What Is a Type E Thermocouple?
A Type E thermocouple is a base-metal thermocouple made from a nickel-chromium positive thermoelement and a copper-nickel negative thermoelement. Among the common thermocouple types, Type E is particularly notable for its relatively high thermoelectric sensitivity and strong millivolt output.
In simple terms: a Type E thermocouple does not output temperature directly. It produces a small electrical voltage that changes with temperature, and a PLC, transmitter or temperature controller converts that EMF into temperature using the standardized Type E reference characteristic.
Type E belongs to the same broad base-metal family as Types J, K, T and N, but it has its own alloy combination and its own temperature–EMF function. It is therefore not electrically interchangeable with any of those thermocouples.
What materials are used in a Type E thermocouple?
The nominal thermoelement pair is:
Positive (+): Nickel-Chromium alloy — NiCr
Negative (-): Copper-Nickel alloy — CuNi
The positive conductor belongs to the same general nickel-chromium alloy family used on the positive side of many Type K thermocouples. The negative leg, however, is a copper-nickel alloy.
Copper-nickel thermoelements are often referred to informally as constantan. That name should be used carefully. The copper-nickel conductor found in a Type J thermocouple should not automatically be assumed to be interchangeable with the negative conductor used for Type E or Type T merely because all may be described historically as constantan.
What is the Type E reference temperature range?
The ITS-90 reference function for Type E covers approximately -270 °C to +1000 °C.
A very important distinction is required here:
The -270 to +1000 °C range describes the standardized reference function; it is not the guaranteed operating range of every physical Type E probe.
The actual service range can be limited by wire diameter, insulation, sheath alloy, mineral insulation, cable construction, process atmosphere and mechanical design.
This distinction between reference data and real sensor capability is explained further in IEC 60584-1 Thermocouple EMF Reference Functions and Tolerances.
Why does Type E produce a relatively strong thermocouple signal?
The thermoelectric behaviour of the nickel-chromium positive conductor differs substantially from that of the copper-nickel negative conductor.
This produces a relatively large difference in Seebeck coefficient between the two legs. The physical principle behind this is described in the Seebeck effect.
For a given temperature change, Type E can therefore produce a larger microvolt or millivolt change than many other common thermocouple types.
A stronger thermoelectric output can improve signal-to-noise conditions in some low-level measurement systems.
Higher EMF does not automatically mean higher measurement accuracy. Thermocouple tolerance, extension wiring, reference-junction measurement, instrument accuracy and mechanical installation still influence the final result.
How does a Type E thermocouple work?
Like every standard thermocouple, Type E develops an electromotive force in a circuit of dissimilar conductors exposed to a temperature distribution.
The nickel-chromium and copper-nickel conductors respond differently to temperature, producing the measurable thermoelectric EMF used for temperature measurement.
The output is nonlinear. A simple fixed relationship such as:
EMF = temperature × one constant
cannot accurately represent the complete Type E range.
Type E temperature–EMF reference function
The forward conversion can be represented conceptually as:
E = f(t90)
A measuring instrument normally performs the inverse conversion:
t90 = g(E)
The temperature is expressed on the ITS-90 scale. The mathematical relationship between tables, reference polynomials and inverse conversion is covered in Thermocouple Reference Tables, Polynomials and ITS-90.
Can Type E be used at very low temperatures?
Yes. The standardized Type E reference function extends deep into the cryogenic region.
Type E can therefore be considered for low-temperature laboratory work, research equipment and cryogenic measurement when the actual sensor construction is suitable.
Below approximately -200 °C, however, good temperature measurement requires more than simply selecting the correct thermocouple letter. Thermoelement homogeneity, calibration, installation, wiring and microvolt-level instrument performance become increasingly important.
For applications primarily focused on low-temperature measurement, Type T thermocouples may also be worth considering.
Can Type E be used at high temperatures?
The Type E reference function extends to approximately 1000 °C, but the practical upper limit of a real probe depends heavily on conductor diameter and sensor construction.
Nickel-chromium/copper-nickel thermocouples are commonly associated with service in suitable oxidizing atmospheres.
Unprotected thermoelements may be less suitable in:
strong reducing atmospheres
alternating oxidizing and reducing conditions
high-temperature vacuum applications
some sulfur-containing environments
In a sheathed industrial probe, the thermoelements may not contact the process directly. The suitability of the installation must therefore consider the thermocouple alloy, sheath material and process atmosphere together.
Type E versus Type K
Both Type E and Type K use a nickel-chromium based positive thermoelement, but their negative conductors are different.
Type E: NiCr / CuNi
Type K: NiCr / nickel-aluminium based alloy
Type E generally produces a stronger thermoelectric signal. Type K, however, is far more common in general high-temperature industrial service and is available in an enormous range of probe constructions.
The two cannot use the same instrument setting. If Type K is replaced with Type E, the controller or PLC input must also be reconfigured for Type E.
Type E versus Type N
Type N uses the Nicrosil/Nisil alloy system and was developed primarily for improved high-temperature thermoelectric stability and oxidation behaviour.
Type E is more notable for its high thermoelectric sensitivity.
A useful simplified comparison is:
Type E → relatively strong EMF output
Type N → improved long-term high-temperature stability
The correct choice still depends on the process rather than one single specification.
Type E versus Type J
Type J uses iron against a copper-nickel conductor. Type E uses nickel-chromium against copper-nickel.
Type J remains extremely common in existing industrial machinery, but its iron positive leg has different oxidation behaviour from the nickel-chromium positive conductor used in Type E.
The fact that both types use copper-nickel material on one side does not mean their cables can automatically be interchanged.
Type E versus Type T
Type T uses copper against copper-nickel and is strongly associated with low-temperature measurement.
Type E uses NiCr/CuNi, produces a relatively strong EMF and has a reference function that extends to higher temperatures.
Even though the negative thermoelements belong to similar copper-nickel alloy families, the complete thermocouple circuits and reference functions are different.
Type E versus Pt100
Type E and a Pt100 use fundamentally different measuring principles.
Type E generates a thermoelectric EMF. Pt100 measures temperature through a change in platinum resistance.
Pt100 can provide excellent stability and accuracy in many low- and moderate-temperature processes. Type E can be attractive where a smaller probe, fast thermal response, wider temperature range or stronger thermocouple signal is desirable.
The technologies are compared in more detail in Thermocouple vs Pt100.
Does Type E require cold-junction compensation?
Yes. Type E is a differential thermoelectric sensor and its reference-junction temperature must be known.
Its standard reference function assumes a reference junction at 0 °C.
Since real PLC and controller terminals are normally at some other temperature, the instrument must apply cold-junction compensation (CJC).
The relatively strong Type E signal does not make incorrect CJC harmless.
Can Type E be grounded, ungrounded or exposed?
Yes. The letter E identifies the thermoelement pair, not the mechanical junction construction.
Type E can be manufactured with a grounded, ungrounded or exposed measuring junction.
Grounded and exposed constructions can provide faster response, while an ungrounded junction can provide better electrical isolation between the measuring junction and metal sheath.
The practical differences are covered in Grounded, Ungrounded and Exposed-Junction Thermocouple Differences.
Can Type E be manufactured as a mineral-insulated thermocouple?
Yes. Type E can be manufactured as a mineral-insulated metal-sheathed thermocouple.
The NiCr and CuNi thermoelements can be embedded in compacted mineral insulation inside a metal sheath to produce small-diameter, vibration-resistant industrial probes.
The general construction requirements are discussed in IEC 61515 Mineral-Insulated Metal-Sheathed Thermocouples.
Why is the correct Type E extension cable important?
The thermoelectric relationship must be maintained from the sensor toward the measuring instrument.
A Type E thermocouple should therefore not simply be extended using Type K or Type J thermocouple cable.
Use the appropriate Type E extension or compensating cable and respect the specified temperature limits of that cable system.
Cable requirements are addressed in IEC 60584-3 Thermocouple Extension and Compensating Cables.
Can Type E be connected directly to a PLC?
Yes, if the PLC thermocouple module supports Type E.
A suitable PLC thermocouple input module measures the millivolt-level signal, measures its terminal temperature, applies CJC and converts the compensated EMF using the Type E reference function.
If the physical sensor is Type E while the PLC input is configured for Type J or Type K, the temperature will be calculated incorrectly even if the sensor and wiring are healthy.
Can Type E be connected to a temperature controller?
A temperature controller that explicitly supports Type E can accept the sensor directly.
The controller performs Type E linearization and compares the resulting temperature with its setpoint before operating the relevant heater, relay, SSR or other control output.
Correct sensor-type configuration is important even when the control algorithm itself is working perfectly. A controller cannot regulate the correct process temperature if the input is being interpreted with the wrong thermocouple curve.
Can Type E be converted to 4–20 mA?
Yes. A compatible temperature transmitter or sensor converter can measure Type E directly.
The transmitter performs cold-junction compensation and Type E linearization, then converts the calculated temperature into a standard industrial signal such as 4–20 mA or 0–10 V.
This can be useful when the sensor is a long distance from the control cabinet or when standard analog PLC inputs are preferred.
Can Type E be used near VFDs?
Yes. Its relatively strong thermocouple output can be helpful, but Type E still operates at millivolt level.
Variable frequency drives (VFDs), servo drives, motor cables and switching contactors can generate electromagnetic interference.
Routing Type E cable beside a VFD-to-motor cable for long distances, poor shielding or incorrect grounding can still cause unstable readings.
A stronger thermocouple signal does not replace good wiring practice.
What does Type E thermocouple tolerance mean?
A real Type E thermocouple may differ slightly from the ideal standardized temperature–EMF function. The permitted deviation is described by the applicable thermocouple tolerance.
That tolerance describes the thermocouple itself; it does not describe the complete accuracy of the installed measurement system.
PLC input error, CJC, extension wiring, electrical noise, calibration and sensor installation can all add further uncertainty.
Old catalogue values such as one fixed ±°C or ±% specification should not automatically be applied across the complete Type E range. For current IEC terminology, see Thermocouple Standards.
Does a Type E thermocouple need calibration?
Individual calibration is not necessary for every ordinary industrial Type E application.
For laboratory systems, critical process measurement or applications requiring lower uncertainty, calibration can determine the actual deviation of one specific sensor from the standardized Type E reference function.
Like other base-metal thermocouples, Type E can also change gradually after prolonged high-temperature exposure because of oxidation, diffusion and thermoelectric inhomogeneity.
What contributes to Type E measurement uncertainty?
A complete Type E measurement system can include uncertainty contributions from:
sensor tolerance or calibration
thermoelectric drift
extension cable
cold-junction compensation
measurement electronics
electromagnetic interference
sensor installation
immersion depth
process temperature gradients
For critical measurements, these effects should be considered together using a full thermocouple measurement uncertainty approach.
Where are Type E thermocouples used?
With an appropriate probe construction, Type E can be used in:
laboratory temperature measurement
test and research systems
low- and moderate-temperature processes
suitable industrial furnace applications
cryogenic and low-temperature research
gas and air temperature measurement
applications where relatively high thermoelectric sensitivity is useful
The final sensor should still be selected by considering sheath material, probe diameter, cable, junction style and process atmosphere.
What should be specified when selecting a Type E thermocouple?
A useful Type E specification should include:
Normal process temperature
Minimum and maximum temperature
Process atmosphere
Probe diameter and insertion length
Sheath material
Grounded, ungrounded or exposed junction
Cable type and length
Type E support in the PLC or controller
Required tolerance
Calibration requirement
Advantages of Type E thermocouples
In a suitable application, Type E can provide:
high thermoelectric sensitivity
relatively strong millivolt output
a standardized reference function extending to very low temperatures
a broad useful industrial temperature region
availability in mineral-insulated and small-diameter probe constructions
lower material cost than noble-metal thermocouples
Limitations of Type E thermocouples
Important limitations include:
no guarantee of unlimited high-temperature stability
need for suitable protection in reducing or aggressive atmospheres
requirement for correct Type E extension wiring
cold-junction compensation requirement
possible long-term drift during high-temperature service
susceptibility of the millivolt signal to electromagnetic interference
Conclusion
Type E is a nickel-chromium / copper-nickel base-metal thermocouple distinguished by its relatively high thermoelectric sensitivity.
Its ITS-90 reference function covers approximately -270 °C to +1000 °C, but this mathematical range should not be confused with the guaranteed service range of every physical Type E probe.
Its strongest technical characteristic is the comparatively high EMF output available from the NiCr/CuNi thermoelement combination. This can be useful in low-level signal measurement, but it does not by itself determine total accuracy.
Reliable Type E measurement requires the correct sensor construction, appropriate Type E extension wiring, accurate CJC, correct instrument linearization, a suitable process atmosphere and calibration where required.
Related thermocouple types and temperature measurement topics
+ Types of Thermocouples (T/C)
+ Type K Thermocouples · Type J Thermocouples
+ What Is a Type N Thermocouple? · What Is a Type T Thermocouple?
+ What Is a Thermocouple (T/C)? · Seebeck Effect
+ Cold-Junction Compensation · Grounded / Ungrounded / Exposed Junctions
+ Thermocouple Standards · IEC 60584-1
+ IEC 60584-3 Thermocouple Cables · IEC 61515 MI Thermocouples
+ Pt100 Sensors · Thermocouple vs Pt100
+ Temperature Sensor Converters · Temperature Controllers · PLC Systems