6ES5 374-1KG11

Siemens SIMATIC S5 6ES5 374-1KG11 128 KB Short 5 V Flash EPROM

The Siemens 6ES5 374-1KG11 is a short-format MC 374 Flash EPROM card for storing the control program of a S5-115U CPU 945. This S5 memory card has 128 KB of storage with BYTE (8-bit) organization. Siemens lists it for the CPU 945-7UA13 in the SIMATIC S5 range. It uses 5 V for reading and writing.

The CPU 945 copies the program into its internal program memory at power-up or after an overall reset and runs it from there. The flash memory retains its contents without power. The earlier 374-1FG11 has the same capacity and uses 12 V for writing. The 374-2KG21 also holds 128 KB and uses a long-format housing.

CPU and card slot compatibility

Siemens ST 50 lists the 1KG11 for the CPU 945-7UA13 and CPU 945-7UA23. The 128 KB card capacity is separate from the CPU’s internal program memory capacity. Insert or remove the card with the PLC powered off.

Siemens publishes separate memory tables for other S5-115U CPUs, including the CPU 941, CPU 943 and CPU 944. Those tables include 375-series submodules such as the 375-1LA21 EPROM and 375-0LC41 EEPROM. Check the full CPU order number and memory socket when selecting a spare.

Reading, erasing and writing with STEP 5

Siemens specifies STEP 5 V6.6 or later for the 1KG11. Use the S5-DOS EPROM/EEPROM package on a compatible PG. Siemens specifies the 6ES5 985-2MC11 adapter if the PG lacks an S5 memory card slot. Unlike a UV-erasable EPROM, this flash card is erased electrically in the programmer.

Read the card offline. For a separate online backup from the running CPU, use an S5 PG cable to connect to SI1 or the fitted CPU 945 programmer interface module. At power-up, the CPU reloads blocks marked as originating from EPROM. Blocks marked as valid in RAM can remain in memory at power-up.

How nearby order numbers differ

The 374-1KH21 is a 256 KB WORD card, and the 374-1KK21 is a 1 MB WORD card. Both are short-format flash cards. Siemens lists the 374-1FH21 and 374-1FJ21 in the earlier generation that uses 12 V for writing. The 374-2KH21 is a 256 KB long-format 5 V card. Check the card length, write voltage and BYTE or WORD organization separately.

Editor’s note

Photograph the 374-1KG11 label and short housing before ordering a spare. Use the full code to distinguish a long card with the same capacity.

Record the full CPU order number and PG software version. When replacing an earlier 1FG11, check that the programmer supports 5 V writing.

Before erasing, save the card contents and running CPU backup to separate files. Data blocks changed on the machine may differ from the card copy.

If an older program appears after an overall reset, compare the blocks on the installed card with the project archive. The CPU loads the program from the card automatically after the reset.

For a used card, ask for a 128 KB identification and read test. After programming, compare the written blocks with the source file.

OtomasyonAVM resources and PDFs

+ SIMATIC S5 memory cards · SIMATIC S5-115U CPU models

+ SIMATIC S5-115U PDF and manual archive

Related topics

+ 6ES5 374-1KH21 256 KB short Flash EPROM · 6ES5 374-2KG21 128 KB long Flash EPROM

+ 6ES5 945-7UA13 CPU 945 · 6ES5 945-7UA23 CPU 945

S5 navigation

+ S5 memory cards · SIMATIC S5 · Siemens S5 PLC

External references

+ Siemens CPU 945 manual · 1KG11, 128 KB and BYTE organization

+ Siemens CPU 945 manual · Program transfer and PG adapter

+ Siemens ST 50 catalog · S5-115U CPU 945 ordering data

+ Siemens 4202137 · 5 V flash cards and transition from the 1FG11 (DE)