6ES5 380-8MA11
Siemens 6ES5 380-8MA11 SIMATIC S5 two-channel timer module
The 6ES5 380-8MA11 is a two-channel 380 pulse timer for SIMATIC S5. Each channel is adjustable on the module from 0.3 to 300 seconds. The PLC starts the function module. While timing is active, the channel’s green LED is lit and the PLC reads a 1.
Time settings and installation
Channels 0 and 1 have separate settings. Select ×0.3 s, ×3 s or ×30 s, then set the potentiometer scale. Multiply the range by the scale reading. ×3 s at 4 gives approximately 12 s. Siemens specifies ±10% setting error and ±3% repeatability. Measure the elapsed time after setting the range and fine adjustment.
Fit the module to a suitable bus unit such as the 700-8MA11. It requires no field wiring and draws a typical 10 mA from the internal +9 V rail. If both channels fail to respond, check bus contact in the S5 rack, the power supply and any remote station interface.
STEP 5 addresses and diagnostics
The Siemens data sheet lists S5-90U, S5-95U, S5-100U, ET 100U and ET 200U. In a cabinet with an S5-90U, S5-95U CPU or S5-100U CPU 103, record the installed CPU number and module slot.
In the S5-90U, S5-95U and S5-100U manuals, channels 0 and 1 start and reset through Qx.0/Qx.1. Their running status appears at Ix.0/Ix.1. STEP 5 addresses these as digital outputs and digital inputs. Resetting the Q bit can interrupt timing.
For ET 100U, check input and output start addresses separately in COM ET 100. The commands are Qx.2/Qx.3 for an output group starting at bit 0 and Qx.6/Qx.7 for a group starting at bit 4. Read status at Iy.0/Iy.1 or Iy.4/Iy.5, according to the input group. x is the output byte address and y is the input byte address.
On ET 200U, use Qx.2/Qx.3 for commands and Iy.0/Iy.1 for status. Verify the input and output byte addresses in the project. At the ET 200 station, check the installed interface, such as IM 318-B, and the DP configuration. The identifiers are 4DX/024 for Siemens DP and 8DX/048 for standard DP.
In Siemens’ on-delay example, the PLC first sees the running bit go high and then checks for it to return to zero. A zero on the first scan alone does not indicate expiry. If the bit falls, also check for an interrupt or reset command.
Modules used in the same system
The 385A and 385B count pulses, the 461 comparator monitors analog thresholds, and the 788 simulator is used to test digital I/O. For bus faults, see the system manual’s procedure for the 330 diagnostic module.
Editor’s note
1. When buying used, check photos of the label, both adjustment dials and the bus connector. Ask for a timing and LED test on both channels.
2. Isolate cabinet and field supplies before removing the module. Record the range and scale settings for each channel separately.
3. If the timer never starts, monitor the STEP 5 Q command first. S5-100U and ET 200U use different command bits. Open the address table for the installed station.
4. If the LED is on but the PLC shows no running status, check the channel and input address. ET 100U input and output start addresses can differ.
5. If timing is short or long, read the range and scale again. Measure how long the LED stays lit on each channel and compare the results.
6. If the machine advances too early, verify that the program first detected a 1. Then check the transition to 0 alongside the reset command.
To offer a 6ES5 380-8MA11 for sale, send the quantity, working condition, label photo and asking price to otomasyonavm@gmail.com.
Manuals and supporting documents
+ Siemens 6ES5 380-8MA11 data sheet (DE)
+ Siemens S5-90U/S5-95U manual, section 16.2 (EN)
+ Siemens S5-100U, Figure 15-2, command and status bits (EN)
+ Siemens ET 100U, Figure 7-2, two address groups (EN)
+ Siemens ET 200U manual, section 9.2, timer module (EN)