6ES7338-4BC01-0AB0

6ES7338-4BC01-0AB0 Siemens SM 338 SSI Position Input Module

6ES7338-4BC01-0AB0 is the SM 338 POS-INPUT position input module for the Siemens SIMATIC S7-300 family. It transfers position data from up to three SSI absolute encoders to the PLC. It provides two FREEZE inputs, a 20-pin front connector and isochronous operation in a compatible system. Selection requires checking the SSI data format and existing project compatibility as well as the encoder supply.

Function and encoder compatibility

The module reads serial position data from absolute encoders. It supports 13-, 21- or 25-bit SSI frames and Gray or binary data. The bit count specifies frame length; it does not by itself define mechanical measurement accuracy. An SSI interface differs from the A/B pulse interface of an incremental encoder.

The PLC program evaluates the position data for tasks such as machine sequencing, position monitoring or identifying where an event occurred. SM 338 is a position input module; driving a motor requires suitable servo and motion hardware as part of the application.

Supply, connection and dimensions

Rated supply: 24 V DC, with a permissible range of 20.4–28.8 V DC. Front connector: 20-pin. Dimensions: 40 × 125 × 120 mm. Select the panel power supply for the connected encoders as well as the module.

The encoder supply output is approximately L+ − 0.8 V, with a maximum total output current of 900 mA. This is not a separate allowance for each encoder. The encoder supply reference is not galvanically isolated from the CPU reference, making the M connection and equipotential bonding important.

SSI clock frequency and cable length

For a shielded twisted-pair SSI cable, the manufacturer specifies maximum lengths of 320 m at 125 kHz, 160 m at 250 kHz, 60 m at 500 kHz and 20 m at 1 MHz. These limits apply to the SSI connection, not the separate digital inputs. Also assess the encoder limits and electromagnetic conditions at the installation.

The important difference between FREEZE and Fast Mode

FREEZE captures a selected position value on the rising edge of DI0 or DI1; it is not a motor stop command. FREEZE is unavailable in Fast Mode. Fast Mode requires at least firmware V2.0.0 and STEP 7 V5.3 + SP2. Select the operating function according to the installed module version.

Isochronous operation and commissioning

Isochronous operation requires a compatible CPU, a PROFIBUS DP master supporting equidistant cycles and an IM 153-x supporting synchronous operation. Set frame length, Gray/binary format, SSI clock frequency, monoflop time and normalization in STEP 7 to match the encoder.

An SF indication alone does not establish that the module has failed. Investigate supply, wiring, encoder and parameter faults as well. When the diagnostic interrupt is enabled, OB82 is called. Application testing should compare actual movement with the reported position and verify the selected operating functions.

PDF files and wiring documentation

Use the S7-300 PDF files and manuals section for terminal connections, parameter settings and diagnostic information. Match the document to order number 6ES7338-4BC01-0AB0 and the installed firmware.

Related topics and categories

S7-300 main page  |  Special and function modules  |  Analog and special signal modules

S7-300 CPU modules  |  Digital input modules  |  Digital output modules

S7-300 memory cards  |  Siemens S7 PLC range  |  Used Siemens products

HMI operator panels  |  Second-hand main page  |  OtomasyonAVM home

Manufacturer references

Siemens — 6ES7338-4BC01-0AB0  |  Siemens — SM 338 POS-INPUT, A5E00409892-01