6ES5 308-3UA11

6ES5 308-3UA11 – SIMATIC S5 IM 308 Distributed I/O Interface

Siemens 6ES5 308-3UA11 is an IM 308 interface module for serial connections between a central controller and remote expansion units or ET 100U stations. Within the S5 interface module range, it operates on the central-controller side and provides the remote I/O link for a Siemens S5 system.

The IM 308/318 family supports connection distances up to 3000 m, subject to cable type, transmission speed and line arrangement. Siemens’ connection table lists the 308-3UA12 revision. Selection and settings for UA11 must also be checked against the actual hardware revision.

Counterpart interface and subrack arrangement

The documented family arrangement uses IM 318-3, 318-3UA11 in expansion units and IM 318-8, 318-8MA12 in ET 100U stations. ER 701-2 and ER 701-3 connections require an additional IM 306. Check the IM 306 selection and S5 subrack against the complete system layout.

Cable, transmission speed and termination

The ET 100U family manual’s cable table specifies 31.25 kbaud at 3000 m for cable type V45551-F21-B5. This does not extend that distance to every cable and transmission speed. Review the installed cable specification and speed settings of all stations together.

The same ET 100U family document specifies 120 Ω / 0.25 W termination at the final station of each line. Check termination, shield continuity and grounding together. These instructions do not establish the pin assignments or jumper settings of a particular UA11 module.

Distinguishing IM 308 versions

The 308-3UB11 / IM 308-B and its 318-8MB11 counterpart belong to a different ET 200 arrangement. The 308-3UC11 and 308-3UC21 are IM 308-C models. When selecting a communications module, keep UA, UB and UC order codes separate.

Since an independent electrical data sheet for UA11 was not verified, supply ratings, current consumption, weight and memory specifications from other revisions have not been assigned to this model. Check the system power supply separately from the remote station’s field supply.

Addressing and fault checks

Compare the addresses of the remote digital input, digital output and analog modules against the existing PLC program. Record station numbers, transmission settings and any configuration memory before making changes.

During troubleshooting, establish whether one station or the entire line has disappeared. Check supplies, cable continuity, connectors and termination before reviewing addressing and configuration. Testing should confirm actual I/O data updates, rather than relying solely on illuminated indicators.

Editor’s note

With these older S5 systems, start with the label: we need 308-3UA11. “An IM 308 is available” is not enough. Before ordering a UA12, UB11 or UC21, check the complete code and the counterpart module.

Do not extend an existing cable simply because the family can reach three kilometres. Cable type and selected speed are a major part of the decision. Record the working settings first so every trial has a clear starting point.

A line fault does not immediately condemn the module. Start with the last station’s termination, loose terminals and shield connections. A small wiring defect can make a healthy interface look faulty.

For a used spare, ask whether the front connector and termination parts are included. Find out which counterpart interface was used to test the Siemens spare part. Missing connection parts can hold up the job even after the module arrives.

Photograph the switches, cable ends and any memory submodule before removal, and isolate power before replacement. Start with one station and verify that its data reaches the correct addresses. Confirm one step before moving to the next.

OtomasyonAVM resources and PDFs

+ S5 interface modules and S5 cables and connectors.

+ Siemens S5 PDF archive: system and connection documents. The English sources below are IM 308/318 and ET 100U family references, rather than independent UA11 data sheets.

Related topics

+ 308-3UA12 · 318-3UA11 · 318-8MA12.

+ IM 308-B · IM 308-C · PLC troubleshooting.

Browse SIMATIC S5

S5 interfaces · S5 communications · S5 subracks · SIMATIC S5 · Siemens second-hand main page

Siemens and external references

+ Siemens S5-135U/155U System Manual, C79000-G8576-C199-07, English; printed page 2-5 / PDF 23: IM 308/318 family pairings, listing the 308-3UA12 revision.

+ Siemens ET 100U Manual, EWA 4NEB 812 6040-02a, English; printed pages 3-42–3-43 / PDF 118–119: termination and cable/speed table.

+ Siemens S5-115U Manual, EWA 4NEB 811 6130-02b, English; printed page 15-63: 308-3UA12 technical page, not a source for UA11 electrical ratings.