6ES5 372-0AA51

Siemens 6ES5 372-0AA51 – SIMATIC S5 16 KB EPROM Memory Submodule

The Siemens 6ES5 372-0AA51 is a 16 KB UV-erasable EPROM submodule in the SIMATIC S5 372 memory range. Siemens shows it installed on a 350 memory carrier in an S5-150S operating in WORD mode. Its capacity is 8 Kword, equivalent to 8,192 16-bit words or 16,384 bytes. Its STEP 5 programming number is 54.

The card stores the machine’s STEP 5 user program. The EPROM retains its contents when power is off. In Siemens’ example configuration, the EPROM and working RAM occupy separate address ranges. Keep the stored program and the system’s working data separate when backing up an existing machine.

350 memory carrier and S5-150S addressing

Siemens gives an example with a 6ES5 350-3KA21 memory carrier and two 372-0AA51 submodules. The front of the 350 has two EPROM slots. On the S5-150S, jumper 7 on the carrier is fitted for WORD operation. Coding socket 19 sets the starting address for the first slot and socket 26 sets it for the second.

Each 0AA51 occupies 8,192 words from its starting address. EPROM ranges must be contiguous and must avoid overlap with each other and with RAM. Before replacing a carrier in an S5 rack, record both slot addresses and the jumper positions. When checking the memory map on a system with a processor such as the CPU 924 or CPU 925, record the full order numbers of the CPU and the central controller as well.

Programming number and readback

Table 11.1 of the Siemens STEP 5 manual lists programming number 54, hardware identifier 44, 4 × 2532 EPROMs and WORD organization. When using a SIMATIC programmer with EPROM hardware, verify support for the exact module and its connection. The PG cable to the CPU and the EPROM programming connection serve separate purposes.

Read and save the card’s existing contents before erasing or writing it. This EPROM is erased with UV light. Perform a blank check before programming, then read the written card back and compare it with the source file. Electrical erasure is used by other memory technologies such as Flash and EEPROM.

Differences from the 372-0AA61 and 373 range

The 6ES5 372-0AA61 holds 32 KB / 16 Kword. Siemens specifies the 6ES5 983-0BA11 adapter for this model on the 350 carrier. When moving from a 0AA51 to a 0AA61, review the larger EPROM range, the second slot’s starting address and the RAM boundary together.

The 373-0AA21 also holds 16 KB. In the Siemens 350 table, the 373 range appears under S5-150 A/K and the 372 range under S5-150S. When comparing parts such as the 373-0AA41 and 373-1AA21, use the full order number, the carrier table and the programming profile.

Editor’s note

Photograph both slots. Record which card belongs in the first slot and which belongs in the second, along with their full order numbers.

Read the contents before removing the cards. If there are two EPROMs, save each backup separately and include the machine name and slot number in the filename.

Check the addresses in words. Interpreting a word address as a byte address changes the memory map. Compare the original jumper settings with the approved address plan.

Check the profile first if reading fails. During fault diagnosis, verify the 54 WORD profile, the EPROM adapter and the card connection separately.

Switch off the supply before handling the carrier. The Siemens 350 manual specifies power-off removal and installation. Verify the spare card’s contents by reading it back before fitting it.

OtomasyonAVM resources and PDFs

S5-150U central controller page · Siemens S5 PLC guide · OtomasyonAVM S5 PDF archive

Related topics

372-0AA61 32 KB EPROM · 373-0AA21 16 KB EPROM · 373-0AA41 32 KB EPROM

Site navigation

Siemens SIMATIC S5 › S5 CPUs and modules › S5 memory cards

External references

Siemens S5-150U system manual – S5-150S example and 350 memory carrier (PDF, German)

Siemens STEP 5 manual – Table 11.1, programming number 54 and 8 Kword (PDF, German)

Siemens 350 memory carrier – installation and addressing instructions (German)