6ES5 374-0BA11

Siemens 6ES5 374-0BA11 – SIMATIC S5 Special EPROM Submodule for IP 252

The Siemens 6ES5 374-0BA11 is a special EPROM memory submodule in the SIMATIC S5 374 range, listed for the IP 252 closed-loop control module. The IP 252 has an X3 user memory socket on its front panel for this type of submodule. The exact part listings do not specify the 0BA11’s memory capacity or controller structure.

In a motor speed control loop, for example, the IP 252 compares the measured feedback with the setpoint and produces a command signal for the drive. The IP 252 runs the control loop. The fitted memory submodule holds the software that defines the controller structure.

X3 memory socket, programmer port and field signals

Siemens identifies the front connections of the IP 252 separately in its documentation for S5 function modules. X3 is the memory socket, X4 is the incremental encoder input, X5 is the programmer port and X6 carries the analog I/O. The 8 analog inputs and 8 analog outputs specified in the manual are channels on the IP 252 itself.

The 6ES5 252-3AA11 and 6ES5 252-3AA13 are separate IP 252 order numbers. Record the host module’s full order number and hardware revision, the S5 rack and the memory code fitted in X3. The S5-115U installation described in the manual uses an adapter casing for the IP 252.

How the 0BA11 differs from the 0AA11 and 0AB11

The Siemens manual lists drive and standard controller structures, designated DR/SR, for the 6ES5 374-0AA11. The 6ES5 374-0AB11 is the DRS/SR version with an extended, self-adjusting drive controller. Part listings identify the 0BA11 as a special version. When selecting a spare, check the full suffix and the machine’s controller structure alongside the EPROM type and connector format.

Retained settings, working memory and COM REG

The IP 252 family manual describes a submodule design with controller firmware in EPROM and retained controller parameters in EEPROM. Live measurements and previous values used in control calculations reside in the IP 252’s working RAM. The battery backup described in the manual applies to the IP 252’s RAM and is supplied through the PLC power supply.

Keep the CPU’s STEP 5 application and the IP 252’s COM REG project as separate maintenance records. At startup, the IP 252 checks the memory identifier. The module can remain in STOP if it fails to recognize a valid identifier. During fault diagnosis, use the appropriate PG connection to check the memory identification and configuration.

Editor’s note

Photograph both labels. Make sure the full 374-0BA11 and IP 252 order numbers are readable, along with any revision marking.

Save the machine’s settings. Keep the loop channel assignments and commissioning values with the COM REG project.

Record when the module went into STOP. If the fault appeared immediately after a card change, begin with the memory identifier and the suffix on the installed card.

Ask how a used card was tested. Find out which IP 252 hardware recognized it and which COM REG project was used to test the controller structure.

Trace the signal through the loop. During the planned commissioning check, verify the measured value, setpoint and corresponding analog output on the same loop.

OtomasyonAVM resources and PDFs

Find the COM REG manual on our IP 252 product and documentation page. For other S5 systems, see the S5 PDF archive and our Siemens S5 PLC guide.

Related topics

IP 252 DR/SR memory submodule · IP 252 6ES5 252-3AA11 · PID speed control