with the guaranteed service range of every physical Type T probe.
One of Type T's strengths is the well-characterized thermoelectric behaviour of its copper positive conductor over much of its operating region. At extreme low temperatures, however, material purity and thermoelement homogeneity become increasingly important.
A reliable Type T measurement requires correct Type T wiring, correct polarity, proper cold-junction compensation, the correct Type T reference conversion and a sensor construction suitable for the process environment.
Related thermocouple types and temperature measurement topics
+ Types of Thermocouples (T/C)
+ What Is a Thermocouple (T/C)?
+ What Is a Type E Thermocouple? · What Is a Type N Thermocouple?
+ Type J Thermocouples · Type K Thermocouples
+ Thermocouple Cold-Junction Compensation
+ Grounded, Ungrounded and Exposed-Junction Thermocouples
+ Thermocouple Standards · IEC 60584-3 Cables
+ Pt100 Sensors · Thermocouple vs Pt100
+ Temperature Sensor Converters · Temperature Controllers · PLC Systems