6ES7 134-4JB51-0AB0
6ES7 134-4JB51-0AB0 – Siemens ET 200S 2/4AI RTD Standard
Series: Siemens SIMATIC DP / ET 200S
Category: RTD temperature and resistance input module
Description and system role
6ES7 134-4JB51-0AB0 is a 2/4AI RTD Standard analog input module for ET 200S stations. It reads resistance thermometers and resistance values, then transfers the measurements to the PLC program. Applications include process and machine temperature measurement using Pt100 temperature sensors.
When selecting a spare, check the sensor type, two-/three-/four-wire connection, number of channels in use, terminal base and station interface module together. For analog measurement, the sensor output type must match the channel configuration.
Using two or four channels
The module provides four inputs with two-wire connections or two inputs with three-wire or four-wire connections. With two-wire measurement, cable resistance contributes to the result. Three-wire wiring allows line-resistance compensation, while four-wire wiring separates the measurement leads from the current leads.
Select the channel arrangement by considering the sensor wiring and required measurement accuracy together. The screw-terminal TM-E15S24-01 and spring-terminal TM-E15C24-01 are among the compatible terminal bases; check the installed base's exact order number and wiring diagram.
Sensors, measurement ranges and resolution
Standard and Climate settings are available for Pt100 and Ni100 sensors. RTD measurement resolution is 15 bits plus sign. Direct resistance measurement supports 0–150 Ω, 0–300 Ω and 0–600 Ω; the manual specifies 14 bits for 150 Ω and 15 bits for 300 Ω and 600 Ω.
The nominal range is −200 to +850 °C for Pt100 Standard and −120 to +130 °C for Pt100 Climate. Also observe the sensor's own temperature rating. Assess numerical resolution and measurement accuracy separately: sensor, cable and module errors all contribute to the result.
A separate evaluation mode is available for suitable PTC thermistors. It reports normal, prewarning and threshold-exceeded states. When selecting the sensor, consider the difference between Pt100 and thermocouples; thermocouples require an appropriate TC input module.
Supply and isolation
The module receives 24 V DC through the ET 200S power module. Maximum L+ current consumption is 30 mA, and module width is 15 mm. The module supplies the constant measuring current required for resistance measurement. Size the power supply for the complete station.
The channels are not galvanically isolated from each other. The inputs are isolated from the backplane bus and L+ supply. For grounded sensors, check the measurement reference, shielding and the installation's grounding arrangement.
Measurement timing and diagnostics
The module cycle depends on the number of active channels and the conversion time per channel. 50/60 Hz interference suppression and smoothing settings also affect response. Four-wire connections require additional conversion time for wire-break diagnostics. Assess the application's update requirements with these settings in mind.
The red SF LED indicates a group fault. Parameter, measurement-limit and wire-break diagnostics are available; configure them for the selected measurement type. Wire-break diagnostics are disabled when PTC is selected. Deactivate unused inputs in the project and apply the terminal-bridge arrangement specified in the manual for unused channels.
4JB50 compatibility and interface restrictions
The Siemens manual describes configuration as the predecessor model when replacing 6ES7 134-4JB50-0AB0. Existing wiring can be retained for this replacement, while the diagnostic data structure and available functions must be checked separately.
With IM151-1 BASIC, IM151-1 COMPACT or IM151-1 FO STANDARD, this electronic module can operate only as 2AI RTD Standard. To use four channels, confirm that the interface and hardware configuration support that operating mode.
Editor's Note
For a used RTD module, check every channel that will be used. Testing at several points with an RTD simulator or suitable precision resistors provides more information than a reading at one temperature. Ask for the sensor type, wiring arrangement, measurement range and filter setting to be recorded; this helps distinguish wiring or configuration errors from module faults.
PDFs and operating manuals
Visit the Siemens ET 200 PDFs and user manuals section. The main document for this model is the 2/4AI RTD ST manual, 07/2008, A5E01076865-02. Review its connection, predecessor-compatibility and diagnostics sections against the installed station.
Related topics
For control and monitoring, explore PLC and HMI systems, operator panels and SCADA. For system research, see Siemens S7-300, about Siemens ET 200 and ET 200 PROFIBUS and PROFINET.
Other module groups: ET 200 analog input modules · Digital input modules · Digital output modules · Connection modules · Additional modules.