6ES5 246-4UA41

Siemens SIMATIC S5 6ES5 246-4UA41 – IP 246I incremental positioning module

The 6ES5 246-4UA41 (IP 246I) provides closed-loop positioning for two independent axes using incremental encoder feedback. It sends an analogue speed reference to each drive. In the S5 positioning range, the 4UA41 is the S5-115 incremental version for operation without forced ventilation. The 4UA31 is the incremental version for forced ventilation. The 4UB21 and 4UB11 use parallel Gray-code absolute encoders.

Encoder, drive and power connections

Incremental encoders X4 is the 15-pin socket for axis 1 and X5 is the corresponding socket for axis 2. A and B determine count direction, and R is the reference pulse. The count limits are 500 kHz for 5 V differential RS-422 and 50 kHz for 24 V signals. Both axes must use the same signal type. Use the separate 5 V and 24 V diagrams in section 3.3 when selecting S5 cables and connectors.

Drive command X6 provides one ±10 V analogue speed reference per axis. Trace this separately from signals on other S5 analogue modules. X7 carries four 24 V inputs and two 24 V/120 mA outputs per axis. Alongside external digital input and digital output cards, check the IP 246 limit, BERO reference precontact, start/stop, position-reached and FUM drive-enable signals on the schematic.

Power The S5 system supply provides 5 V via the backplane. The front L+ terminal takes a nominal 24 V DC load supply. Siemens specifies 20–30 V for L+ and 0–55 °C ambient operation for this version.

Mounting and COM 246

For the S5-115U CPU family, the hardware manual lists CPUs 941, 942, 943 and 944 and specifies CP slots. If the S5 rack is a CR 700-2 or CR 700-3, check the CP slot and mounting clearance in the rack drawing. On an expansion unit, compare the central-controller bus and fitted interface modules with the installation drawings.

COM 246 uses the X8 TTY programming port to read and back up machine data and traversing programs. In STEP 5, FB164 handles operation and monitoring, while FB165 handles parameter assignment. The Siemens S5 PLC guide and S5 function modules pages help identify the other cards in the system.

When evaluating other axis cards, compare the encoder interface, drive command and axis count on the IP 247, IP 266 and IP 288 pages with the existing equipment.

Editor’s note

When buying used, ask for photos of the full 4UA41 label, the X4/X5 sockets and the fitted EPROM. Ask for a COM 246 bench readout that shows actual position and count direction on both axes.

When replacing an encoder, verify its output stage from its label and data sheet. Siemens specifies that open-collector encoders cannot be connected to the IP 246I inputs.

With card and encoder supplies isolated, check X18 and X20 for the signal level and X17 for the choice of module or external encoder supply. Use the separate 5 V and 24 V diagrams in sections 3.3.1 and 3.3.2.

Before replacing the card, back up the machine data and traversing programs for both axes in COM 246. Verify count direction, limits and the reference point before returning the machine to automatic operation.

If the axis slows during a BA 5 reference search and fails to find its reference, check the BERO precontact transition and the encoder R pulse separately. Establish safe test conditions before approaching the travel limits.

If the PLC reports 54 or COM 246 shows B6, the actual position did not change after the analogue speed demand crossed the 5 V threshold. Check the L+ supply, drive enable, X6 speed reference and X4/X5 feedback in that order.

Siemens PDF documents

+ IP 246 / COM 246 manual – 6ES5 998-5SA23 (EN)

+ IP 246 / COM 246 manual – 6ES5 998-5SA13 (DE)

+ SIMATIC S5 shared PDF archive

Related topics

+ IP 246I 6ES5 246-4UA31 incremental version

+ IP 246A 6ES5 246-4UB21 absolute version

Navigation

+ S5 positioning modules

+ SIMATIC S5

+ Siemens S5 PLC

+ Used Siemens equipment