6ES5 458-7LC11
Siemens 6ES5 458-7LC11 — 16-Channel Relay Output Module
6ES5 458-7LC11 is a 16-channel relay-contact digital output module for SIMATIC S5 systems. Outputs are galvanically isolated in four groups of four. Contact capacity depends on voltage and load type; the 5 A rating at 250 V AC applies to resistive loads.
Siemens ST 50 lists the model for S5-115U/H. Relay operation requires an external 24 V DC supply, with a permissible range of 20–30 V. Assess this supply separately from the load circuits switched by the contacts.
Contact capacity by load type
At 250 V AC, the limit is 5 A for resistive loads and 1.5 A for inductive loads. When selecting contactors or coil loads, check pickup and release conditions as well as steady current. Verify the coil data for Siemens contactors against their own technical documentation.
At 30 V DC, the ratings are 5 A resistive and 1 A inductive; at 110 V DC, they are 0.4 A resistive and 0.08 A inductive. Select any interposing relay and socket according to the actual load. AC and DC ratings are not interchangeable.
Outputs operating together within one group
Siemens also specifies a per-contact current limit for relays sharing one common: one relay: 5 A; two: 4 A; three: 2.5 A; four: 2 A. Apply this together with the contact rating for the load voltage and type, using the lower applicable limit.
Switching frequency is 10 Hz maximum for resistive loads and 2 Hz for inductive loads. A PLC output changing rapidly in software does not establish that a mechanical contact is suitable for continuous operation at that rate. Review program timing and unnecessary switching for contact life.
Front connector and wiring checks
The module uses a 46-pin front connector. Catalogue options include 490-7LB21 for screw terminals and 490-7LA11 or 490-7LA21 for crimp connections. When selecting cables and connectors, match the group commons, relay supply and load circuits to the manufacturer’s drawing.
The outputs have no short-circuit protection. Assess load-circuit protection, conductor size and contact capacity together. A relay can click while its contact is welded, damaged or connected through an overheating terminal; perform functional checks with a suitable load.
Similar models and used-module checks
458-7LA11 is a different relay output intended for measuring circuits, while 458-7LB11 provides eight relay outputs. Differences in channel count, contact arrangement and load capacity prevent treating these models as direct equivalents.
DC outputs such as 451-7LA12 and AC electronic outputs such as 456-7LA11 also operate differently. Compare output technology, load voltage, common-terminal arrangement and connector when selecting a replacement.
During fault investigation, check the CPU command, 24 V relay supply and actual contact state separately. Establish appropriate safe conditions for contact testing, accounting for both load and control supplies. Before removal, retain the program/memory backup and wiring photographs of the existing S5 system.
Editor’s note
Do not take the 5 A figure as permission to load every output that way at once. The number of relays operating within a common group also matters. Write down the loads and check their grouping first.
A contactor coil and a heater are different loads. Even with similar current readings, opening the circuit presents different conditions. Use the inductive-load rating for coils and give the contacts a reasonable working life.
A clicking relay is only part of the story. Check contact performance under an appropriate load, particularly on an older card. A sound alone is a poor basis for accepting the complete module.
Photograph the front connector and group wiring before removal. Keep the 24 V relay supply distinct from the voltage being switched. In an old panel, wire colour alone is not enough to identify a circuit.
For a used module, test all sixteen channels under suitable conditions where possible. A few working outputs cannot speak for the whole card. Inspect the label, common terminals and connector for signs of heating too.
OtomasyonAVM resources and PDFs
+ OtomasyonAVM S5 PDF archive · About Siemens S5 PLCs. Use S5-115U manual page 15-43 for the exact model’s wiring and load limits, and ST 50 pages 3/38–3/40 for connector and model comparisons.
Related topics
+ 458-7LA11 · 458-7LB11 · 490-7LB21 front connector · How relays work · Contactors.
Browse SIMATIC S5
+ S5 digital output modules · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand equipment.