6ES7 135-4MB00-0AB0
Siemens main menu › SIMATIC S7 › SIMATIC ET 200
Siemens 6ES7 135-4MB00-0AB0 — ET 200S 2AO I High Feature
Siemens 6ES7 135-4MB00-0AB0 is an ET 200S 2AO I High Feature analog current output module within the Siemens ET 200 distributed I/O family. Its two output channels provide ±20 mA or 4–20 mA signals. It sends analog references from the PLC to devices with compatible current inputs, such as drives, valve positioners and process equipment.
Order number: 6ES7135-4MB00-0AB0
Product family: SIMATIC ET 200S
Function: 2-channel analog current output, High Feature
Signal ranges: ±20 mA and 4–20 mA
Catalog resolution: 15-bit, high resolution
Diagnostics: Internal module diagnostics and wire-break monitoring
CPU STOP: Parameterizable substitute value
Sending a reference to the field
Within the ET 200 system architecture, analog inputs and outputs have different signal directions. 6ES7 134-4MB00-0AB0 is a separate product in the ET 200 analog input modules range. This 135-4MB00 is an output module. It also differs from the 135-4LB00 voltage output module. When comparing ET 200 output modules, check current versus voltage output as well as the channel count.
Five selection and commissioning checks
1. Signal range and scaling: The module parameter and receiving device input setting must match. In a linear 4–20 mA application, for example, 4 mA represents the lower limit, 12 mA the midpoint and 20 mA the upper limit. This example does not define PLC raw values; check scaling separately in the Siemens S7 hardware project and application program.
2. Current loop: Consider the receiver input resistance together with cable resistance, and compare the total load with the limit specified for this exact order number. Check polarity, reference connections and shielding. Selecting suitable ET 200 connection components does not replace correct field wiring.
3. Terminal base and supply: Compare the installed base order number with the information for ET 200 terminal modules. Do not copy terminal numbers from a similar-looking module. Check the relevant potential group supply against the field wiring diagram, including the arrangement of ET 200 power supply components and ET 200 power distribution.
4. STOP behavior and diagnostics: Configure the CPU STOP substitute value to suit the process. When a wire-break diagnostic occurs, inspect the cable, terminals and receiver connection. Verify the diagnostic conditions and enable settings in the Siemens documentation for the selected range.
5. Exact version and system compatibility: Do not assume that 4MB00, 4MB01 and 4MB02 are interchangeable. Siemens lists explicitly identify isochronous support for later versions; do not assign that feature to 4MB00. Identify the installed interface through the ET 200 communication options, then verify the hardware catalog selection and station compatibility.
Editor's note
A changing reference on the PLC display does not by itself prove that the correct current reaches the field device. When process conditions permit testing, verify loop current with a suitable instrument and compare it with the receiver indication. Check parameters, wiring and measurements before assessing the module. Explore other product families through the Siemens main menu.
ET 200 PDF documentation and technical resources
When using our Siemens ET 200 PDF and user manuals page, confirm that the document covers 6ES7135-4MB00-0AB0. Product catalogs and released-module lists establish the basic identity; terminal assignments, load limits and detailed parameters require technical documentation covering this version. Do not directly apply tables for later 4MB01/4MB02 modules.
Related topics and Siemens navigation
Product family: Siemens main menu | SIMATIC S7 | ET 200 family
Station and field devices: Terminal modules | Analog input modules | PROFIBUS and PROFINET
Technical resources: About ET 200 | Power supply modules | ET 200 PDF manuals